| Date |
Text |
| 2005-09-07 00:00:00 | ************ UNSAT 3ND REVIEW ********* |
| | |
| | PLEASE SEENOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | PLEASE ALSO SEESOME NEW NOTES. |
| | |
| | *************************************** |
| | PLEASE SEE FIRST AND SECOND PART OF |
| | NOTES IS DIRECTLY TAKEN FROM FIRST TWO |
| | REVIEW. PART 3 WILL BE NEW NOTES. |
| | *************************************** |
| | |
| | 1)NOTE: NOTE #1, OK, HOWEVER PLEASE SEE |
| | NOTE #19FROM SECOND REVIEW WHICH STILL |
| | HAS ONE COMMENT. |
| | |
| | 2)NOTE: NOTE #2 OK |
| | |
| | 3)NOTE: NOTE #3 OK |
| | |
| | 4)NOTE: NOTE #4 OK. |
| | |
| | 5)NOTE: NOTE #5 OK ON PREVIOUS REVIEW, |
| | HOWEVER PLEASE NOW SEE 2.04 WHICH SHOWS |
| | BOTH FPL VAULT AND MAIN ELECTRICAL RM |
| | BEING THE SAME ROOM? |
| | |
| | 6)NOTE: NOTE #6 OK, NO, PLEASE SEE |
| | RESPONSE LTR FROM ENGINEER STATES |
| | SIGNAGE AND LOCATIONS, HOWEVER PLEASE |
| | SEE NOTES ADDED TO PLANS SEEMS TO HAV |
| | MISSED /OR HAVE FIRE COMMAND ROOM |
| | REMOVED FROM NOTE. PLEASE SEE NOTE FOR |
| | "ARC FLASH" COULD NOT BE LOCATED. |
| | |
| | 7)NOTE: NOTE #7,OK |
| | |
| | 8)NOTE: NOTE #8 OK. CORRECT, ADDED |
| | CIRCUITS. |
| | |
| | 9)NOTE: NOTE #9 OK. |
| | |
| | 10)NOTE: NOTE #10 OK, |
| | PLEASE SEE NEW NOTES PERTAINING TO FIRE |
| | ALAEM SHEETS AND CODES REFEERNCED. |
| | |
| | 11)NOTE: NOTE #11 OK. |
| | |
| | 12)NOTE: NOTE #12 OK, ARCHITECTURUAL |
| | RESPONSE MENTIONS FULL ACCESSIBILTY FROM |
| | GARAGE TO UNITS BY WAY OF RAMPS FOR THE |
| | ENTIRE LENGTH OF TRAVEL. THIS COMMENT |
| | NOW BECOMES A BUILDING COMMENT AS NEC |
| | DOES NOT APPLY. IF THERE ARE ANY CHANGES |
| | TO DESIGN, PLEASE CORRELATE WITH |
| | ELECTRICAL PLANS. |
| | |
| | 13)NOTE: NOTE: OK |
| | |
| | 14)NOTE: NOTE: OK. |
| | |
| | 15)NOTE: NOTE #15 NO,PLEASE SEE NOTE #44 |
| | FROM SECOND REVIEW. CIRCUITING FOR SD'S. |
| | |
| | 16)NOTE: NOTE #16 OK. |
| | |
| | 17)NOTE: NOTE #17 OK. |
| | |
| | 18)NOTE: NOTE #18 OK, HOWEVER PLEASE SEE |
| | NOTE# 49 FROM 2ND REVIEW. |
| | PLEASE ALSO SEE NEW NOTES ABOUT CATV AND |
| | TELEPHONE CABINETS. |
| | |
| | 19)NOTE: NOTE #19 NO, PLEASEUNIT "M" |
| | STILL INDICATES AN ADDITIONAL PANEL, |
| | SEEM S TO BE A MISPRINT/OVERLAY PROBLEM. |
| | PANEL IN "LT GRAY". |
| | |
| | 20)NOTE: NOTE #20 OK, SEE PREVIOUS NOTE |
| | FOR PANEL IN UNIT "M". |
| | |
| | 21)NOTE: NOTE #21 OK. |
| | |
| | 22)NOTE: NOTE #22 NO, PLEASE SEE MANY |
| | UNITS HAVE BEEN REDLINED FOR AREAS IN |
| | QUESTION. PLEASE SEE 210.52C1-5 FOR |
| | REQUIRED LOCATIONS OF GFI RECEPTS ALONG |
| | KITCHEN COUNTERSPACES, INCLUDING |
| | PENINSULARS AND " SEPARATE SPACES". |
| | 210.52C2,4 |
| | PLEASE SEE MANY OF THESE WERE CORRECTED |
| | AND RECEPTS WERE ADDED, HOWEVER PLEASE |
| | SEE PLANS WHICH HAVE BEEN REDLINED FOR |
| | OTHER LOCATIONS. |
| | PLEASE SEE UNITS, V-1,E-1,A,J,H,P,P1,U, |
| | O, N. |
| | |
| | 23)NOTE: NOTE #23 NO, COULD NOT LOCATE |
| | NOTE REQUESTED FOR SD PLACEMENT ON |
| | PLANS. |
| | PLEASE CLARIFY WHERE THIS IS. |
| | PLEASE SEE RESPONSE LTR MENTIONS NOTE |
| | ADDED TO FIRE ALARM SHEET. |
| | PLEASE SEE E0.01, WHICH DID HAVE A NOTE |
| | FOR 3' MIN CLEARENCE FROM AIR DIFFUSERS, |
| | HOWEVER, PLEASE LIST 3' MIN FROM BATH |
| | AND KITCHEN DOORS, 20' FROM COOKING |
| | APPLIANCES. PLEASE SEE THERE ARE SD'S |
| | SHOWN W/IN 3' OF BATHROOM DOORS. |
| | PLEASE SEE REFERENCE TO NFPA-72 WAS |
| | INCORRECT. PLEASE SEE PROJECT WAS |
| | SUBMITTED FOR PERMIT AFTER JAN 1ST 2005, |
| | WHICH BRINGS NFPA-72 TO THE 2002 |
| | EDITION.PLEASE SEE CHAPTER 11.8.3.5 |
| | INSTALLATION SPEACIFICS. |
| | WRONG CODE WAS REFERENCED DUE TO PLANS |
| | ONLY BEING SUBMITTED FOR "PLAN REVIEW" |
| | BEFORE THE CODE CHANGE. THE REQUIREMENTS |
| | HAVE NOT CHANGED FOR THIS, ONLY THE |
| | CHAPTER NUMBER. |
| | PLEASE SEE NEW COMMENTS PERTAINING TO |
| | 2003 NFPA-101 |
| | |
| | 24)NOTE: NOTE #24 OK. |
| | |
| | 25)NOTE: NOTE #25 OK, NO JACUZZI TUBS AT |
| | THIS TIME PER ENGINNER. |
| | |
| | 26)NOTE: NOTE #26NO. PLEASE SEE NOTE |
| | WAS ADDED FOR FIRE PUMP AND LOCKED |
| | ROTOR, HOWEVER PLEASE SEE NO SPECS WERE |
| | SUBMITTED FOR FIRE PUMP OR FIRE PUMP |
| | CPNTROLLER. PLEASE ALSO SEE OTHER |
| | COMMENTS FROMFIRST AND SECOND REVIEW |
| | AND THIS REVIEW WHICH REQUESTED THIS |
| | WILL BE THE THIRD REVIEW REQUESTING |
| | THESE TO BE SUBMITTED IN TO REVIEW THESE |
| | DEVICES FOR CODE COMPLIANCE. |
| | ********SEE NEW NOTES FOR THIS**** |
| | |
| | 27)NOTE: NOTE #27 NO, PLEASE SEE ABOVE |
| | NOTE. PLEASE SEE NO SPECS FOR GENERATOR, |
| | SUB BASE FUEL TANK ATS WERE SUBMITTED. |
| | PLEASE SEE ABOVE NOTE AND NEW NOTES FOR |
| | 3RD REVIEW. |
| | PLEASE SEE NEW NOTES FOLLOWING. |
| | |
| | 28)NOTE: NOTE #28 OK. |
| | |
| | |
| | 29)NOTE: NOTE #29 OK. |
| | |
| | 30)NOTE: NOTE #30 OK. |
| | PLEASE SEE NEW NOTES: |
| | |
| | 31)NOTE: NO, PLEASE SEE RESPONSE LTR |
| | MENTIONS "WILL COMPLY" HOWEVER PLEASE |
| | SEE NEW NOTES PERTAINING TO NOTES ON |
| | PLANS AND SPECS. |
| | NO SEE NEW NOTES FROM SECOND REVIEW AND |
| | NEW FROM THIRD REVIEW. |
| | |
| | 32)NOTE: NOTE #32 OK, (NO)NOTE ADDED , |
| | GENERATOR WILL NOT BE SEPARATELY |
| | DERIVED. THIS WILL BE VERIFIED ONCE |
| | MANUFACTURE SPECS ARE SUBMITTED. |
| | SEE NEW NOTES AND PREVIOUS NOTES WITH |
| | RESPECT TO SHEETS FOR ALL REQUESTED |
| | EQUIPMENT AND CORRELATING WITH PLANS AND |
| | CODE COMPLIANCE. |
| | |
| | 33)NOTE: NOTE #33 OK. |
| | |
| | 34)NOTE: NOTE #34 NO, PLEASE SEE RISER |
| | DIAGRAM STILLDOES NOT INCLUDE A |
| | REDUCED "KEYED NOTES" OR RECDUCED |
| | "FEEDER SCHEDULE FOR REFERENCE WITHOUT |
| | HAVING TO TURN BACK AND FORTH FROM RISER |
| | DIAGRAM PAGE TO E-6.13. |
| | PLEASE SEE ONLY "KEYED NOTES ARE ON |
| | RISER SHEETS. PLEASE SEE REDLINED SET OF |
| | PLANS IN-WHICH A COPY OF THE FEEDER |
| | SCHEDULE WAS REDUCED AND PLACED ON RISER |
| | SHEETS 6.13. |
| | PLEASE MAKE CHANGES TO THIS , PLEASE SEE |
| | NEW COMMENTS PERTAINING TO "F" SCHEDULE |
| | AND CORRELATION WITH RISER AND PANEL |
| | SCHEDULES. |
| | 2ND PART TO NOTE#34, NO. PLEASE SEE |
| | NEW COMMENTS AS RISERS, BUS DUCT ETC |
| | STILL DO NOT CORRELATE. |
| | |
| | 35)NOTE: NOTE #35 OK. |
| | |
| | 36)NOTE: NOTE # 36 OK. |
| | |
| | 37)NOTE: NOTE #37 OK, PLEASE SEE |
| | FOLLOWING COMMENT WHICH STILL NEEDS TO |
| | BE ADDRESSED. |
| | |
| | 38)NOTE: NOTE #38 NO, PLEASE SEE |
| | PANELS STILL SHOWN AS 200A WITH 225A OCP |
| | FEEDING PANEL(S). |
| | PLEASE SEE PANEL FOR UNIT "M". |
| | |
| | 39)NOTE: NOTE #39 NO, PLEASE SEE WATER |
| | HEATERS SHOWN WITH 2P50A OCP FOR 4500VA |
| | UNITS ON #10 AWG.PLEASE SEE PANEL |
| | SCHEDULES, PANEL SCHEDULE "S" STILL |
| | SHOWS 50A OCP FOR 4.5KW WATER HEATER. |
| | PLEASE SEE NEW COMMENTS PERTAINING TO |
| | PANEL FOR UNIT "N". |
| | PLEASE SEE 422.13,422.11,240.4, 310.16 |
| | ETC. |
| | |
| | *************************************** |
| | NEW NOTES FOR REVIEW ** (2ND REVIEW) **. |
| | |
| | 40)NOTE: OK. |
| | |
| | 41)NOTE: OK, PLEASE SEE AN EMERGENCY |
| | BATTERY BACK UP TYPE OF FIXTURE WILL BE |
| | REQUIRED FOR FIRE COMMAND ROMM. SEE THIS |
| | AS NEW NOTE. |
| | |
| | 42)NOTE: NO, PLEASE SEE SOME UNITS FOR |
| | 2' OF WALL SPACE REDLINED AT LOCATIONS. |
| | (KITCHENS WALL SPACE 2' OR MORE. MOST |
| | BEDRM WERE DONE, PLEASE SEE ANY POSSIBLE |
| | LOCATIONS REDLINED FOR THESE. |
| | PLEASE SEE P, P1, P2. |
| | |
| | 43)NOTE: OK, NO FAN FOR DRYER TO BE |
| | ADDED PER ENGINEER. |
| | |
| | 44)NOTE: NO,PLEASE SEE MANY UNITS WHERE |
| | CIRCUITING WAS UPDATED DUE TO PREVIOUS |
| | COMMENTS FOR ARC FAULT PROTECTION, |
| | HOWEVER PLEASE SEE NOW MANY SMOKE |
| | DETECTORS ARE BEINGSHOWN TWO DIFFERENT |
| | CIRCUITS IN THE SAME UNITS. PLEASE SEE |
| | NFPA-72 11.5.1.1 WHICH REQUIRES SD'S TO |
| | BE WIRED "IN-LINE". MUTIPLE CIRCUITS FOR |
| | SD'S CAN NOT BE DONE. |
| | 2002 NEC 210.12 PLEASE BE SURE ARC FAULT |
| | CIRCUITS STILL CORRELATE AFTE UPDATING |
| | ANY CIRCUITING. |
| | PLEASE SEE ALL "OUTLETS" INCLUDING SD'S, |
| | LTS, FANS AND RECEPTS REQUIRED THIS. |
| | PLEASE SEE MANY OF THESE CIRCUIT #'S |
| | HAVE BEEN REDLINED ON PLANS, BUT NOT |
| | ALL. SEE UNITS, 15,V, V1, L, K, G, |
| | M,J,,, |
| | |
| | 45)NOTE: OK. FIXTURES REMOVED. |
| | |
| | 46)NOTE: OK, FIXTURE TYPE NOTED. |
| | |
| | 47)NOTE: OK. |
| | |
| | 48)NOTE: OK. |
| | |
| | 49)NOTE:OK. |
| | |
| | 49)NOTE:YE/ NO,PLEASE SEE MOST UNITS |
| | HAVE BEEN REVISED TO RE-LOCATE THESE |
| | PANELS, HOWEVER PLEASE SEE UNIT "Q" |
| | WHICH SHOWS THESE INWHAT APPEARS TO BE |
| | THE LINEN CLOSET. |
| | PLEASE SEE MANY CLOTHES CLOSETS |
| | CONTAINING COMBUSTIBLES ARE SHOWN WITH |
| | CATV AND TELEPHONE CABINETS. PLEASE SEE |
| | IF THESE UNITS WILL REQUIRE ANY "LV |
| | PLUG-IN" TYOE TRANSFORMERS THEN THESE |
| | RECEPTS WHICH ARE NOT SHOWN AT THIS TIME |
| | WOULD ONLY BE ALLOWED DIRECTLY OVER |
| | DOORS. |
| | |
| | 50)NOTE:NO, PLEASE SEE2002 210.8B3 |
| | FOR KITCHENS IN OTHER THAN DWELLING |
| | UNITS WHICH REQUIRES ALL 15- AND |
| | 20-AMPERE, 125-VOLT RECEPTACLES IN |
| | NON-DWELLING-TYPE KITCHENS TO BE GFCI |
| | PROTECTED. THIS REQUIREMENT APPLIES TO |
| | EACH AND EVERY 15- AND 20-AMPERE, |
| | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR |
| | NOT THE RECEPTACLE SERVES COUNTERTOP |
| | APPLIANCES. |
| | THIS WOULD BE FOR "HOUSE KITCHEN". |
| | |
| | 51)NOTE: OK, PLEASE SEE NOTES PERTAING |
| | TO 210.52, 210.52C1-5 |
| | |
| | 52)NOTE: OK. |
| | SEE NOTE WHICH WILL REQUIRE THE BATTERY |
| | BACK UP FIXTURE. |
| | |
| | 53)NOTE: OK, HOWEVER NOTES WITH RESPECT |
| | TO SPECS,/MANUFACTURE CUT SHEETS. PLEASE |
| | ALSO NEW NOTES WITH RESPECT TO DPHE. |
| | |
| | 54)NOTE: OK. |
| | |
| | 55)NOTE: OK, DETAIL SUBMITTED WHICH |
| | NOTES NEW GROUNDING TO BLDG GROUNDING |
| | ELECTRODE SYSTEM. |
| | |
| | 56)NOTE: OK, PLEASE KNOW, INFORMATION |
| | FOR ALL THIS ELEVATOR |
| | EQUIPMENT.DISCONNECTS ETC WILL BE |
| | REQUIRED TO BE REVISED BEFORE |
| | INSPECTIONS. NO CORRECTIONS NEEDED AT |
| | THIS TIME. |
| | |
| | 57)NOTE: OK. |
| | |
| | 58)NOTE: OK, HOWEVER SEE NEW NOTES TO |
| | FIRE PUMP FEEDERS NOW INDICATED. |
| | |
| | 59)NOTE: NO, PLEASE SEE BUST DUCTKEY |
| | NOTES ON 6.02 AND 6.03. PLEASE SEE K-3 |
| | WHICH MENTIONS CORRECTION, HOWEVER |
| | PLEASE SEE "K-7" WHICH SHOWS OLD. PLEASE |
| | SEE "SPEC BOOK", 16465 |
| | 2.2C WHICH MENTIONS ALUM BUS-DUCT WAS |
| | NOT REVISED. |
| | PLEASE SEE PREVIOUS NOTES IN REFERENCE |
| | TO EQUIPMENT GROUNDING METHOD OF |
| | BUS-DUCT. DOES THIS BUS-DUCT CONTAIN A |
| | SEPARATE ALUM BUS FOR GROUNDING? OR IS |
| | THE EQUIPMENT GROUNDING THAT IS GOING TO |
| | BE USED "PART" OF THE BUS-DUCT. |
| | *************************************** |
| | PLEASE SEE 2ND PART OF THIS NOTE COULD |
| | NOT BE LOCATED ON PLANS? |
| | *************************************** |
| | PLEASE ALSO PLACE NOTE ON PLANS FOR |
| | REQUIRED CURBS FOR FLOOR PENATRATIONS. |
| | PER 368.6BFLOOR PENETRATIONS SHALL |
| | COMPLY WITH (1) AND (2): |
| | BUSWAYS SHALL BE PERMITTED TO BE |
| | EXTENDED VERTICALLY THROUGH DRY FLOORS |
| | IF TOTALLY ENCLOSED (UNVENTILATED) WHERE |
| | PASSING THROUGH AND FOR A MINIMUM |
| | DISTANCE OF 1.8 M (6 FT) ABOVE THE FLOOR |
| | TO PROVIDE ADEQUATE PROTECTION FROM |
| | PHYSICAL DAMAGE. |
| | IN OTHER THAN INDUSTRIAL ESTABLISHMENTS, |
| | WHERE A VERTICAL RISER PENETRATES TWO OR |
| | MORE DRY FLOORS, A MINIMUM 100 MM (4 |
| | IN.) HIGH CURB SHALL BE INSTALLED AROUND |
| | ALL FLOOR OPENINGS FOR RISER BUSWAYS TO |
| | PREVENT LIQUIDS FROM ENTERING THE |
| | OPENING. THE CURB SHALL BE INSTALLED |
| | WITHIN 300 MM (12 IN.) OF THE FLOOR |
| | OPENING. ELECTRICAL EQUIPMENT SHALL BE |
| | LOCATED SO THAT IT WILL NOT BE DAMAGED |
| | BY LIQUIDS THAT ARE RETAINED BY THE |
| | CURB. |
| | |
| | 60)NOTE: NO, THIS WAS NOT CORRECT. |
| | PLEASE SEE "SPEC BOOK" 16120 |
| | 2.3A5, PLEASE SEE COLOR CODING FOR |
| | 277/480V SHALL BE BROWN, PURPLE, YELLOW. |
| | 215.8 LOCAL AMENDMENTS. |
| | |
| | 61)NOTE:OK. |
| | |
| | 62)NOTE: OK. |
| | HOWEVER PLEASE SEE NEW NOTES. |
| | |
| | 63)NOTE: OK. |
| | HOWEVER SEE NEW NOTES. |
| | |
| | 64)NOTE:OK. |
| | |
| | 65)NOTE: OK. |
| | SEE NEW NOTES FOR OTHER "F" FEEDER |
| | SCHEDULE AND CORRELATION WITH PANE |
| | SCHEDULES.L |
| | |
| | 66)NOTE: OK. |
| | |
| | 67)NOTE: OK, HOWEVER GEN INFORMATION, |
| | FUEL SUB-BASE TANK STILL NOT SUBMITTED. |
| | |
| | |
| | 68)NOTE:NO, SPECS FOR FIRE PUMP |
| | CONTROLLER ETCRATING S STILL TO BE |
| | VERIFIED.PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | AIC RATINGS SHOULD BE NOTED ON ALL |
| | EQUIPMENT. |
| | |
| | 69)NOTE:OK, ENGINEER'S RESPONSE LETTER |
| | MENTIONS, "LIGHTNING PROTECTION SYSTEM" |
| | WILL BE UNDER SEPARATE PERMITS. |
| | PLEASE SEE ALL INFORMATION FOR |
| | |
| | 70)NOTE: NO, INFORMATION NEEDS TO BE |
| | SUBMITTED FOR VERIFICATION OF CODE |
| | COMPLIANCE WITH SAID SYSTEMS.PLEASE ALSO |
| | SEEIF ALL INFORMATION FOR FIRE PUMP, |
| | FIRE PUMP CONTROLLER,GENERATOR, ATS, |
| | ETC WAS NOT SUBMITTED FOR REVIEW WITH |
| | BASE BLDG. |
| | PLEASE SEE FIRE REVIEW COMMENTS. |
| | |
| | 71)NOTE: OK, NO RESPONSE NEEDED. |
| | |
| | 72)NOTE:OK. NO RESPONSE NEEDED. |
| | |
| | 73)NOTE: PLEASE KNOW, AS NOTED IN SOME |
| | NOTES, DUE TO SOME INFORMATION MISSING |
| | ON PLANS AND WITH PLANS, SOME COMMENTS |
| | ARE NEW AND SOME ARE REPEAT. |
| | *************************************** |
| | |
| | 3RD REVIEW |
| | NEW COMMENTS/AND REPEAT COMMENTS WITH |
| | FURTHER EXPLANATION IN ORDER FOR |
| | COMMENTS TO BE ADDRESSED FOR A FINAL |
| | REVIEW. |
| | |
| | |
| | 74) NOTE: PLEASE SEE PREVOUS NOTES |
| | PERTAINING TO BUS DUCT. |
| | PLEASE CORRELATE BUS-DUCT SIZES ON RISER |
| | DIAGRAM AND BLDG RISER UP THROUGH THE |
| | BLDG. |
| | A) PLEASE SEE MAIN RISER NOW HAS BEEN |
| | REVISED FOR BUS-STABS INTO FPL VAULT FOR |
| | MAINS, HOWEVER PLEASE NOW SEE 1SMCN AND |
| | 2SMCN WHICH SHOWS 4000A BUS-DUCT INTO |
| | BOTH 3000A MAINS. (SEE KEY NOTE K-4) |
| | THIS OK, HOWEVER PLEASE CORRECT OF |
| | INDEED ONLY 3000A BUS IS GOING TO BE |
| | USED. |
| | B) PLEASE SEE 6.02, AND 6.03 FOR "KEY |
| | NOTES". PLEASE SEE 6.02 HAS NOW BEEN |
| | REVISED FOR 1SMCN RISER WHICH CONTAINS |
| | REVISION "K-3", PLEASE SEE THIS WAS |
| | CHANGED TO 4000A ON A 3000A MAIN, THIS |
| | IS OK, HOWEVER PLEASE SEE 6.03 "KEY |
| | NOTE" FOR SAME BUS DUCT RISER. PLEASE |
| | SEE KEY NOTES REF K-7 FOR THE SAME RISER |
| | WHICH IS SHOWN AS 3000A'S?? |
| | PLEASE VERIFY SIZING OF BUST DUCT 3OR 4K |
| | AND IF THERE ARE TWO DIFFERENT SIZES |
| | BEING INSTALLED FOR THIS 3K MAIN.? |
| | PLEASE SEEFEEDERS AS NOTED ARE FOR |
| | 3000A'S. |
| | |
| | 75)NOTE: PLEASE SEE PREVIOUS NOTED A |
| | REQUEST TO PROVIDE "FEEDER SCHEDULE" ON |
| | RISER DIAGRAM AND TO NOTES TO CORRELATE |
| | FEEDERS. |
| | PLEASE SEE THE FOLLOWING: |
| | |
| | A) DPHREL, SHOWS F-9 ON RISER, F-10 ON |
| | PANEL SCHEDULE AND F-10 ON SHE. REDLINED |
| | LOCATION. |
| | |
| | B)DPHRE, SHOWS F-11 ON RISER, F-13 ON |
| | PANEL SCHEDULE. REDLINED LOCATION. |
| | |
| | C)DPHRN, SHOWS F-4 ON RISER, F-5 ON SHN, |
| | REDLINED LOCATION. PLEASE NOTE F-4 IS |
| | FOR 2500A'S? |
| | |
| | D)HRHN, SHOWS F-15 ON RISER, F-19 ON |
| | SHN, REDLINED LOCATION. |
| | |
| | E)HGME, SHOWS BLANK ON RISER, SHOWS F-12 |
| | ON PANEL SCHEDULE DPHE. |
| | |
| | F)H5ME, SHOWS F-18 ON RISER, SHOWS F-20 |
| | ON DPHE, REDLINED LOCATION. |
| | |
| | G)FIRE PUMP FEEDERS, F-10 INDICATE AN |
| | "EQUIPMENT GROUNDING CONDUCTOR" FROM |
| | FPL. PLEASE SEE 250.6 AND EQUIPMENT |
| | GROUNDING CONDUCTOR IS ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISC. |
| | (IT IS NOTED, FEEDERS NOT TO HAVE EQP |
| | GRND). |
| | PLEASE SEE FEEDERS LISTED AS K-24 WHICH |
| | INDICATES 6-SETS OF 3-3/0'S AND 3/0 GRND |
| | FOR FEEDERS TO FIRE PUMP FROM FIRE PUMP |
| | CONTROLLER?? PLEASE VERIFY THE SIZES AND |
| | NUMBER OF PARALLEL RUNS. |
| | |
| | H)SHN AND SHE ON RISER DIAGRAM INDICATES |
| | A "BUS-STAB" INOT FPL VAULT, HOWEVER, |
| | PANEL SCHEDULES FOR EACH OF THESE ON |
| | 7.12 INDICATES "FEEDERS" AS F-3 AND F-6. |
| | PLEASE CORRELATE, LOCATION REDLINED. |
| | |
| | 76)NOTE: PLEASE SEE SPECS FOR ATS NOT |
| | SUBMITTED TO VERIFY MEANS OF DISCONNECT, |
| | MANUAL, LOCATED ON OUTSIDE OF EQUIPMENT |
| | ETC. |
| | PLEASE SEE DPHE WILL BE REQUIRED TO HAVE |
| | A MAIN CIRCUIT BREAKER FOR SERVICE |
| | DISCONNECT FROM FPL AND GENERATOR. |
| | THIS WAS REDLINED ON SETS FROM PREVIOUS |
| | REVIEW, BUT UNABLE TO VERIFY MEANS OF |
| | DISCONNECT FROM OTHER REVIEWS DUE TO NO |
| | SPECS ETC SUBMITTED FOR ATS. |
| | NO OCP COULD BE LOCATED FOR SEC'S COMING |
| | INOT BLDG FROM FPL ON THIS. |
| | 230.70,230.76,230.79,230.72,240.4. |
| | |
| | 77)NOTE: PLEASE KNOW, PLANS WERE |
| | SUBMITTED ONLY FOR "PLAN REVIEW" BEFORE |
| | JAN 1ST, 2005 AND NOT FOR PERMIT |
| | APPLICATION.. PLEASE SEE NFPA-72 AND 101 |
| | AND FIRE CODES CHANGE AT THAT TIME. |
| | PLEASE SEE NFPA 101 REFERENCES A 1999 |
| | EDITION. EVEN IF UNDER THE OLD CODE, |
| | THIS WOULD BE 2000 EDITION OF 101, |
| | HOWEVER PERMIT APPLICATIONS AFTER JAN |
| | 1ST , WOULD PLACE THIS PROJECT UNDER THE |
| | 2002 NFPA-72 AND 2003 NFPA-101. |
| | |
| | 78)NOTE: PLEASE SEE CHANGES TO PREVIOUS |
| | NOTES FOR WATER HEATERS SHOWING OCP AT |
| | 50A'S FOR A 4.5KW UNIT. PLEASE SEEUNIT |
| | "N" WHICH NOW SHOWS SECOND WATER HEATER |
| | AS A "BLANK" FOR OCP ETC. |
| | PLEASE SEE LOAD CALCULATIONS AND PLANS |
| | STILL INDICATE TWO UNITS. |
| | PLEASE ADJUST AND CORRELATE. |
| | |
| | 79)NOTE: PLEASE SEE PANEL SCHEDULE FOR |
| | UNIT D-2 COULD NOT BE LOCATED. |
| | PLEASE CLARIFY IF THIS IS A DIFFERENT |
| | PANEL. UNITS "D" AND D-1 ARE SUBMITTED. |
| | |
| | 80)NOTE: PLEASE SEELAUNDRY RMS IN SOME |
| | UNITS INDICATE THE CIRCUIT PROVIDED FOR |
| | WASHER ALSO FEEDING THE ADDITIONAL GFI |
| | IN THE SAME RM? PLEASE SEE LOADING FOR |
| | CIRCUITING AS A DEDICATED CIRUIT AND NO |
| | OTHER RECEPTS ON THAT CIRCUIT SHOULD BE |
| | VERIFIED. |
| | LOAD FOR WASHER UNIT CAN NOT BE |
| | VERIFIED. |
| | PLEASE SEE 210.11C2 |
| | |
| | 81)NOTE: PLEASE SEENFPA-101 7-9 UNDER |
| | THE 2003. WHICH WOULD REQUIRE MUTIPLE |
| | CIRCUITS FEEDING EM LTS IN STAIR TOWERS. |
| | PLEASE KNOW THE AHJ/ FIRE MARSHAL'S |
| | OFFICE HAS DETERMIND EITHER EVERY OTHER |
| | EM LT TO ALTERNATE CIRUITS OR A BATTERY |
| | BACK UP FIXTURE AT EVERY OTHER LEVEL |
| | WOULD BE REQUIRED FOR EGRESS IN STAIR |
| | TOWER. PLEASE KNOW, IF BLDG IS UNDER |
| | GENERATOR/ EM POWER AND A TRIPPING OF A |
| | SINGLE BRKR , EITHER BRANCH CIRCUIT OR |
| | MAIN, THIS WOULD PLACE STAIR TOWER(S) IN |
| | TOTAL DARKNESS. TO ALLEAVIATE ANY OF |
| | ALTERNATING CIRCUITS, OR TRIPPING OF ANY |
| | OVERCURRENT PROTECTION DEVICE, A BATTERY |
| | BACK-UP TYPE OF FIXTURE WOULD BE |
| | REQUIRED TO PROVIDE A MIN OF .1 FT |
| | CANDLE AS LISTED UNDER 7.9.2.1, |
| | 7.9.2.2, 7.8.1.2. |
| | THIS COMMENT CAN BE SET UP AS A |
| | "PROVISO"TO REVISE BEFORE ROUGH OR CAN |
| | BE ADDRESSED AT THIS TIME. PLEASE CALL |
| | TO GO OVER. |
| | |
| | 82)NOTE: PLEASE SEE ATTACHED COPY OF FS |
| | 553.80(2)(B) IS GIVEN ASNOTICE ONLY. |
| | |
| | PLEASE BE SURE TO SEE ANY COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE BE SURE TO REMOVED ALL OLD/ |
| | VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. |
| | ONE COMPLETE SET OF OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT ALL OF THE ABOVE |
| | INFORMATION FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS, PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | PLEASE SEE ANY COMMENTS FROM O |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| 2005-09-06 00:00:00 | PLANS WILL GO INTO A "F" STATUS. |
| | |
| | PLAN REVIEW NOTES TO FOLLOW, PLAN REVIEW |
| | AND NOTES IN PROGRESS. |
| 2005-09-04 00:00:00 | ELECTRICAL PLANSONLY ARE AT DP'S DESK |
| | FOR REVIEW. |
| | REVIEW TO CONTINUE,,,, STOPPED FOR 9/4 |
| 2005-08-24 00:00:00 | REVISION TO THE TEMPORARY POWERJL |