| 2007-08-17 11:21:58 | REV 13R |
| | THE FOLLOWING PAGES WERE REVIEWED AND PASSED: |
| | M2.12, M2.25, M2.26C, M2.26E |
| | |
| | THE FOLLOWING PAGES WERE DENIED WITH COMMENTS: |
| | M2.22, M2.26A, M2.26B, M2.26D, M2.26F |
| | |
| | ONE COPY OF PASSED PAGES WAS RETAINED FOR PERMIT |
| | RECORDS. ONE COPY OF DENIDE PAGES WAS RED-LINED TO |
| | ASSIST IN UNDERSTANDING THE LOCATION AND NATURE OF |
| | WRITTEN REVIEW COMMENTS. |
| | |
| | 1. M2.22 UNIT D1: THERE IS NO RETURN GRILL IN THE |
| | PLENUM. PLEASE CORRECT. |
| | |
| | 2. M2.26A- |
| | UNITS C AND L: MISSING RETURNS IN BEDROOM #2. FBC,M |
| | 601.4 |
| | UNITS B5 AND B6: PLAN SHOWS 14X14 R/A IN CEILING OF |
| | MASTER BEDROOM FOR WHAT PURPOSE? PLEASE CLARIFY. |
| | |
| | 3. M2.26B- |
| | UNIT G1: CONTAINS NOTE FOR FLEX DUCT TO OFFSET DRYER |
| | EXHAUST. FLEX DUCT SHALL NOT BE USED IN CONCEALED |
| | SPACES. FBC,M 504.6. ALSO IN G1, 16X16 R/A GRILL IN |
| | MASTER BEDROOM HAS NO DUCT OR PLENUM OR OTHER WAY FOR |
| | AIR TO RETURN FROM ROOM. |
| | UNIT D1, THERE IS NO RETURN GRILL IN PLENUM CEILING. |
| | UNIT C2, 12X12 R/A FOR MASTER BEDROOM IS NOT LOCATED |
| | WITHIN THE CEILING PLENUM SPACE. |
| | |
| | 4. M2.26D UNIT J: THERE IS NO DEFINED CEILING PLENUM |
| | AREA SHOWN ON PLAN. PLEASE CORRECT. |
| | |
| | 5. M2.26F UNIT C1: NO FIRE RATING OR OPENING |
| | PROTECTIVES ARE SHOWN WHERE THE PLENUM EXTENDS INTO THE |
| | CORRIDOR. PLEASE CORRECT. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: |