| 2005-09-01 00:00:00 | DENIED: |
| | 1.PLAN SHEET M1.13 & A2.15, PLAN |
| | INDICATES PAU-1 THROUGH 4 ARE LOCATED IN |
| | AREA THAT IS ENCLOSED.PLEASE PROVIDE |
| | MANUFACTURER'S INTALLATION/SUBMITALL |
| | DATA FOR REVIEW.OA PACKAGE UNITS ARE |
| | TYPICALLY LOCATED OUTDOORS. |
| | |
| | 2.PLEASE CLARIFY RATIONALE FOR THE |
| | SPF-3 (STAIRWELL PRESSURIZATION) IS THIS |
| | DUCTED TO THE OA LOUVER?PLAN INIDCATES |
| | EF-R-2 (POOL DECK ATTIC) EXHAUSTING INTO |
| | THE SAME ROOM AS PAU-1 & SPF-3.PER |
| | 2001 FBC(M)501.3, MECHANICAL EXHAUST |
| | SYSTEMS SHALL TERMINATE OUTDOORS AT A |
| | POINT WHERE IT CANNOT BE RECIRCULATED BY |
| | THE VENTILATING SYSTEM. FRESH AIR IS TO |
| | BE TAKEN FROM THE OUTDOORS WHICH |
| | ACCORDING TO THE DEFINITION; OUTDOORS, |
| | NOT ENCLOSED; HAVING NO ROOF. |
| | PLEASE VERFIY ALL AREAS WHERE OUTSIDE |
| | |
| | AIR LOUVERS ARE LOCATED. |
| | |
| | 3.PLAN SHEET M2.01, DOMESTIC WATER |
| | PUMP ROOM AND THE FIRE PUMP ROOM |
| | INDICATE OUTSIDE AIR FROM THE GARAGE |
| | AREA & EXHAUST ALSO GOING INTO THE |
| | GARAGE AREA.PER 2001 FBC(M)401.5.1, |
| | OUTSIDE AIR INTAKES SHALL BE LOCATED A |
| | MINIMUM OF 10FT FROM PARKING LOTS, |
| | STREETS, ALLEYS, AND LOADING DOCKS. |
| | |
| | 4.PLAN SHEET M2.01 REFERS TO THE ARCH |
| | DWGS., PLEASE SPECIFY SHEET NUMBER. |
| | PROVIDE DETAIL OF THE SEALED ENCLOSURE. |
| | |
| | 5.PLAN SHEET M2.02 UNIT GENERAL NOTES |
| | #1; AKK TOILET EXHAUST RUNNING INSIDE |
| | PLENUMS SHALL BE WRAPPED.PLEASE |
| | CLARIFY, ONLY DRYER EXHAUST DUCTS WILL |
| | BE ENCLOSED SEPERATELY?PER 2001 FBC(M) |
| | 601.3, EXHAUST DUCTS UNDER POSITIVE |
| | PRESSURE & VENTING SYSTEMS SHALL NOT |
| | EXTEND INTO OR PASS THROUGH PLENUMS. |
| | PLANS STILL INDICATE EXHAUST DUCT |
| | THROUGH PLENUMS WITHOUT THE NOTE |
| | INDICATING A SEPERATE ENCLOSURE. |
| | |
| | 6.PLANS INDICATE DRYER BOOSTER FANS |
| | WERE DELETED IN LEIU OF A SPECIFIC |
| | DRYER.PLEASE NOTE, SPECIFIC DRYER TO |
| | BE INSTALLED AT FINAL INSPECTION. |
| | DRYERS THAT EXHAUST GREATER THAN 2,000 |
| | CFM SHALL BE PROVIDED WITH MAKE-UP AIR, |
| | 2001 FBC(M)504.5. |
| | |