| 2006-01-23 00:00:00 | 19. PLEASE EXPLAIN "OR THROUGH THE |
| | ANNUNCIATION OF AT LEAST THREE (3) AREA |
| | WIDE SMOKE DETECTORS SERVING A SMOKE |
| | CONTROL ZONE". (SMOKE CONTROL OPERATION |
| | PAGE M7.01.) WHY WILL IT TAKE THREE |
| | SMOKE DETECTORS TO OPERATE. |
| | |
| | 20. PLEASE INCLUDE NOTE TO PAGE M7.01 |
| | "ANTICPATED STACK EFFECT" REGARDING |
| | STAIR PRESSURIZATION. |
| | |
| | 21. FIRE SPRINKLER PROTECTION REQUIRED |
| | BELOW DUCTWORK THAT IS GREATER THAN 48" |
| | WIDE. |
| | |
| | 22. THE EMERGENCY GENERATOR TERMINATION |
| | EXHAUST DUCT POINT SHALL BE LOCATED WITH |
| | RESPECT TO WINDOWS, DOORS OR SUPPLY AIR |
| | OPENING. ALSO ARCHITECTURAL FEATURES CAN |
| | CAUSE A BACKFEED CONDITION. |
| | |
| | 23. ALL FIRE DAMPERS ARE TO BE DROP |
| | TESTED AND CERTIFIED AFTER INSTALLATION. |
| | |
| | 24. COOLING TOWERS TO COMPLY WITH NFPA |
| | 214. |
| | |
| | 25. TWO DAMPERS APPEAR TO BE SHOWN ON |
| | DRAWING BUT ARE NOT CALLED OUT ON PAGE |
| | M2.09. |
| | |
| | 26. A DAMPER IS SHOWN ON PAGE M2.03 DOES |
| | NOT APPEAR TO BE CALLED OUT. |
| | |
| | 27. WILL THE HORIZONTAL MEMBERS OF THE |
| | TRELLIS HAVE AN EFFECT ON SEF-1, SHOWN |
| | ON THE SECTION 1, PAGE M1.13. |
| | |
| | 28. THE SMOKE SYSTEM AND STAIRWELL |
| | PRESSURIZATION SYSTEMS SHALL BE TESTED |
| | PRIOR TO REQUESTING A TCO OR CO AND BOTH |
| | SYSTEMS MUST BE APPROVED BY CITY |
| | OFFICIALS. |
| 2006-01-06 00:00:00 | 1. ALL EXIT ACCESS AREAS AND EXIT DOORS |
| | SHALL BE PROVIDED WITH EXIT SIGNS. SOME |
| | ELECTRICAL SHEETS APPEAR TO BE MISSING |
| | EXIT SIGNS. |
| | |
| | 2. NO EXIT SIGNS SHOWN ON MAIN ROOF |
| | LEVEL WEST. E2.19. THE SAME CONDITION |
| | MAIN ROOF LEVEL EAST. |
| | |
| | 3. THERE APPEARS TO BE A DISCREPANCY |
| | BETWEEN SOME DRAWING SHEETS. ON ONE |
| | SHEET THE SMOKE MANAGEMENT PANEL IS |
| | MISSING FROM THE FIRE COMMAND ROOM AND |
| | ANOTHER PAGE IT IS SHOWN. |
| | |
| | 4. THE REQUIRED FIRE ALARM SYSTEM SHALL |
| | BE MONITORED BY A UL LISTED CENTRAL |
| | STATION APPROVED FOR CENTRAL STATION |
| | SERVICE. |
| | |
| | 5. FIRE SPRINKLER HEADS SHALL BE QUICK |
| | RESPONSE OR BE RESIDENTIAL TYPES. |
| | |
| | 6. STANDPIPES SHALL PROVIDE COVERAGE TO |
| | ALL ARES OF THE BUILDING. ALL REQUIRED |
| | STAIRWELLS ARE REQUIRED TO HAVE |
| | STANDPIPES. |
| | |
| | 7. ALL ELEVATORS THAT CAN BE USED FOR |
| | STRETCHERS SHALL BE IDENTIFIED. |
| | |
| | 8. DOOR MISSING FROM EXIT PATH FROM |
| | ELEVATOR VESTIBULE # 3 UP THE STAIRS AND |
| | APPEARS TO TRAVEL BEHIND PARKING SPACE. |
| | PLEASE SEE PAGE LS1.03. |
| | |
| | 9. PLEASE VERIFY DOOR SWINGS IN |
| | HORIZONTAL EXITS SHOWN ON PAGE LS1.03. |
| | |
| | 10. EXIT SIGNS ON POOL DECK SHALL NOT |
| | EXCEED 100 FEET. PLEASE SEE LS1.10. |
| | |
| | 11. PLEASE PROVIDE FLAMESPREAD DATA ON |
| | "THERMOCON SPRAY -ON INSULATION SHOWN ON |
| | PAGE A4.02. |
| | |
| | 12. THE "3-0 WIDE PEDESTRIAN PASS GATE |
| | MUST BE LABELED AS AN EXIT. WHEN THE |
| | VEHICULAR SECTIONAL GATE IS DOWN ONLY |
| | ONE EXIT APPEAR VISIBLES FROM THE THAT |
| | SPECIFIC PARKING AREA. PLEASE SEE A4.11. |
| | |
| | 13. PLEASE EXPLAIN CARD READERS SHOWN ON |
| | PAGE A4.14. WILL THEY POSE ANY PROBLEMS |
| | WITH REGARDS TO EXITING. |
| | |
| | 14. CARD READERS NOTED IN SEVERAL PLACES |
| | ON DOOR SCHEDULE. PLEASE NOTE ON THE |
| | PLANS HOW THESE DEVICES WILL NOT |
| | INTERFERE WITH EXITING REQUIREMENTS. |
| | |
| | 15. MECHANICAL ACCESS SPACES SHOWN ON |
| | SEVERAL A PAGES. PLEASE PROVIDE DETAILS. |
| | |
| | 16. POOL DECK FLOOR HAS A DOOR THAT |
| | OPPOSES ONE OF THE POOL PUMP ROOM DOOR. |
| | PLEASE SEE PAGE A7.05A |
| | |
| | 17. MORE DETAILS NEEDED ON NON-RATED |
| | METAL MESH PARTITION SHOWN ON PAGE |
| | A7.03. |
| | |
| | 18. ON SOME OF THE REFLECTED CEILING |
| | PLANS, SMOKE DETECTORS APPEAR TO BE |
| | DIRECTLY NEXT TO HVAC DIFFUSERS. THE |
| | MINIMUM THREE FOOT RULE IS TO APPLY. |
| | |
| | NOTE: MECHANICAL DRAWINGS WILL BE NEXT |
| | SET OF DRAWINGS TO BE REVIEWED BY THIS |
| | OFFICE. |