Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop B
Sequence Number 5
Notes
Date Text
2006-03-29 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
  
 PRODUCT APPROVAL PROVISOS:
  
  
 -PROVISO-
 STAIRWELL DOORS S1, R1 AND R15. SHEET
 A9.11, DOOR SCHEDULE, SHOWS THESE DOORS
 AS TYPE I, WHICH HAS A 10"X 10" VISION
 PANEL.THE SUBMITTED STATEWIDE PRODUCT
 APPROVAL FL2167 GIVES DESIGN WIND
 PRESSURES OF +65 PSF AND -65 PSF WITH
 THE RIM EXIT DEVICE (SEE DRAWING SHEET 3
 OF THE PRODUCT APPROVAL NOA# 02-0523.06
 THAT WAS SUBMITTED WITH THE STATEWIDE
 APPROVAL).THOSE PRESSURES ARE EXCEEDED
 BY THE WIND PRESSURES ON THE BUILDING AT
 THESE LOCATIONS.SUBMIT A PRODUCT
 APPROVAL FOR DOORS WITH ADEQUATE DESIGN
 WIND PRESSURES.
  
 -PROVISO-
 LOUVERS, SHEET A8.44.GRILLE/LOUVER
 TYPE N IS SHOWN AS 10'-3" HIGH ON THE
 LOUVER AND GRILLE SCHEDULE.THAT
 HEIGHT EXCEEDS THE MAXIMUM ALLOWED IN
 BOTH OF THE TWO SUBMITTED PRODUCT
 APPROVALS (FL4352 AND FL5160).AMEND
 THE SIZE OR SUBMIT AN APPROPRIATE
 PRODUCT APPROVALS.
  
 -PROVISO-
 AUTOMATIC SLIDING MAIN ENTRY DOOR.ON
 SHEET A8.41 THE UNIT HEIGHT IS SHOWN AS
 8'-0" WHICH EXCEEDS THE 7'-8" HEIGHT
 SHOWN IN THE SUBMITTED STANLEY ACCESS
 TECHNOLOGIES STATEWIDE PRODUCT APPROVAL
 FL6249 (SEE DRAWING SHEET 1 OF NOA#
 04-1026.02, SUBMITTED WITH THE STATEWIDE
 PRODUCT APPROVAL).EITHER AMEND THE
 HEIGHT SHOWN ON THE PLANS OR SUBMIT A
 PRODUCT APPROVAL SHOWING A DOOR HEIGHT
 NO LESS THAN THAT STATED ON THE PLANS.
  
 -PROVISO-
 SINGLE HUNG WINDOW, SHEET A8.41 SHOWS
 WINDOW TYPES W-2 AND W-2A AS 10'-1" TALL
 FROM FLOOR TO HORIZONTAL MULLION.THIS
 EXCEEDS THE MAXIMUM 9'-2" SHOWN IN THE
 SUBMITTED RC ALUMINUM STATEWIDE PRODUCT
 APPROVAL FL3398 (SEE DRAWING SHEET 1 OF
 NOA# 03-1216.06, SMALL MISSILE IMPACT
 AND NOA# 03.1216.04, LARGE MISSILE
 IMPACT).SUBMIT ALTERNATIVE OR
 ADDITIONAL PRODUCT APPROVALS TO COVER
 THE PROPOSED MAXIMUM WINDOW HEIGHT.
  
 -PROVISO-
 FIXED WINDOW, SHEET A8.41.DUE TO THEIR
 LOCATION ON THE BUILDING, WINDOW TYPES
 W-3 AND W-3.2 WILL BE SUBJECT TO 140 PSF
 NEGATIVE WIND PRESSURE.THE MAXIMUM
 NEGATIVE PRESSURE ALLOWED BY THE
 SUBMITTED EFCO STATEWIDE PRODUCT
 APPROVAL FL1520 IS 130 PSF (SEE DRAWING
 SHEET 1 OF NOA# 02-0410.04 SUBMITTED
 WITH THE STATEWIDE PRODUCT APPROVAL).
 SUBMIT AN ADDITIONAL OR ALTERNATE
 PRODUCT APPROVAL TO COVER THE WIND
 PRESSURES THAT THE WINDOWS WILL BE
 SUBJECTED TO.
  
 -PROVISO-
 STOREFRONT, SHEET A8.41.ALL THREE OF
 THE SUBMITTEDTHE SUBMITTED GAMMA
 U.S.A. WINDOW WALLPRODUCT APPROVALS
 ARE FOR SMALL MISSILE IMPACT LOCATIONS.
 NO APPROPRIATE PRODUCT APPROVAL HAS BEEN
 SUBMITTED FOR THE STOREFRONT WINDOWS
 (AND DOORS) ON THE FIRST FLOOR WHICH ARE
 IN THE LARGE MISSILE IMPACT ZONE. SUBMIT
 PRODUCT APPROVAL(S) FOR LARGE MISSILE
 IMPACT STOREFRONT WINDOWS (AND DOORS).