| 2007-07-23 10:13:52 | THE FOLLOWING PAGES WERE REVIEWED AND STAMPED: |
| | |
| | M1.01 THROUGH M1.12, M2.14, M2.15, M2.16, M2.19A, |
| | M2.20B, M3.02, M3.03, M3.04 |
| | |
| | THE FOLLOWING PAGES WERE DENIED WITH COMMENTS: |
| | |
| | 1. M2.05: EF-A IN JANITOR'S CLOSET, DUCT PASSES THROUGH |
| | MECHANICAL ROOM WHICH IS A PLENUM. EXHAUST DUCTS UNDER |
| | POSITIVE PRESSURE SHALL NOT PASS THROUGH A PLENUM. |
| | FBC,M 601.3 |
| | |
| | 2. M2.05: EXHAUST DUCT PENETRATION AT MECHANICAL ROOM |
| | RATED WALL REQUIRES A FIRE DAMPER. IT DOES NOT MEET ALL |
| | CONDITIONS OF THE EXCEPTION UNDER FBC,M 607.1.3 UNLESS |
| | THE DUCT IS INTALLED ABOVE A CEILING. SEE ITEM (4) OF |
| | THIS SECTION. |
| | |
| | 3. M2.13: UNIT VV, THERE IS NO DUCT SHOWN ON PLANS |
| | FEEDING THE 8X6 SUPPLY REGISTER IN THE MASTER BEDROOM. |
| | PLEASE CORRECT. |
| | |
| | 4. M2.17: UNIT H4, PORTIONS OF SUPPLY TRUNK ARE MISSING |
| | FROM PLAN. PLEASE CORRECT. |
| | |
| | 5. M2.18: UNIT V1, PLAN SHOWS INLINE BACKDRAFT DAMPER |
| | IN EXHAUST DUCT. IS THIS FOR BATH EXHAUST ONLY OR ALSO |
| | FOR DRYER? IS THE INLINE BACKDRAFT DAMPER LISTED FOR |
| | USE IN A DRYER EXHAUST DUCT? DRYER EXHAUST DUCT IS TO |
| | BE FREE OF OBSTRUCTIONS AND HAVE A SMOOTH INTERIOR |
| | SURFACE. SEE FBC,M 504.4 AND 504.6. ALSO, HAS THERE |
| | BEEN A SUBMITTAL FOR THE "CUBE CORE GRILL" FOR USE ON |
| | DRYER EXHAUST? THE GRILL FOR BATH EXHAUST REQUIRES A |
| | SCREEN (FBC,M 401.6) AND A SCREEN IS PROHIBITED ON |
| | DRYER EXHAUST OUTLETS (FBC,M 504.4). |
| | |
| | 6. M2.19: MOTORIZED DAMPER 5-1-2 IS NO LONGER SHOWN IN |
| | DUCT, BUT THE DESIGNATION AND NOTE ARE STILL ON THE |
| | PLAN. IS THE SMOKE CONTROL SYSTEM BEING REVISED OR IS |
| | THE DAMPER MISTAKENLY OMITTED? |
| | |
| | 7. M2.19: GRILL AND DUCT SIZE MISSING FROM TWO DROPS IN |
| | MULTI USE ROOM AND KITCHEN. |
| | |
| | 8. M2.19B: UNIT C2, PROVIDE NOTE REGARDING EXHAUST |
| | DUCTS IN RETURN AIR PLENUM. WILL THE SYSTEM WHICH WAS |
| | SUBMITTED AS AN ALTERNATE MATERIAL/METHOD FOR EXHAUST |
| | IN A PLENUM WORK IN THIS CASE, WHERE THE EXHAUST FAN |
| | ITSELF IS LOCATED IN THE PLENUM? PLEASE PROVIDE DETAIL. |
| | FBC,M 601.3 |
| | |
| | 9. M2.20: COMMON AREAS ARE NOT SHOWN ON PLAN AS HAVING |
| | BEEN REVISED. HOWEVER, THE AREA CONTAINS SEVERAL |
| | CHANGES FROM PREVIOUS APPROVED PLANS. PLEASE INDICATE |
| | ALL AREAS WHICH ARE PART OF THIS REVISION. |
| | |
| | 10. M:20A: SAME AS COMMENT #10. COMMON AREA DUCT |
| | SYSTEMS WHICH ARE SHOWN IN THEIR ENTIRETY ON PG M2.20 |
| | MAY BE OMITTED FROM THIS PAGE, OR THE AREAS BEING |
| | REVISED MUST BE CLEARLY IDENTIFIED. |
| | |