| Date |
Text |
| 2006-02-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: (FROM 1ST REVIEW) |
| | |
| | 12) SHT A4.41 KITCHEN SINK & JUICE BAR |
| | SINK IN COMMON AREAS SHALL COMPLY WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | SUBMIT A DETAIL. RESPONSE NOTED, BUT NO |
| | DETAIL WAS FOUND. - THIS WILL BE A FIELD |
| | INSPECTOR APPROVAL. IF COMMON USE AREA |
| | IS AVAILABLE TO TENANTS AND GUESTS, ALL |
| | REQUIREMENTS OF SECTION 11-4.24 WILL BE |
| | ADHERED TO. - DETAIL SUBMITTED IS FOR |
| | THE DWELLING UNITS. SINKS INDICATED |
| | SHALL COMPLY AS REQUIRED IN SECTION |
| | 11-4.24 AND ALL SUBSECTIONS. SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.24.2/HEIGHT, 11-4.24.3/KNEE |
| | CLEARANCE, 11-4.24.4/SINK DEPTH, |
| | 11-4.24.5/CLEAR FLOOR SPACE (FORWARD |
| | APPROACH), 11-4.24.6/EXPOSED PIPES & |
| | SURFACES, & 11-4.24.7/FAUCETS. |
| | |
| | SECOND REVIEW |
| | **************NEW COMMENTS************** |
| | |
| | 52B) SHT P2.26 UNIT E1 FLOOR PLAN DOES |
| | NOT REFLECT THE RISER DIAGRAM. SECTION |
| | 104.2.1. - RISER #60 SHOWS W/M'S & |
| | KITCHEN SINKS, BUT FLOOR PLAN SHOWS |
| | POWDER ROOMS 2ND, 3RD, & 4TH FLOORS. |
| | PLEASE CORRELATE RISER & FLOOR PLAN. - |
| | FLOOR PLAN SHOWS RISER #11 DOWN TO MEZZ. |
| | LEVEL, THEN CONNECTING TO RISER 60, BUT |
| | RISERS DO NOT SHOW THIS. PLEASE |
| | CORRELATE RISERS AND FLOOR PLAN.- |
| | THERE ARE TWO NUMBER 60 SANT. RISER |
| | DIAGRAMS. (SEE SHEETS P2.03, P2.09, |
| | P2.14, P2.20, P2.26, P2.32, & P2.38 FOR |
| | ONE RISER #60). (SEE SHEETS P2.05, |
| | P2.11, P2.16, P2.22, P2.29, P2.35, & |
| | P2.41 FOR THE OTHER RISER #60). THE |
| | FIRST RISER #60 SHOWS A SHOWER BATH FROM |
| | THE 6TH FLOOR UP, AND THE SECOND RISER |
| | #60 SHOWS W/M'S AND KITCHEN SINKS (WHICH |
| | REFLECT THE RISER DIAGRAM). PLEASE |
| | CLARIFY. (3.26, P3.29, P3.34, P3.35). |
| | 73B) SHT P2.39 ALL UNITS SHOW PIPING TO |
| | REFLECT RISERS. SECTION 104.2.1. - RISER |
| | #54 DOES NOT REFLECT THE FLOOR PLAN. |
| | (SEE SHT P3.21 SEALED 7-1-5) - THIS USED |
| | TO SHOW CORRECT FIXTURES, BUT WAS IN |
| | WRONG LOCATION. IT HAS BEEN CHANGED TO |
| | BATHROOM FIXTURES. PLEASE CLARIFY. - NOW |
| | SHEET HAS BEEN CHANGED AND DOES NOT |
| | REFLECT THE FLOOR PLAN INDICATED IN THE |
| | KEY PLAN AREA. NOT ALL UNITS ARE SHOWN. |
| | - NOW RISERS 1 & 2 ARE NOT SHOWN ON SHTS |
| | P2.02 & P2.08. - OFFSET SHOWN ON THE 5TH |
| | FLOOR, (P2.25), AND W/C PIPING DOES NOT |
| | REFLECT RISER 54A. DOES THIS THEN OFFSET |
| | BACK ON THE NEXT FLOOR? |
| | 94B) SHT P2.64 STORM DRAIN LINE RUNNING |
| | EAST TO WEST AND CONNECTING TO RISER |
| | (4)(5) SHALL SLOPE 1/4"/FT THE ENTIRE |
| | LENGTH. SECTION 704.1 - NOT ADDRESSED, |
| | INDICATE ON PLANS. - PIPE SIZE INCREASED |
| | TO 12" BUT STILL SHOWS 1/4"FT ON ONE |
| | LENGTH AND NOT ENTIRE RUN. PLEASE |
| | CLARIFY. |
| | 103B) SHTS P3.16 THRU P3.25 THE |
| | FOLLOWING SANITARY RISER DIAGRAMS WERE |
| | NOT LOCATED ON THE BUILDING DRAIN |
| | ISOMETRIC. 1, 2, 16, 8, (2 #8'S SHOWN), |
| | 10, 59, 12, 13, 14, 17, 15, 18, 19, 20, |
| | 21, 22, 72, 57, 75, 40, 41, 42, 37. - |
| | RISERS 12 THRU 22, 40 THRU 42 AND RISER |
| | 75 HAVE NOT BEEN LOCATED ON THE BUILDING |
| | DRAIN ISOMETRIC AS NOTED IN THE COMMENT |
| | RESPONSE. - RISERS 19, 20, 72, & 75 |
| | STILL NOT LOCATED ON BLDG DRAIN |
| | ISOMETRIC. COMMENT RESPONSE REFERS TO |
| | SHT P2.00. NO SHT P2.00 SUBMITTED. |
| | PLEASE CLARIFY. |
| | 108B) SHT P3.21 RISER 26/35 KITCHEN SINK |
| | NOT SHOWN, DOES NOT REFLECT THE FLOOR |
| | PLAN, WASH MACHINE/LAUNDRY SINK OFFSET |
| | TO THE RIGHT SIDE NOT TO THE LEFT, |
| | VENTING FROM LAV DOES NOT REFLECT FLOOR |
| | PLAN. SECTION 104.2.1. - RISER 26/35 NOT |
| | SPLIT AND RISER 26 NOT FOUND ABOVE THE |
| | 5TH FLOOR. PLEASE CLARIFY. - RISER 26 |
| | STILL DOES NOT REFLECT THE FLOOR PLAN. |
| | (P3.31). VENTING FROM LAV NOT ADDRESSED. |
| | RISER 26 NOT FOUND ABOVE THE 5TH FLOOR. |
| | SHT P3.31 STATES "FOR CONT. SEE P3.16". |
| | RISER 26 NOT FOUND ON P3.16. PLEASE |
| | CLARIFY. |
| | 109B) SHT P3.22 RISER 55 DOES NOT |
| | REFLECT THE FLOOR PLAN. SECTION 104.2.1. |
| | - STILL DOES NOT REFLECT FROM THE 6TH |
| | FLOOR UP. PLEASE CORRELATE RISER & FLOOR |
| | PLAN. RESPONSE INDICATES RISER 55 HAS |
| | BEEN CHANGED TO RISER 55A. WHY THE |
| | CHANGE. RISER IS SHOWN AS 55 & 55A. |
| | RISER 55 NOT LOCATED FROM THE 6TH FLOOR |
| | UP. RISER 55A DOES NOT REFLECT THE FLOOR |
| | PLAN. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THIRD REVIEW |
| | **************NEW COMMENTS************** |
| | |
| | 4C) SHT P2.39 UNIT B3 RISER 54 FLOOR |
| | PLAN DOES NOT REFLECT THE RISER DIAGRAM. |
| | - RISER 55 UNIT B1 NO REVENT TO RISER 27 |
| | SHOWN ON FLOOR PLAN. SECTION 104.2.1. |
| | 5C) SHT P2.40 UNABLE TO LOCATE RISER 56. |
| | SECTION 104.2.1. - NOW SHT P2.39 DOES |
| | NOT SHOW ALL UNITS. |
| | |
| | 19C) SEE ATTACHED SHEET CONCERNING THE |
| | DESIGN PROFESSIONAL AND FS 553.80(2)(B). |
| | THIS IS GIVEN AS A NOTICE ONLY. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | FORTH REVIEW |
| | ***************NEW COMMENTS************* |
| | |
| | 1D. SHTS P2.05, P2.11, & P2.16 SHOW |
| | RISER 76 ON ALL FLOORS FROM GROUND FLOOR |
| | BASE OF STACK. SECTION 104.2.1. |
| | 2D. SHTS P202 & P2.08 SHOW RISERS 1 & 2 |
| | ON ALL FLOORS FROM THE GROUND FLOOR BASE |
| | OF STACK. SECTION 104.2.1. |
| | 3D. SHT P2.13 VENT SHOWN ON RISER |
| | DIAGRAM NOT SHOWN ON THE FLOOR PLAN. |
| | (RISER 3,56,57). RISER AND FLOOR PLAN |
| | SHALL REFLECT EACH OTHER. SECTION |
| | 104.2.1. |
| | 4D. SHT P2.18 RISER 26 DOES NOT REFLECT |
| | THE FLOOR PLAN AT THE W/C OF THE POWDER |
| | ROOM. CORRELATE. SECTION 104.2.1. |
| | 5D. SHTS P2.21, P2.22, P2.23,. P2.50 & |
| | P2.52 HAVE DIFFERENT DATES ON THE SEAL, |
| | DIFFERENT INFORMATION. - IT SEEMS THAT |
| | THE 6-3-5 SHEETS HAVE MORE UP TO DATE |
| | INFORMATION THAN THE 7-14-5 SHEETS. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 6D. SHT P2.24 NOTE IN UNIT H6 STATES |
| | "SEE DRWG P2.20" PIPING LAYOUT NOT SHOWN |
| | ON SHT P2.20. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 7D. SHT P2.25 OFFSET NOT SHOWN ON THE |
| | 5TH FLOOR FLOOR PLAN AT RISER 54A, BUT |
| | IS SHOWN ON THE RISER DIAGRAM. PLEASE |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | 8D. SHT P2.28 VENTS FOR LAVS NOT SHOWN |
| | IN M/B UNIT B2. SECTION 104.2.1. |
| | 9D. SHT P2.33 UNIT BE NOTES STATE "FOR |
| | SANT. LAYOUT SEE UNIT B3 DRAWING P2.39". |
| | B3 UNIT NOT SHOWN ON P2.39. - SHOW |
| | KITCHEN SINK PIPING FOR UNITS J & H. |
| | SECTION 104.2.1. |
| | 10D. SHT. P2.34 SHOW RISER NUMBERS WHERE |
| | RISERS 30 & 32 DROP DOWN TO THE 5TH |
| | FLOOR. SECTION 104.2.1. |
| | 11D. SHT P2.35 UNIT B WASH MACHINE |
| | OFFSET NOT SHOWN ON RISER DIAGRAM. |
| | PIPING IS NOT SHOWN TO THE LAUNDRY BOX. |
| | CLARIFY. SECTION 104.2.1. |
| | 12D. SHT P2.39 NEW SHEET DOES NOT SHOW |
| | ALL UNITS INDICATED ON THE SHEET TITLE |
| | OF KEY PLAN SECTION. NEW SHEET REQUIRED. |
| | SECTION 104.2.1. |
| | 13D. SHT P2.43 VENT RISER "FROM" RISER |
| | 53 TO RISER 5 IS SHOWN AS "TO RISER 5E". |
| | THIS DOES NOT REFLECT THE RISER DIAGRAM. |
| | PLEASE CLARIFY/CORRELATE. SECTION |
| | 104.2.1. |
| | 14D. SHT P2.60 SECONDARY ROOF DRAINS ARE |
| | NOT SHOWN FOR THE DECK AREA. SECTIONS |
| | 104.2.1. & 1107. |
| | 15D. SHT P2.64 PIPE SIZING FOR THE NEW |
| | OVERFLOW DRAINS IS NOT CORRECT. IF THEY |
| | ARE SECONDARY DRAINS, THEN THEY SHALL BE |
| | CALCULATED FOR ALL DRAINS IN EACH AREA |
| | AND SHALL ALL BE 8". IF THEY ARE SCUPPER |
| | DRAINS, ALL BUT THE AREAS THAT DRAIN |
| | 3080SF & 3074SF SHALL BE 10". THE OTHER |
| | TWO SHALL BE 8". PLEASE CLARIFY. SECTION |
| | 1107 & ALL SUBSECTIONS. - 6" DECK DRAIN |
| | 3806SF SHOWS 816SF-A + 3990SF-V WHICH |
| | ADDS UP TO 4806SF & 6" DECK DRAIN 3619SF |
| | SHOWS 719A + 2099SF-V WHICH ADDS UP TO |
| | 2818SF. PLEASE RECHECK ADDITION ON |
| | DRAINS. SECTION 104.2.1. - MUCH OF THE |
| | VERTICAL CONTRIBUTION OF STORM WATER |
| | WILL BE DRAINING INTO THE PLANTERS. WILL |
| | THIS BECOME A NUISANCE PROBLEM. PLEASE |
| | INDICATE HOW THISWILL WORK. |
| | 16D. SHTS P3.01 THRU P3.16 ARE MISSING |
| | FROM ONE SET OF PLANS. SECTION 104.2.1. |
| | 17D. SHT P3.28 RISER 54A DOES NOT |
| | REFLECT THE FLOOR PLAN ON THE 5TH FLOOR. |
| | - RISER 3 VENT STACK ON THE 16TH FLOOR |
| | NOT APPROVED AS SHOWN. VENT MAY NOT |
| | TERMINATE ON THE 15TH FLOOR AND START |
| | AGAIN ON THE 16TH FLOOR. SECTIONS |
| | 104.2.1. & 903.3. |
| | 18D. SHT P3.26 RISER 64 MISNUMBERED AT |
| | 5TH FLOOR. (62) - INDICATE IF RISERS 48 |
| | & 50 ARE TYPICAL FROM THE 16TH FLOOR |
| | THRU THE 21ST FLOOR. SECTION 104.2.1. |
| | 19D. SHT P3.30 RISER DIAGRAM 50 DOES NOT |
| | REFLECT THE FLOOR PLAN 3RD & 4TH FLOORS. |
| | PLEASE CORRELATE. (P2.21) - RISER |
| | DIAGRAM 50/48 DOES NOT REFLECT THE FLOOR |
| | PLAN ON THE 16TH FLOOR. RISER 50 SHOWS |
| | NO FIXTURES FROM THE 16TH THRU THE 20TH |
| | FLOORS. - RISER 78 IS NOT INDICATED |
| | UNTIL THE 16TH FLOOR. SHOW RISER NUMBER |
| | FROM THE GROUND FLOOR UP. SECTION |
| | 104.2.1. |
| | 20D. SHT P3.39 THE TRENCH DRAINS ON THE |
| | 5TH FLOOR LANAI LEVEL ARE NOT SHOWN ON |
| | THE RISER DIAGRAM FOR THE STORM. PLEASE |
| | CORRELATE RISER AND FLOOR PLAN AND |
| | INDICATE SQUARE FOOTAGE DRAINED BY THE |
| | TRENCH DRAINS. SECTIONS 104.2.1 & 1106 |
| | AND TABLE 1106.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |