2007-04-04 18:02:12BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S.OLIVE AVE
 CONT: KAST CONST.
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW SUBMITTAL #05100.05 EXHAUST SHAFT TRUSS
 DRAWINGS.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE ENGINEER SHALL INDICATE THE BOTTOM CHORD LIVE
 LOADPER FBC TABLE 1607.1 ON THE TRUSS DRAWINGS. THE
 BREAK CONNECTION DETAIL DRAWINGS SHALL ALSO BE SIGNED
 AND SEALED BY THE PERSON TAKING RESPONSIBILITY FOR
 THOSE DRAWINGS.THE RUBBER SEAL ON THE DRAWINGS ARE
 NOTORIGINAL SEAL. SEE F.A.C. 61G15-23.002/ FL.
 STATUTES 471.025.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726