Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop E
Sequence Number 23
Notes
Date Text
2007-08-26 20:28:382007-08-26 20:28:38
  
 ** TWO CITY PLAZA **
 REVISIONS.
  
 **PLEASE SEE MANY OF THE SHEETS WERE OK AND WERE
 STAMPED. THESE ARE OK PENDING FIRE REVIEW.
  
 ** PLEASE SEE THE SUBMITTED ELECTRICAL NARRATIVE WAS
 NOT ACCURATE FOR ALL SHEETS BASED ON THE ELECTRICAL
 SHEETS SUBMITTED. THERE WERE SEVERAL SHEETS SUBMITTED
 WHICH WERE NOT ON THE NARRATIVE LIST.
 PLEASE SEE THE FOLLOWING COMMENTS:
  
  
 1) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES WITH
 RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS SIGNED
 INTO LAW JULY OF 07.
 PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE
 AFFECTED. PLEASE SEE THAT AN INDUSTRY BULLETIN IS BEING
 PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL
 INFORMATION.
 *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED,
 PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND
 DOCUMENTATION FOR REVIEW.
 PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE
 NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS
 ETC.
  
 2) NOTE: PLEASE SEE REVIEW NOTES DATED 3/10/07 HAVE NOT
 BEEN FULLY ADDRESSED AS OF YET.
 PLEASE SEE THE FOLLOWING WHICH WAS STATED ON THAT
 REVIEW.
 ****
 2) NOTE: PLEASE SEE NFPA-20, 1999 OR 2003. PLEASE KNOW
 THE AMOUNT OF FUEL FOR THE FIRE PUMP SHALL BE REVISED
 FOR THE ON-SITE POWER OF THE GENERATOR TO INDICATE THE
 MINIMUM FUEL AS STATED. PLEASE KNOW THAT THE ACTUAL
 LOAD ON THE GENERATOR WITH ALL ASSOCIATED OTHER LOADS
 SHALL BE CONSIDERED THE BASIS FOR THE FUEL CONSUMPTION
 PER HOUR. THE PLANS INDICATE 92.1 GALS PER HOUR AT THIS
 TIME.
 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT TO
 PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100 PERCENT
 OF THE RATED PUMP CAPACITY IN ADDITION TO THE SUPPLY
 REQUIRED FOR OTHER DEMANDS.
  
 3) NOTE: PLEASE SEE SHEET E3.32 WAS REPEATED IN TWO
 SETS.
  
 4) NOTE: PLEASE SEE SHEET E-1705.1 IS NOT TO THE
 MINIMUM SCALE AS REQUIRED UNDER THE FBC ADMIN SECTION.
 104.1.2 OR THE CURRENT CODE ADMIN SECTION WHICH STATES
 THE SAME AS THE ADMIN CODE IN EFFECT AT THE TIME OF
 PERMIT.106.1.3
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]