| 2008-03-15 21:01:21 | PG. E2.02THE TWO A/CS IN P1 SHOW OCP THAT |
| | VIOLATES THE NAMEPLATE OF THE UNITS PLEASE CORRECT OCP |
| | FOR UNITS |
| | |
| | PG. E2.02SHOWS TWO SWITCHES TO FIXTURES ABOVE, |
| | ARE THESE FIXTURES IN THE SAME ROOM? PLAN IS |
| | CONFUSING. |
| | |
| | PG. E4.01 COMMUNICATION ROOM SHOW TAILS TO |
| | EQUIPMENT, HOW DO YOU KNOW TAILS WILL BE LARGE ENOUGH |
| | (AMPEREAGE)? |
| | YOU WILL NEED TO SUPPLY |
| | EQUIPMENT DETAILS FOR SIZING BRANCH CIRCUITS.ALSOL |
| | NEED TO SHOW EQUIPMENT ON PLANS. |
| | |
| | PG. E6.01LOOKING AT REV1 FOR THE GENERATOR SHOWS |
| | TWO BREAKERS BUILTIN, ON JOB ONE WAS ADDED TO |
| | GENERATOR, PLEASE HAVE GENERATOR RELISTED TO SHOW ONE |
| | INTERNAL |
| | AND ONE EXTERNAL. |
| | |
| | PG. E6.08, E6.09SHOWS TWO 4" CONDUITS STUBBING INTO |
| | THE CORIDOOR CEILING, DO YOU WANT ACCESS PANELS IN THE |
| | CORIDOOR CEILING TO BE ABLE TO ACCESS PIPES? |
| | SHOWS A 20 DEDICATED |
| | CIRCUIT TO COMMUNICATIONS PANEL IN BEDROOM CLOSET. THIS |
| | NEEDS TO BE AFCI PROTECTED.210.12 |
| | SHOWS A CADWELL PLATE FOR |
| | GROUNDING, IS THIS JUST A TYPE OR ARE THE WIRES TO BE |
| | CADWELDED TO THIS BAR? |
| | |
| | PG. E7.14TRANSFORMER THAT FEEDS LGHE IS PROTECTED ON |
| | PRIMARY BY 3 POLE 25A BREAKER, AND SECONDARY HAS 100A. |
| | THERE IS NOT A 100A AVAILABLE ON THE SECONDARY SIDE |
| | PRIMARY HAS ROOM FOR 2.7 AMPERES. I WILL LOOK INTO THIS |
| | FURTHER AND GET BACK TO YOU BUT I DON'T FEEL THAT THE |
| | SECONDARY SHOULD BE PROTECTED BY 100A MAIN |
| | WHEN THERE IS NO ROOM FOR FUTURE |
| | EXPANSION.IF LOAD GOES TO 100% THE 25AMP MAIN SHOULD |
| | TRIP. |