| 2005-11-11 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 5/19/05: |
| | |
| | 4) INFORMATIVE. NOTE THAT THE NOTICE OF |
| | COMMENCEMENT, IMPACT FEE RECEIPT AND |
| | SPECIAL INSPECTOR AGREEMENT WILL BE |
| | REQUIRED BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 5) FBC* 104.2.4SITE SURVEY. THIS |
| | COMMENT HAS NOT BEEN PROPERLY ADDRESSED. |
| | THIS TIME NO SURVEY DRAWING WAS |
| | SUBMITTED.A SIGNED AND SEALED SURVEY |
| | DRAWING PREPARED BY A LICENSED |
| | SURVEYOR/MAPPER IS REQUIRED. |
| | (REF: 472.025(1) FL. STATUTES). |
| | |
| | 8) FBC* 1804.2.2SHEET S-0, GENERAL |
| | NOTES - FOUNDATIONS.THIS COMMENT HAS |
| | NOT BEEN ADDRESSED.SUBMIT THREE |
| | COPIES OF ARDAMAN & ASSOCIATES SOIL |
| | REPORT DATED 7/28/04 AS REFERENCED |
| | UNDER THE 'FOUNDATION' NOTE. |
| | |
| | 9) FBC 13-103.1.2THIS COMMENT HAS NOT |
| | BEEN ADDRESSED.SHEET 2 OF THE |
| | SUBMITTED ENERGY CODE COMPLIANCE FORMS |
| | MUST BE SIGNED BY THE BUILDING OWNER, |
| | THE OWNER'S ARCHITECT OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY |
| | THE OWNER.ALSO THE ARCHITECT'S LICENSE |
| | NUMBER MUST BE ADDED IN THE SPACE |
| | PROVIDED ON SHEET 2 AND ALL OF THE |
| | PROJECT INFORMATION ITEMS ON SHEET 1 |
| | SHALL BE ENTERED. |
| | |
| | 10) PRODUCT APPROVALS.THIS COMMENT HAS |
| | NOT BEEN ADDRESSED. SUBMIT PRODUCT |
| | APPROVALS FOR THE WINDOWS, STOREFRONTS, |
| | EXTERIOR DOORS AND ROOFING PRODUCTS. |
| | |
| | 25) NFPA 823-2.4.3.1THE COMMENT |
| | RESPONSE REFERING TO APPROVAL BY THE |
| | CONSTRUCTION BOARD OF ADJUSTMENTS AND |
| | APPEALS (CBAA) IS NOTED.PLEASE SUBMIT |
| | A COPY OF THE CBAA FINAL DECISION, FOR |
| | THE PERMIT FILE,SO THAT IT MAY BE |
| | DEEMED UNNECESSARY, FOR THIS PROJECT |
| | ONLY, TO PROVIDE A MINIMUM 6" CLEARANCE |
| | BETWEEN THE OPEN CHUTE LOADING DOOR AND |
| | CLOSED SERVICE OPENING ROOM DOOR. |
| | |
| | 37) FBC 1601.1SHEET A8.24, |
| | ARCHITECTURAL TRIM.SUBMITTAL OF |
| | DETAILS FOR ATTACHMENT OF MOULDINGS, |
| | ORNAMENTAL PANELS AND BANDS, AND OTHER |
| | ARCHITECTURAL TRIM IS NOTED BUT THE |
| | DETAILS DO NOT STATE THE HORIZONTAL |
| | SPACING OF THE 'TAPCONS'.AMEND THE |
| | DETAILS TO SHOW THE FASTENER SPACING. |
| | |
| | 42) FBC 11.4.6.3SHEETS A2.04 THROUGH |
| | A2.09.ALL ACCESSIBLE PARKING SPACES |
| | SHALL BE MIN. 12'-0" WIDE.THE PLANS |
| | ONLY SHOW THE VAN ACCESSIBLE SPACES TO |
| | COMPLY WITH THIS REQUIREMENT.ALL OF |
| | THE REMAINING ACCESSIBLE SPACES ARE |
| | SHOWN AS ONLY 8'-6" WIDE.AMEND THE |
| | PLANS. |
| | |
| | 43) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| | WHICH REQUIRES NEW PLANS IN ORDER TO |
| | ADDRESS THE ABOVE COMMENTS, THE OLD |
| | SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| | REMAINING OLD SHEETS, TO FORM A SET OF |
| | 'OLD/VOID SHEETS', FOR COMPARISON OF |
| | REVISIONS WHEN REVIEWING THE RESUBMITTED |
| | PLANS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |
| 2005-10-21 00:00:00 | ****PLAN REVIEW IN PROGRESS**** |