| 2006-01-30 00:00:00 | PLEASE CLARIFY THE FOLLOWING: |
| | COMMENT #1 FROM REVIEW DATED 9-1-05; |
| | PLAN SHEET M1.13 & A2.15 PAY-1 THROUGH 4 |
| | ARE LOCATED IN AREA THAT IS ENCLOSED. |
| | PER CONVERSATION WITH MATT, LOUVERS ARE |
| | NOT INSTALLED AT OPENINGS.PLEASE SHOW |
| | COMPLIANCE WITH 2001 FMC CHAPTER 11 |
| | SECTIONS 1102, 1103, 1104, & 1105. |
| | |
| | COMMENT #5 RESPONSE INDCIATES EXHAUST |
| | DUCTS THROUGH PLENUMS WILL BE SEPARATED |
| | BY A NON-RATED SEALED ENCLOSURE AS SHOWN |
| | IN DETAIL #2 PLANS SHEET A9.02.PLAN |
| | SHEET M2.01 APPEARS TO HAVE DRYER |
| | EXHAUST (COMBUSTIBLE) ALSO RUNNING |
| | THROUGH PLENUM. |
| | |
| | ADDITIONAL COMMENTS: |
| | PLAN SHEET A4.01 INDICATES 500 GAL FUEL |
| | TANK PER CONVERSATION WITH MATT, THE |
| | REMOTE FUEL TANK WAS ELIMATED.PLEASE |
| | REMOVE FROM PLANS. |
| | |
| | PLAN SHEET A7.09 DETAIL FOR STAIR #4 |
| | INDICATES "2 HR RATED ENCLOSURE" THROUGH |
| | THE STAIRWELL.PLEASE CLARIFY WHY THIS |
| | ENCLOSURE IS NECESSARY.PLEASE NOTE, |
| | THE ONLY PENETRATIONS ALLOWED THROUGH OR |
| | INTO A STAIRWAYS ARE THE ITEMS LISTED |
| | UNDER 2001 FBC 1006.1.3.1.THE CODE |
| | DOES NOT ALLOW ANY PENETRATIONS WHETHER |
| | RATED OR NOT, IT STILL IS PENETRATING |
| | THE STAIRWAY. |
| | |
| | PLEASE CLARIFY THE DESIGNATION OF FIRE |
| | DAMPERS AND FIRE/SMOKE DAMPERS.SOME |
| | PENETRATIONS ONLY INDICATE FIRE DAMPERS |
| | WHEN IN FACT THEY SHOULD READ FIRE/SMOKE |
| | DAMPERS. |
| | |
| | PLEASE HAVE THE ADDITIONAL COMMENTS |
| | ADDRESSED WITH NEXT SUBMITTAL OR |
| | REVISION. |
| | |
| | PLEASE ALSO SEE COMMENTS #19 THROUGH 28 |
| | BY ASST FIRE MARSHALL, MIKE CARSILLO. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |