| Plan Review Notes For Permit 04120353 |
| Permit Number |
04120353 |
|
| Review Stop |
P |
| Sequence Number |
24 |
|
| Notes |
| Date |
Text |
| 2007-02-22 18:58:17 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1. SHT P2.52 UNIT TYPES S1 & R ARE INDICATING SUPPLYING | | | WATER TO THE ROOF LEVEL FOR THE SHOWER, DRINKING | | | FOUNTAIN AND HOSE BIBB AT THE POOL AREA. THIS IS NOT | | | APPROVED AND THE WATER FOR COMMON AREA USAGE SHALL BE | | | SUPPLIED FROM COMMON AREA WATER SUPPLY, NOT FROM THE | | | DWELLING UNITS. SECTIONS 608.1 & 103.6 AND TABLE | | | 608.1. | | | | | | 2. SHT P2.58 4" DD & 3" SANT. LINE NOT INDICATED ON | | | PREVIOUS REVISIONS. SECOND SHOWER LINE BEHIND ELEVATORS | | | AS INDICATED ON SHT P2.52 NOT SHOWN. PLEASE CLARIFY. | | | SECTION 104.2.1. | | | | | | 3. SHT P3.05 UNIT S & S1 SHOWS SHOWER, HOSE BIBB & | | | DRINKING FOUNTAIN WATER SUPPLY FROM DWELLING UNIT. | | | WATER SUPPLY SHALL BE CONNECTED TO THE COMMON AREA | | | WATER SUPPLY. SECTIONS 608.1, 103.6 AND TABLE 608.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|