| Date |
Text |
| 2005-05-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | |
| | FROM PREVIOUS REVIEW: |
| | 3) SHT A2.10 SUBMIT CALCULATIONS FOR |
| | MINIMUM FACILITIES PER TABLES 1003.2 AND |
| | 403.1. SHOW SQUARE FEET FOR EACH COMMON |
| | USE ROOM. RESPONSE NOTED, BUT NOT |
| | INDICATED WHERE I CAN FIND THE |
| | CALCULATIONS. SECTION 104.2.1. |
| | 4) SHT A2.10 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY STORM DRAINS FOR |
| | THE 5TH FLOOR OPEN AREAS PER SECTIONS |
| | 1106 & 1107. SHOW THE LOCATIONS FOR ALL |
| | PRIMARY AND SECONDARY DRAINS. RESPONSE |
| | NOTED, BUT NO CALCULATIONS WERE |
| | INDICATED OR FOUND. SECONDARY DRAINS |
| | WERE NOT LOCATED FOR ALL AREAS. SECTION |
| | 104.2.1. |
| | 10) ALL SHEETS FOR UNITS, SHOW THE |
| | OPENING SIZE FOR ALL W/C'S AND SHOW THE |
| | W/C TO BE 18" FROM THE CENTER LINE OF |
| | THE FIXTURE TO THE WALL WHERE |
| | APPLICABLE. RESPONSE NOTED, BUT NOT ALL |
| | UNITS SHOW THE REQUIREMENT. SECTION |
| | 104.2.1. |
| | 11) ALL SHEETS FOR UNITS, INDICATE |
| | SPECIFICATION "A" OR "B" AS REQUIRED BY |
| | THE FHA-98 DESIGN MANUAL FOR EACH UNIT. |
| | RESPONSE NOTED, BUT NOT UNITS SHOW |
| | SPECIFICATION "A" OR "B". SECTION |
| | 104.2.1. |
| | 12) SHT A4.41 KITCHEN SINK & JUICE BAR |
| | SINK IN COMMON AREAS SHALL COMPLY WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | SUBMIT A DETAIL. RESPONSE NOTED, BUT NO |
| | DETAIL WAS FOUND. |
| | 13) SHT A4.41 SUBMIT A DETAIL FOR THE |
| | TOILET ROOM IN THE COMMON AREA. SHOW |
| | COMPLIANCE WITH SECTIONS 11-4.16, |
| | 11-4.19, 11-4.21, & 11-4.22 AND ALL |
| | SUBSECTIONS. ALSO SEE SECTION 2 OF THE |
| | FHA-98 DESIGN MANUAL. RESPONSE NOTED, |
| | BUT THE FOLLOWING INFORMATION IS NOT |
| | SHOWN ON THE DETAIL: |
| | A. FLUSH CONTROLS 11-4.16.5 |
| | B. EXPOSED PIPES & SURFACES 11-4.19.4 |
| | C. FAUCETS 11-4.19.5 |
| | D. CURBS 11-4.21.7 |
| | 14) SHT A4.41 A DRINKING FOUNTAIN IS |
| | REQUIRED PER TABLE 403.1 FOR THE COMMON |
| | AREA. SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH SECTION 11-4.15 AND ALL SUBSECTIONS |
| | ALSO SEE SECTION 410.1. RESPONSE NOTED, |
| | BUT NOT INDICATED WHERE DETAIL IS |
| | LOCATED. |
| | 15) SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 |
| | AND 1107 AND ALL SUBSECTIONS. SHOW THE |
| | SQUARE FOOTAGE OF EACH AREA DRAINED WITH |
| | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS SHOWN ADDED TO THE ROOF AREA. |
| | ALSO SHOW THE AREA OF UPPER ROOFS |
| | DRAINING ONTO EACH AREA ADDED TO THE SF |
| | IN CALCULATIONS. SHOW THE LOCATION OF |
| | EACH SECONDARY ROOF DRAIN OR SCUPPER. - |
| | RESPONSE NOTED, BUT CALCULATIONS ALL |
| | SECONDARY DRAINS ECT. NOT FOUND. THESE |
| | CALCULATIONS WILL BE FOR THE 5TH FLOOR |
| | PRIMARY DRAINS AND SECONDARY DRAINS AS |
| | WELL. - PLEASE PROVIDE CALCULATIONS. |
| | 18) SHT A4.71A INDICATE LOCATION OF |
| | SECONDARY ROOF DRAINS IN AREAS OF ROOF |
| | WHERE SCUPPERS ARE NOT AVAILABLE. |
| | SECTION 1107. - RESPONSE NOTED, BUT |
| | INFORMATION NOT SHOWN. |
| | 19) SHT A4.72A INDICATE LOCATION OF |
| | SECONDARY ROOF DRAINS FOR DECK DRAIN |
| | AREAS. SECTION 1107. RESPONSE NOTED, BUT |
| | INFORMATION NOT LOCATED. |
| | 20) SHT A4.73A INDICATE LOCATION OF |
| | SECONDARY ROOF DRAIN FOR ALL AREAS. |
| | SECTION 1107. - RESPONSE NOTED, BUT ALL |
| | DRAINS NOT SHOWN. |
| | 32) SHEETS FOR UNIT TYPES ARE INCOMPLETE |
| | AND REQUIRE MORE INFORMATION. SOME |
| | SHEETS SHOW SANT., VENTS, WATER, COND., |
| | T/P, OR ANOTHER UNIDENTIFIED LINE, BUT |
| | ALL DO NOT HAVE ALL INFORMATION |
| | REQUIRED. - RESPONSE NOTED, BUT |
| | INFORMATION IS STILL MISSING ON MANY |
| | SHEETS. SOME EXAMPLES NO SANT SHOWN TO |
| | WASH MACHINE IN UNIT 1, RISER NUMBERS |
| | ARE MISSING OR MISLABLED, SOME SANT. |
| | LINES NOT SHOWN, WATER LINES MISSING, |
| | ECT. RECHECK ALL UNITS TO MAKE SURE ALL |
| | PIPING, (SANT., WATER, COND, VENTS, P/T, |
| | PAN DRAINS, WASTE ARMS ECT ARE SHOWN) |
| | 33) SHOW STACK NUMBERS FOR EACH STACK IN |
| | ALL UNIT SHEETS. SECTION 104.2.1. |
| | RESPONSE NOTED, BUT NOT ALL STACK |
| | NUMBERS ARE SHOWN, AND SOME STACK |
| | NUMBERS ARE NOT IN THE CORRECT LOCATION |
| | AS THE STACK. |
| | 45) SHT P2.21 UNITS A1 & VV1 BATH #2 |
| | SHOWERS ARE NOT VENTED. SECTION 901.2.1 |
| | UNIT A1 WHAT TYPE OF VENT IS KITCHEN |
| | SINK UTILIZING. SECTION 901.2.1 - |
| | RESPONSE NOTED, BUT SHOWERS ARE NOT |
| | VENTED AND NO INFORMATION FOR THE |
| | KITCHEN VENT HAS BEEN GIVEN. |
| | 46) SHT P2.39 HAS A REFERENCE TO SHT P2. |
| | NO SHT P2 IS LOCATED. PLEASE CLARIFY |
| | SECTION 104.2.1. - RESPONSE NOTED, BUT |
| | THE REFERENCE IS STILL THERE. IN FACT |
| | THERE ARE AT LEAST 2 REFERENCES TO SHEET |
| | P2 ON THIS SHEET. |
| | 50) SHT P2.57 WOMEN'S BATHROOM DOES NOT |
| | REFLECT THE SANT. RISER DIAGRAM. W/C IN |
| | WOMEN'S STALL MAX. 10' FROM POINT OF |
| | VENT TABLE 906.1. INDICATE THE USE OF |
| | THE FLOOR DRAIN FOR FIXTURE NEXT TO |
| | SHOWER IN THE MEN'S BATHROOM. SECTION |
| | 104.2.1. - RESPONSE NOTED, BUT THE W/C |
| | IN THE WOMEN'S BATHROOM DOES NOT SHOW |
| | SANITARY PIPING FROM THE BRANCH LINE TO |
| | THE WATER CLOSET TO THE LAV AS SHOWN ON |
| | THE RISER DIAGRAM. ALSO THE FLOOR DRAIN |
| | IN THE MEN'S BATHROOM HAS NOT BEEN |
| | EXPLAINED BY THE RESPONSE "DRAWING |
| | CORRECTED" |
| | 51) ALL SANT. RISERS WITH WASH MACHINES |
| | REQUIRE A STANDPIPE, AND THE CLEANOUTS |
| | SHALL BE LOCATED 4' ABOVE THE FLOOR FOR |
| | ACCESS. SECTIONS 1002.1, 802.4, & |
| | 708.10. - RESPONSE NOTED, BUT COMMENT |
| | NOT ADDRESSED. |
| | 64) BACKFLOW PROTECTION REQUIRED FOR THE |
| | POOL MAKE UP WATER. SUBMIT A DETAIL. |
| | SECTION 608.13.2. - RESPONSE NOTED, BUT |
| | BACKFLOW PROTECTION IS NOT IN THE SCOPE |
| | OF THE POOL CONTRACTOR UNLESS IT IS AN |
| | AIR GAP AT THE COLLECTOR TANK. PLEASE |
| | INDICATE METHOD OF BACKFLOW PROTECTION. |
| | 65) BECAUSE PLANS ARE INCOMPLETE, MORE |
| | COMMENTS MAY BE FORTHCOMING WHEN PLANS |
| | ARE RESUBMITTED. - PLEASE RETURN THE |
| | PLUMBING PLANS WITH THE RED LINE NOTES |
| | WHEN RESUBMITTING TO HELP REVIEWING |
| | PLANS FOR THE SECOND TIME. - RESPONSE |
| | NOTED, BUT PLANS WERE NOT RETURNED. I |
| | WILL BE KEEPING THE RED LINE SET OF |
| | PLANS TO ASSIST IN THE THIRD REVIEW. |
| | ALSO IT SEEM THAT THE PLANS ARE NOT 100% |
| | COMPLETE AT THIS TIME AND MORE COMMENTS |
| | MAY FOLLOW ON THE THIRD REVIEW. |
| | **************NEW COMMENTS************** |
| | 1B) SHT A4.43 PLANTERS SHOW 8"H OPENINGS |
| | IN PLANTER WALLS AND REFER TO SHT A8.21 |
| | FOR A DETAIL. NO DETAIL FOR THESE |
| | OPENINGS WAS LOCATED. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 2B) SHTS A4.41 THRU AR.44A SUBMIT DETAIL |
| | FOR SCUPPERS FOR TERRACES ON THE 5TH |
| | FLOOR. INDICATE HEIGHT AND WIDTH. |
| | SECTIONS 1107 & 104.2.1. - DETAILS #1 |
| | PRECAST SCUPPER ON S.W. CORNER NOT SHOWN |
| | WHERE INDICATOR IS POINTING. WHERE IS A |
| | CUT SECTION FOR AREA ADJACENT TO |
| | STAIRWAY #5. NO SECONDARY DRAIN/SCUPPER |
| | SHOWN. SECTION 1107. - ALSO DETAIL #2 NO |
| | SECONDARY DRAIN/SCUPPER IN OPPOSITE |
| | CORNER. |
| | 3B) A4.60 SUBMIT DETAIL FOR SCUPPERS ON |
| | THE 16TH FLOOR. SECTION 1107 |
| | 4B) SHTS A4.71, A4.72, A4.73, & A4.74 |
| | SHOW LOCATION OF ALL SECONDARY ROOF |
| | DRAINS FOR AREAS THAT DO NOT HAVE |
| | SCUPPERS. SECTION 1107 |
| | 5B) SHT A5.11 DETAIL #9 INDICATES A |
| | SHOWER BATHROOM DETAIL NOT SHOWN ON THE |
| | DETAIL INDEX. PLEASE CLARIFY |
| | 6B) SHT A5.11 SHOW ELEVATION FOR W/C |
| | AND LAVS IN USABLE BATHROOMS SHOWING |
| | OPENINGS FOR W/C, 18" OFF WALL TO |
| | CENTERLINE OF FIXTURE, AND HEIGHT OF LAV |
| | COUNTER TOPS AT 34". FHA-98 DESIGN |
| | MANUAL REQUIREMENT 7. |
| | 7B) SHTS P2.01 & P2.02 PAN DRAIN LINES |
| | FROM THE WATER HEATERS SHALL TERMINATE |
| | OVER A SUITABLY LOCATED INDIRECT WASTE |
| | RECEPTOR OR FLOOR SINK OR EXTEND TO THE |
| | EXTERIOR OF THE BUILDING AND TERMINATE |
| | NOT LESS THA 6" OR MORE THAN 24" ABOVE |
| | THE ADJACENT GROUND SURFACE GROUND |
| | SURFACE. SECTION 504.8.2. |
| | 8B) SHT P2.02 NO SANT. SHOWN TO WASH |
| | MACHINE FOR UNIT #1. SECTION 104.2.1. |
| | 9B) SHT P2.02 FLOOR PLAN DOES NOT |
| | REFLECT THE RISER DIAGRAM 54/68 AT UNIT |
| | #3. SECTION 104.2.1. |
| | 10B) SHT P2.02 UNIT #4 INDICATE RISER |
| | NUMBERS AT BATH #1. SECTION 104.2.1. |
| | 11B) SHT P2.02UNIT #4 RISER NUMBERS BY |
| | THE WASH MACHINE DO NOT REFLECT THE |
| | NUMBERS SHOWN ON THE RISER DIAGRAM. |
| | PLEASE CORRELATE RISER & FLOOR PLAN |
| | RISER DESIGNATION. SECTION 104.2.1. |
| | 12B) SHT P2.03 UNIT 5 RISER NUMBERS AT |
| | POWDER ROOM ON THE FLOOR PLAN DO NOT |
| | REFLECT NUMBERS SHOWN ON RISER DIAGRAM. |
| | PLEASE CORRELATE RISER AND FLOOR PLAN. |
| | SECTION 104.2.1. |
| | 13B) SHT P2.03 UNIT 7 FLOOR PLAN DOES |
| | NOT REFLECT THE RISER DIAG. PLEASE |
| | CORRELATE RISER WITH FLOOR PLAN. SECTION |
| | 104.2.1 |
| | 14B) SHT P2.06 RISER SOUTH OF ELEVATOR & |
| | STAIRWAY DOES NOT SHOW RISER #60. |
| | SECTION 104.2.1. |
| | 15B) SHT P2.08 UNIT 3 BATH #2 DOES NOT |
| | REFLECT THE RISER DIAGRAM. PLEASE |
| | CORRELATE RISER & FLOOR PLAN. SECTION |
| | 104.2.1. |
| | 16B) SHT P2.10 UNIT 10 BATHROOM DOES NOT |
| | REFLECT THE RISER DIAGRAM. PLEASE |
| | CORRELATE. SECTION 104.2.1. |
| | 17B) SHT P2.12 UNIT 19 OFFSET FOR BATH |
| | #2 DOES NOT REFLECT THE RISER DIAGRAM. |
| | PLEASE CORRELATE. SECTION 104.2.1. |
| | 18B) SHT P2.12 UNIT 17 OFFSET DOES NOT |
| | REFLECT THE RISER DIAGRAM. PLEASE |
| | CORRELATE. SECTION 104.2.1. |
| | 19B) SHT P2.12 UNIT 15 IDENTIFY RISER. - |
| | FLOOR PLAN DOES NOT REFLECT THE RISER |
| | DIAGRAM. PLEASE CORRELATE. SEC 104.2.1. |
| | 20B) UNIT 14 BATH #2 VENT DOES NOT |
| | REFLECT RISER DIAGRAM. PLEASE CORRELATE. |
| | SECTION 104.2.1. |
| | 21B) SHT P2.13 UNIT V MASTER BATH |
| | HORIZONTAL DRY VENT NOT APPROVED. |
| | SECTIONS 905.3 & 905.4. SANT. OFFSET |
| | DOES NOT REFLECT THE RISER DIAGRAM. |
| | PLEASE CORRELATE. SECTION 104.2.1. |
| | 22B) SHT P2.13 UNIT VV VENT AND SANT. |
| | STACK DO NOT REFLECT THE RISER DIAGRAM. |
| | VENT IS NOT SHOWN. PLEASE CORRELATE. |
| | SECTION 104.2.1. |
| | 23B) SHT P2.14 UNIT H7 WHICH RISER DOES |
| | KITCHEN SINK DRAIN INTO. RISER DOES NOT |
| | REFLECT FLOOR PLAN AT THE WASH MACHINE. |
| | PLEASE CORRELATE. SECTION 104.2.1. |
| | 24B) SHT P2.14 UNITS H1 & H2 DO NOT |
| | REFLECT THE DIAGRAM. PLEASE CORRELATE. |
| | SECTION 104.2.1. |
| | 25B) UNIT P2.15 UNIT VV1 MASTER BATH |
| | DOES NOT REFLECT THE RISER DIAGRAM, AND |
| | DRY HORIZONTAL VENT IS NOT APPROVED. |
| | COMMENT RESPONSE INDICATES THAT OFFSET |
| | UNDER TUB IS BELOW THE FLOOR, BUT FLOOR |
| | PLAN SHOWS THE VENT FROM THE WATER |
| | CLOSET ABOVE THE SLAB CONNECTING INTO |
| | THIS VENT OFFSET. PLEASE CLARIFY. PLEASE |
| | CORRELATE. SECTIONS 905.3, 905.4 & |
| | 104.2.1. |
| | 26B) SHT P2.16 UNIT B7 DOES NOT REFLECT |
| | THE RISER DIAGRAM AT THE MASTER BATH. |
| | PLEASE CORRELATE. SECTION 104.2.1. |
| | 27B) SHT P2.17 UNIT H4 TUB DRAIN LINE IS |
| | NOT SHOWN ON THE RISER DIAGRAM. PLEASE |
| | CORRELATE. SECTION 104.2.1. |
| | 28B) SHT P2.17 UNIT H3 POWDER ROOM RISER |
| | SHOWN AS SOIL STACK ON THE RISER |
| | DIAGRAM, BUT AS A VENT STACK ON THE |
| | FLOOR PLAN. - MASTER BATH LINE TO RIGHT |
| | OF WATER CLOSET, (RISER 37), SHOWN AS |
| | THE VENT LINE ON THE RISER DIAGRAM, |
| | WHICH WILL MAKE IT A DRY HORIZONTAL |
| | VENT. THIS IS NOT APPROVED BY SECTIONS |
| | 905.3 & 905.4 - BATH #2 VENT NOT SHOWN |
| | ON THE FLOOR PLAN. SECTION 104.2.1. |
| | 29B) SHT P2.18 UNIT V1 HORIZONTAL DRY |
| | VENT NOT APPROVED IN MASTER BATH AND |
| | POWDER ROOM. SECTIONS 905.3 & 905.4. |
| | 30B) SHT P2.18 UNIT HD POWDER ROOM LAV |
| | ARM NOT SHOWN. SECTION 104.2.1. |
| | 31B) SHT P2.18 UNIT H3 VENT LINE FOR |
| | MASTER BATH NOT SHOWN. SECTION 104.2.1. |
| | 32B) SHT P2.18 UNIT H6 VENT LINE FOR |
| | MASTER BATH NOT SHOWN. SECTION 104.2.1. |
| | 33B) SHT P2.19 UNIT V VENT LAYOUT DOES |
| | NOT REFLECT THE RISER DIAGRAM AT MASTER |
| | BATH. SECTION 104.2.1. |
| | 34B) SHT P2.19 UNIT VV STACK & VENT FOR |
| | KITCHEN MISSING. SECTION 104.2.1. |
| | 35B) SHT P2.19 UNIT B8 NO SANITARY OR |
| | VENT TO KITCHEN SINK. SECTION 104.2.1. |
| | 36B) SHT P2.20 UNIT HH1 PIPING FOR |
| | KITCHEN SINK & POWDER ROOM MISSING. |
| | SECTION 104.2.1. |
| | 37B) SHT P2.20 UNIT H7 INDICATE RISER |
| | NUMBER AND SANITARY DOES NOT REFLECT THE |
| | RISER DIAGRAM. SECTION 104.2.1. |
| | 38B) SHT P2.20 UNIT H2 SHOW DWV PIPING |
| | TO REFLECT RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 38B) SHT P2.21 UNIT H1 SHOW DWV PIPING |
| | TO REFLECT RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 39B) SHT P2.21 UNIT A1 BATH #2 DOES NOT |
| | REFLECT THE RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 40B) SHT P2.22 UNIT B7 SHOW DWV PIPING |
| | TO REFLECT RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 41B) SHT P2.22 UNIT B7 BATH #2 DOES NOT |
| | REFLECT THE RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 42B) SHT P2.23 UNIT A1 SHOW DWV PIPING |
| | TO REFLECT THE RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 43B) SHT P2.24 UNIT HD SHOW DWV PIPING |
| | TO REFLECT THE RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 44B) SHT P2.24 UNIT H3 SHOW DWV PIPING |
| | TO REFLECT THE RISER DIAGRAM. SECTION |
| | 104.2.1. - RISER (24) DESIGNATION IN |
| | WRONG LOCATION. SECTION 104.2.1. |
| | 45B) SHT P2.24 UNIT H6 SHOW DWV PIPING |
| | TO REFLECT THE RISER DIAGRAM. SECTION |
| | 104.2.1 |
| | 46B) SHT P2.25 UNIT L INDICATE THE |
| | LOCATION OF THE CONTINUATION OF RISERS |
| | (67) & (68). SECTION 104.2.1. |
| | 47B) SHT P2.25 UNIT C OFFSET DOES NOT |
| | REFLECT THE RISER DIAGRAM, (6). SECTION |
| | 104.2.1. |
| | 48B) SHT P2.25 UNIT C SHOW RISER |
| | DESIGNATION NUMBER FOR RISER #5 BY W/M. |
| | SECTION 104.2.1. |
| | 49B) SHT P2.25 UNIT C RWL #1 DOES NOT |
| | REFLECT THE RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 50B) SHT P2.25 UNIT B5 RISER (3)(56)(57) |
| | DOES NOT REFLECT THE RISER DIAGRAM. |
| | (KITCHEN DRAIN ARM NOT SHOWN). SECTION |
| | 104.2.1. |
| | 51B) SHT P2.25 UNIT B6 MASTER BATH DOES |
| | NOT REFLECT THE RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 52B) SHT P2.26 UNIT E1 FLOOR PLAN DOES |
| | NOT REFLECT THE RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 53B) SHT P2.26 UNIT E1 RWL #4 DOES NOT |
| | REFLECT THE RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 54B) SHT P2.27 UNIT A BATH #2 NOT VENTED |
| | NOT SANITARY TO RISER (25). SECTION |
| | 104.2.1. |
| | 55B) SHT P2.27 UNIT B1 SHOW RISER |
| | DESIGNATION NUMBERS FOR (29)(30)(31)(32) |
| | - VENT LINES NOT SHOWN - NO SANT. DRAIN |
| | LINE TO KITCHEN SINK. SECTION 104.2.1. |
| | 56B) SHT P2.28 UNIT B1 NO VENT LINES |
| | SHOWN. SECTION 104.2.1. |
| | 57B) SHT P2.28 UNIT B2 VENT LINES TO |
| | REFLECT RISERS DIAGRAM BATH #2 - MASTER |
| | BATH LAV DRAIN CONNECTION TO BRANCH IS |
| | SHOWN INSTALLED AGAINST THE FLOW. |
| | SECTION 706.3. - RISER #37 DESIGNATION |
| | SHOWN IN THE WRONG LOCATIONS. PLACE NEXT |
| | TO RISER. SECTION 104.2.1. |
| | 58B) SHT P2.28 UNIT A SHOW ALL PIPING TO |
| | REFLECT RISERS. SECTION 104.2.1. |
| | 59B) SHT P2.29 BOTH UNITS SHOW ALL |
| | PIPING TO REFLECT THE RISER DIAGRAMS. |
| | SECTION 104.2.1. |
| | 60B) SHT P2.30 UNIT A BATH #2 DOES NOT |
| | REFLECT RISER DIAGRAM. SECTION 104.2.1. |
| | 61B) SHT P2.31 ALL UNITS SHOW PIPING TO |
| | REFLECT RISER DIAGRAMS. SECTION 104.2.1. |
| | 62B) SHT P2.32 UNIT E1 FLOOR PLAN DOES |
| | NOT REFLECT THE RISER DIAGRAM. RISER 11 |
| | - SHOW ALL PIPING TO REFLECT RISER |
| | DIAGRAM. SECTION 104.2.1. |
| | 63B) SHT P2.32 UNITS D1 & G1 SHOW ALL |
| | PIPING TO REFLECT THE RISER DIAGRAMS. |
| | SECTION 104.2.1. |
| | 64B) SHT P2.33 ALL UNITS SHOW PIPING TO |
| | REFLECT RISER DIAGRAMS. SECTION 104.2.1. |
| | 65B) SHT P2.34 ALL UNITS SHOW PIPING TO |
| | REFLECT RISER DIAGRAMS. SECTION 104.2.1. |
| | 66B) SHT P2.35 ALL UNITS SHOW PIPING TO |
| | REFLECT RISERS. SHOW THE LOCATION OF |
| | RISER (45). SECTION 104.2.1. |
| | 67B) SHT P2.36 ALL UNITS SHOW PIPING TO |
| | REFLECT RISER DIAGRAMS. SECTION 104.2.1. |
| | 68B) SHT P2.36 UNIT C1 SHOW RISER |
| | DESIGNATION #(49). SECTION 104.2.1. |
| | 69B) UNIT E KITCHEN PIPING DOES NOT |
| | REFLECT THE RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 70B) SHT P2.36 UNIT E KITCHEN SINK |
| | PIPING DOES NOT REFLECT THE RISER |
| | DIAGRAM. SECTION 104.2.1 |
| | 71B) SHT P2.37B) UNITS B5 & B6 MASTER |
| | BATH DOES NOT REFLECT THE RISER DIAGRAM |
| | AT LAVS NEXT TO THE WATER CLOSET. |
| | SECTION 104.2.1. |
| | 72B) SHT P2.38B) UNIT G1 SHOW PIPING TO |
| | REFLECT RISERS. SECTION 104.2.1. |
| | 73B) SHT P2.39 ALL UNITS SHOW PIPING TO |
| | REFLECT RISERS. SECTION 104.2.1. |
| | 74B) SHT P2.40 UNIT B1 SHOW PIPING TO |
| | REFLECT THE RISERS. SHOW RISER LOCATION |
| | AND RISER DESIGNATION NUMBERS. SECTION |
| | 104.2.1. |
| | 75B) SHT P2.41 UNITS B & D SHOW PIPING |
| | TO REFLECT THE RISERS. SECTION 104.2.1. |
| | 76B) SHT P2.42 UNIT A SHOW PIPING TO |
| | REFLECT RISER DIAGRAMS. SECTION 104.2.1. |
| | 77B) SHT P2.44 UNIT G1 SHOW PIPING TO |
| | REFLECT RISER DIAGRAMS. SECTION 104.2.1. |
| | 78B) SHT P2.45 UNIT R1 FLOOR PLAN DOES |
| | NOT REFLECT THE RISER DIAGRAM. (26) |
| | SECTION 104.2.1. |
| | 79B) SHT P2.45 UNITS B4 & G SHOW PIPING |
| | TO REFLECT RISER DIAGRAMS. SECTION |
| | 104.2.1. |
| | 80B) SHT P2.46 UNIT P SHOW PIPING TO |
| | REFLECT RISER (36) AT BATH #2. SECTION |
| | 104.2.1. |
| | 81B) SHT P2.47 UNIT U DOES NOT REFLECT |
| | RISER (44) BATH #2. SECTION 104.2.1. |
| | 82B) SHT P2.48 SHOW PIPING FOR 2 LAVS. |
| | SECTION 104.2.1. |
| | 83B) SHT P2.51 SHOW ALL PIPING TO |
| | REFLECT RISER DIAGRAMS. SECTION 104.2.1. |
| | 84B) SHT P2.52 UNIT R VENT MISSING BATH |
| | #2 LAV. SECTION 104.2.1. |
| | 85B) SHT P2.55 INDICATE THE LOCATION FOR |
| | THE SECONDARY ROOF DRAINS. SECTION |
| | 104.2.1. |
| | 86B) SHT P2.55 OVERFLOW SHALL DRAIN FROM |
| | COOLING TOWERS TO STORM - DRAIN FROM |
| | COOLING TOWERS TO SANITARY. PLEASE |
| | INDICATE ON PLANS. SECTION 104.2.1. |
| | 87B) SHT P2.55 5" REQUIRED FOR STORM |
| | DRAIN DOWNSTREAM OF 4" R.D. @ 520 SF. |
| | TABLE 1106.3 |
| | 88B) SHT P2.56 INDICATE LOCATION OF ALL |
| | SECONDARY ROOF DRAINS. SECTIONS 104.2.1 |
| | & 1107. |
| | 89B) SHT P2.57 INDICATE LOCATION OF ALL |
| | SECONDARY ROOF DRAINS. SECTIONS 104.2.1 |
| | & 1107. |
| | 90B) SHT P2.57 RWL #6 3" PD @ 80 SF NOES |
| | NOT REFLECT THE RISER DIAGRAM. - 3" PD @ |
| | 50 SF DOES NOT REFLECT THE RISER |
| | DIAGRAM. - PIPE SIZE DOWNSTREAM OF 3" PD |
| | @ 280 SF REQUIRES A MINIMUM OF 5" PIPE. |
| | SECTION 104.2.1. |
| | 91B) SHT P2.57 FLOOR PLAN DOES NOT |
| | REFLECT THE RISER DIAGRAM. WOMENS HDCP |
| | TOILET LAV. RISER (25) IS A DRY VENT |
| | WHICH IS NOT APPROVED. SECTIONS 905.3 & |
| | 905.4. SECTION 104.2.1. |
| | 92B) SHT P2.58 RWL #7 DOWNSTREAM OF 3"DD |
| | @ 125 SF 5" REQUIRED. 4" SHOWN. TABLE |
| | 1106.3. - 3"PD @ 220 SF DOES NOT REFLECT |
| | RISER SHOWN AND 211 SF. PLEASE CORRELATE |
| | - RWL #8 3"PD @ 88 SF DOES NOT REFLECT |
| | RISER DIAGRAM SHOW AS 80 SF. PLEASE |
| | CORRELATE. SECTION 104.2.1. |
| | 93B) SHT P2.64 STORM DRAIN LAYOUT DOES |
| | NOT REFLECT RISER (2)(3) IN UNIT E, |
| | RISER (4)(5) IN UNIT B4, AND RISER |
| | (7)(8) IN UNIT D. SECTION 104.2.1. |
| | 94B) SHT P2.64 STORM DRAIN LINE RUNNING |
| | EAST TO WEST AND CONNECTING TO RISER |
| | (4)(5) SHALL SLOPE 1/4"/FT THE ENTIRE |
| | LENGTH. SECTION 704.1 |
| | 95B) SHT P3.00 SANITARY RISER DIAGRAM |
| | FOR TOILET ROOM POOL DECK, DRY |
| | HORIZONTAL VENT NOT APPROVED. SECTIONS |
| | 905.3 & 905.4. |
| | 96B) SHT P3.00 SANITARY RISER DIAGRAM |
| | FOR TOILET ROOM POOL DECK, FLOOR DRAIN |
| | BY SHOWER NOT APPROVED FOR INDIRECT |
| | WASTE. A FLOOR SINK OR HUB DRAIN IS |
| | REQUIRED. SECTIONS 802.3 & 802.3.2. |
| | 97B) SHT P3.00 DOMESTIC WATER RISER |
| | DIAGRAM POOL DECK TOILET ROOMS, LANAI |
| | LEVEL PUBLIC TOILETS, & WATER RISER |
| | DIAGRAM 5TH FLOOR PUBLIC AREA, THE WATER |
| | SUPPLY IS MISSING FOR 1 LAV, POOL DECK |
| | TOILET ROOMS, AND FULL OPEN VALVES ARE |
| | REQUIRED ON EVERY WATER DOWN-FEED PIPE. |
| | SECTION 606.1(4). |
| | 98B) SHTS P3.05 THRU P3.15 ALL UNIT |
| | WATER RISER DIAGRAMS, DELETE ALL AIR |
| | CHAMBERS AS THEY ARE NOT APPROVED. |
| | SECTION 604.9. - ALL WATER LINES TO THE |
| | REF. ICE MAKERS ARE REQUIRED TO HAVE A |
| | WATER HAMMER ARRESTOR. SECTION 604.9. - |
| | SOME UNITS SHOW A SEPARATE WATER LINE TO |
| | THE REF. ICE MAKER AND A LINE UNDER THE |
| | KITCHEN SINK FOR THE REF. ICE MAKER. |
| | PLEASE CLARIFY AS THEY DO NOT REFLECT |
| | THE RISER DIAGRAM IN MOST CASES. RISERS |
| | DO NOT SHOW TWO LINES TO THE ICE MAKER. |
| | - SOME RISERS ARE MISSING SUPPLY LINES |
| | TO FIXTURES. SECTION 104.2.1. |
| | 99B) SHT P3.16 RISER (4) OFFSET ON 16TH |
| | FLOOR NOT SHOWN. - RISER (5) TIE OFFSET |
| | VENT IN AS SHOWN IN EXAMPLE ON ATTACHED |
| | SHEET. (FIG. 915.2) |
| | 100B) SHT P3.17 RISER (6) TIE OFFSET |
| | VENT IN AS SHOWN IN EXAMPLE ON ATTACHED |
| | SHEET. (FIG 915.2) - 5TH FLOOR PLUMBING |
| | PIPE LAYOUT IS NOT SHOWN. (DIFFERENT |
| | FROM TYPICAL - NO OFFSET SHOWN. - RISER |
| | (56) TIE OFFSET VENT IN AS SHOWN IN |
| | EXAMPLE ON ATTACHED SHEET. (FIG. 915.2) |
| | - RISER (8) DOES NOT REFLECT THE FLOOR |
| | PLAN 5TH FLOOR, NOR DOES IT REFLECT THE |
| | FLOOR PLAN 6TH THRU 15TH FLOORS FOR THE |
| | LAVS. SECTION 104.2.1. |
| | 101B) SHT P3.18 RISER (69) DOES NOT |
| | REFLECT THE FLOOR PLAN. - RISER (10) |
| | DOES NOT REFLECT THE FLOOR PLAN 17TH |
| | THRU 21ST FLOOR. - RISER (11) NO BRANCH |
| | LINES FROM 4TH FLOOR THRU 15TH FLOOR. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 102B) ALL RISERS THAT HAVE OFFSET VENTS, |
| | THE CONNECTION FROM THE WASTE STACK TO |
| | THE VENT STACKS SHALL BE BY AN UPRIGHT |
| | WYE FITTING NOT A SANT. TEE FITTING AS |
| | SHOWN ON SOME RISERS, AND SHALL BE |
| | CONNECTED ON THE UPPER SECTION AS SHOWN |
| | ON ATTACHED SHEET. (FIG 915.2) |
| | 103B) SHTS P3.16 THRU P3.25 THE |
| | FOLLOWING SANITARY RISER DIAGRAMS WERE |
| | NOT LOCATED ON THE BUILDING DRAIN |
| | ISOMETRIC. 1, 2, 16, 8, (2 #8'S SHOWN), |
| | 10, 59, 12, 13, 14, 17, 15, 18, 19, 20, |
| | 21, 22, 72, 57, 75, 40, 41, 42, 37. |
| | 104B) SHTS P3.27 THRU P3.36 THE |
| | FOLLOWING RISERS SHOWN ON THE BUILDING |
| | DRAIN ISOMETRIC WERE NOT FOUND. 67, 83, |
| | 53, 68, 51, 58, 84, 85, 86, 87, 89, 90, |
| | 91, 84, 73, 33, 34, 74, 81. |
| | 105B) SHT P3.21 SANT. RISER #23 SHOWS |
| | 16TH FLOOR THEN 15TH FLOOR ABOVE. |
| | 106B) SHT P3.21 SANT. RISERS 24, & 36 |
| | INDICATE WHERE RISER #25 WILL CONNECT TO |
| | THESE RISERS. PLEASE CLARIFY AND |
| | INDICATE SHEET WHERE RISER #25 IS |
| | LOCATED. SECTION 104.2.1. |
| | 107B) SHT P3.21 RISER 71 INDICATE HOW |
| | RISER 54 TIES INTO THIS RISER AS IT IS |
| | NOT SHOWN ON PREVIOUS FLOORS. SECTION |
| | 104.2.1. |
| | 108B) SHT P3.21 RISER 26/35 KITCHEN SINK |
| | NOT SHOWN, DOES NOT REFLECT THE FLOOR |
| | PLAN, WASH MACHINE/LAUNDRY SINK OFFSET |
| | TO THE RIGHT SIDE NOT TO THE LEFT, |
| | VENTING FROM LAV DOES NOT REFLECT FLOOR |
| | PLAN. SECTION 104.2.1. |
| | 109B) SHT P3.22 RISER 55 DOES NOT |
| | REFLECT THE FLOOR PLAN. SECTION 104.2.1. |
| | 110B) SHT P3.22 RISER 29/31, RISER 31 |
| | NOT SHOWN 17TH TO 21ST FLOOR, MASTER |
| | BATH 15TH FLOOR MAXIMUM 4 FU MAX. ON 2" |
| | WET VENT. SECTION 104.2.1. & TABLE |
| | 909.3. |
| | 111B) SHT P3.22 RISER 30/32 ONLY RISER |
| | 32 IS SHOWN. NO 16TH FLOOR PIPING SHOWN, |
| | ONLY 4 FU MAX. ON 2" WET VENT. SECTION |
| | 104.2.1. AND TABLE 909.3. |
| | 112B) SHT P3.23 RISER 38 ONLY 4 FU MAX. |
| | ON 2" WET VENT. TABLE 909.3. |
| | 113B) SHT P3.24 SANT. RISER 77 16TH |
| | FLOOR DOES NOT REFLECT THE FLOOR PLAN, |
| | AND NO FIXTURE BRANCH LINES OR FIXTURES |
| | SHOWN FOR FLOORS 6 THRU 15. SECTION |
| | 104.2.1. |
| | 114B) SHT P3.24 RISER 76 ONLY 4 FU MAX. |
| | ON 2" WET VENT. TABLE 909.3 |
| | 115B) SHT P3.24 RISER 44 OFFSET VENT |
| | REQUIRED. SECTION 915 |
| | 116B) SHT P3.25 RISER 47 16TH FLOOR DOES |
| | NOT REFLECT THE FLOOR PLAN. NO SHOWER ON |
| | RISER. SECTION 104.2.1. |
| | 117B) SHT P3.25 RISER 49 OFFSET VENT |
| | SHALL BE CONNECTED ABOVE THE BRANCH LINE |
| | PRIOR TO OFFSET. SECTION 915 - 16TH |
| | FLOOR 4 FU MAX. ON 2" WET VENT. TABLE |
| | 909.3. - 15TH FLOOR DOES NOT REFLECT THE |
| | FLOOR PLAN. SECTION 104.2.1. |
| | 118B) SHT P3.26 RISER 66 15TH FLOOR 4 FU |
| | MAX. ON 2" WET VENT. TABLE 909.3. |
| | 119B) SHT P3.27 DRY HORIZONTAL VENT NOT |
| | APPROVED. SECTIONS 905.3 & 905.4. - 4 FU |
| | MAX. ON 2" WET VENT. TABLE 909.3 - NO |
| | VENT TERMINATION SHOWN FOR AREA AT LEFT |
| | SIDE OF BLDG DRAIN. - NO VENT SHOWN FOR |
| | LAV AT MEZZ. LEVEL. SECTION 901.2.1. - |
| | OFFSET VENT REQUIRED FOR RISER (6). |
| | SECTION 915. - CLEANOUT REQUIRED 4' AFF |
| | FOR W/M. SECTION 708.10. - VENTS FOR |
| | KITCHEN SINKS DO NOT REFLECT THE FLOOR |
| | PLAN. (NOT SHOWN ON FLOOR PLAN). SECTION |
| | 104.2.1. - INDICATE SHEET NUMBER FOR THE |
| | CONTINUATION OF RISERS 53, 67/83 UNABLE |
| | TO LOCATE. SECTION 104.2.1. |
| | 120B) EVERY VENT STACK SHALL CONNECT TO |
| | THE BASE OF THE DRAINAGE STACK. SECTION |
| | 903.4 |
| | 121B) SHT P3.28 RISER 68 INDICATE SHEET |
| | NUMBER FOR CONTINUATION OF RISER. |
| | SECTION 104.2.1. - RISER 54 OFFSET VENT |
| | REQUIRED, AND 4 FU MAX. ON 2" WET VENT. |
| | SECTION 915 AND TABLE 909.3. - RISER 7 |
| | OFFSET VENTS REQUIRED. UPPER OFFSET, |
| | (2ND FLOOR),VENT SHALL BE CONNECTED TO |
| | THE VERTICAL STACK NOT THE BRANCH LINE. |
| | SECTION 915. - RISER 3, 56, 57 OFFSET |
| | VENT REQUIRED SECTION 915 - DOES NOT |
| | SHOW KITCHEN SINK 5TH FLOOR SECTION |
| | 104.2.1. - MISLABELED AS RISER 51 - |
| | SECTION 104.2.1. - WASH MACHINE GROUND |
| | FLOOR REQUIRES THAT CLEANOUT IS 4' AFF. |
| | SECTION 104.2.1. - RISERS 4, 9, 58, 9 AT |
| | BASE, HORIZONTAL DRY VENT NOT APPROVED. |
| | SECTIONS 905.3 & 905.4. VENT SHALL BE |
| | CONNECTED AT THE BASE OF THE STACK. |
| | SECTION 903.4 - THESE RISERS ARE |
| | INDICATED AS 4, 9, 10, 58, & 59. PLEASE |
| | CORRELATE. SECTION 104.2.1. - OFFSET |
| | SHALL CONNECT ABOVE THE BRANCH LINE. FIG |
| | 915.2. - RISER 58 SOME FIXTURES ARE |
| | MISLABELED, ON NOT LABELED AT ALL. |
| | SECTION 104.2.1. - VENT TERMINATION FOR |
| | 2ND FLOOR BATHROOM NOT SHOWN. SECTION |
| | 104.2.1. - RISER 4/9 MISLABELED FIXTURE. |
| | SECTION 104.2.1, WASH MACHINES, KITCHEN |
| | SINKS, AND BATHROOMS SHALL NOT DRAIN |
| | PAST THE VENT FOR THE BATHROOM ON THE |
| | MEZZ. LEVEL. SECTION 908.3 - DWV FOR THE |
| | MEZZ. LEVEL DOES NOT REFLECT THE FLOOR |
| | PLAN. SECTION 104.2.1. - SECOND FLOOR |
| | POWDER ROOM DOES NOT REFLECT THE FLOOR |
| | PLAN. SECTION 104.2.1. - BATHROOM GROUPS |
| | FOR THE THIRD AND FORTH FLOORS NOT SHOWN |
| | ON RISER 4. SECTION 104.2.1. |
| | 122B) ALL SANITARY RISER DIAGRAMS, SHOW |
| | ALL PIPE SIZES. SIZES ARE MISSING ON |
| | SOME PIPES. SECTION 104.2.1. & TABLE |
| | 710.1(1). |
| | 123B) SHT P3.29 RISER 69 4 FU MAX. ON 2" |
| | WET VENT. TABLE 909.3 - RISER 11 DOES |
| | NOT REFLECT THE FLOOR PLAN - AND NO |
| | BRANCH LINES FROM 4TH FLOOR THRU 15TH |
| | FLOOR. - OFFSET VENTS REQUIRED - RISER |
| | 60 OFFSET VENT REQUIRED - GROUND FLOOR |
| | AT RISER 11/60 DOES NOT REFLECT THE |
| | FLOOR PLAN - RISER 86 SECOND FLOOR DOES |
| | NOT REFLECT THE FLOOR PLAN - SHOW |
| | DESIGNATION NUMBER FOR RISER 88 - RISER |
| | 89 4 FU MAX. ON 2" WET VENT - 89/90/91 |
| | MEZZ. LEVEL BATHROOM DOES NOT REFLECT |
| | THE FLOOR PLAN. SECTIONS 104.2.1. & 915 |
| | TABLE 909.3. |
| | 124B) SHT P3.30 RISER 77 DOES NOT |
| | REFLECT THE FLOOR PLAN, WASH MACHINES |
| | NOT SHOWN. - RISER 47 OFFSET VENTS |
| | REQUIRED, 5TH FLOOR DOES NOT REFLECT THE |
| | FLOOR PLAN, NO KITCHEN SINK SHOWN. - |
| | RISER 49 OFFSET VENTS REQUIRED. - RISER |
| | 49 DOES NOT REFLECT THE FLOOR PLAN, LAV |
| | MISSING IN MASTER BATH 2ND FLOOR, OFFSET |
| | VENTS REQUIRED, 2ND FLOOR INDICATED |
| | DOWNSTREAM OF MEZZ. - RISER 65 DOES NOT |
| | REFLECT THE FLOOR PLAN. - RISER 50 DOES |
| | NOT REFLECT THE FLOOR PLAN ON THE 2ND |
| | FLOOR AND THE 5TH FLOOR, OFFSET VENTS |
| | REQUIRED, FIXTURE MISLABELED, 4 FU MAX. |
| | ON 2" WET VENT, DRY HORIZONTAL VENT NOT |
| | APPROVED. SECTIONS 104.2.1, 915, & TABLE |
| | 909.3 |
| | 125B) SHT P3.31 RISER 24 DOES NOT |
| | REFLECT THE FLOOR PLAN 4TH FLOOR, 4 FU |
| | MAX. ON 2" WET VENT, OFFSET VENTS |
| | REQUIRED, DRY HORIZONTAL VENT NOT |
| | APPROVED. - RISER 54 OFFSET VENTS |
| | REQUIRED. - RISER 26 OFFSET VENTS |
| | REQUIRED. - RISER 27/28 OFFSET VENTS |
| | REQUIRED, 4 FU MAX. ON 2" WET VENT, DOES |
| | NOT REFLECT THE FLOOR PLAN AT/BELOW MEZZ |
| | LEVEL. - RISER 55/28/84 RISER |
| | DESIGNATION NUMBER DOES NOT REFLECT THE |
| | FLOOR PLAN, (SHOW AS 55/73/84), PLEASE |
| | CLARIFY, DOES NOT REFLECT THE FLOOR PLAN |
| | NO WASH MACHINES SHOWN, OFFSET VENTS |
| | REQUIRED. SECTIONS 104.2.1, 915, & TABLE |
| | 909.3. |
| | 126B) SHT P3.32 RISER 29/30/31/32 OFFSET |
| | VENTS REQUIRED, FIXTURE MISLABLED, |
| | FIXTURE BRANCH LINE SHALL NOT CONNECT TO |
| | THE HORIZONTAL OFFSET. - RISER 34 DOES |
| | NOT REFLECT THE FLOOR PLAN, OFFSET VENTS |
| | REQUIRED. - RISER 33/35 OFFSET VENTS |
| | REQUIRED, LAV VENTS 2ND THRU 4TH FLOOR |
| | DO NOT REFLECT THE FLOOR PLAN. - RISER |
| | 56/74/81 OFFSET VENTS REQUIRED, KITCHEN |
| | SINK VENTS DO NOT REFLECT THE FLOOR PLAN |
| | 2ND THRU 4TH FLOORS. - RISER 56 NO |
| | HORIZONTAL DRY VENT, DOES NOT REFLECT |
| | THE FLOOR PLAN 2ND & 3RD FLOORS, (W/M'S) |
| | SECTIONS 104.2.1, AND 711.2. |
| | 127B) SHT P3.33 SANT. ISOMETRIC SHOWS |
| | TWO HORIZONTAL DRY VENTS, LEFT OF RISER |
| | 61. THESE ARE NOT APPROVED. PER SECTIONS |
| | 905.3 & 905.4. - WASH MACHINE LEFT OF |
| | RISER 61 DOES NOT REFLECT THE FLOOR |
| | PLAN, - RISER 61 OFFSET VENT REQUIRED, |
| | DOES NOT REFLECT THE FLOOR PLAN - RISER |
| | 23 INDICATES TWO 4TH FLOORS, LAV ARMS DO |
| | NOT REFLECT THE FLOOR PLAN, OFFSET VENTS |
| | REQUIRED. - RISER 25 EXTRA BRANCH LINE |
| | CONNECTED TO STACK BELOW 2ND FLOOR NOT |
| | APPROVED, OFFSET VENTS REQUIRED, DOES |
| | NOT REFLECT THE FLOOR PLAN 5TH FLOOR, NO |
| | 3RD FLOOR PIPING SHOWN, TUB MISSING 4TH |
| | FLOOR, 4 FU MAX. ON 2" WET VENT. |
| | SECTIONS 104.2.1, 915, 905.3, 905.4, |
| | 706.3 & TABLE 909.3. |
| | 128B) SHT P3.34 RISER 60 DOES NOT |
| | REFLECT THE FLOOR PLAN, UPRIGHT WYE |
| | REQUIRED AT VENT STACK CONNECTION TO THE |
| | WASTE STACK. - RISER 62 DOES NOT REFLECT |
| | THE FLOOR PLAN. - RISER 45 DOES NOT |
| | REFLECT THE FLOOR PLAN, - RISER 64 DOES |
| | NOT REFLECT THE FLOOR PLAN. - RISER 44 |
| | VENT SHALL CONNECT TO BASE OF STACK, |
| | LABEL ALL FIXTURES. - RISER 76 DOES NOT |
| | REFLECT THE FLOOR PLAN, CONNECT VENT |
| | STACK TO BASE OF SANT. STACK, RISER |
| | SHOWS CONDITION ON 2ND FLOOR THAT IS |
| | ACTUALLY ON THE 5TH FLOOR ONLY, DRY |
| | HORIZONTAL VENT NOT APPROVED. - RISER 46 |
| | SHOW ALL PIPE SIZES. SECTIONS 104.2.1, |
| | 905.3, 905.4, |
| | 129B) SHT P3.35 RISER 38 OFFSET VENTS |
| | REQUIRED, RELIEF VENT REQUIRED, RISER |
| | DOES NOT REFLECT THE FLOOR PLAN, (NO |
| | PIPING SHOW FOR 3RD THRU 5TH FLOORS - |
| | SHOWER MISSING IN BATHROOM), - GROUND |
| | FLOOR WASH MACHINE MISLABELED AS SHOWER, |
| | CLEANOUT SHALL BE 4' AFF AT W/M. - |
| | IDENTIFY OTHER RISER AT END OF RUN. |
| | SECTIONS 104.2.1, 915, 914, 708.10. |
| | 130B) SHT P3.36 GROUND FLOOR DOES NOT |
| | REFLECT THE FLOOR PLAN, (FD IN TRASH |
| | ROOM NOT SHOWN, KITCHEN SINK - W/M AREA, |
| | AND VENTING), INDICATE WHY 10 FU FOR |
| | CLEANOUT AT END OF RUN. - RISER 71 |
| | OFFSET VENTS REQUIRED, NO PIPING FOR 3RD |
| | FLOOR, NO KITCHEN SINK ON 4TH FLOOR, |
| | INDICATE FLOOR LEVEL TOP OF RISER. - |
| | RISER 37 VENT STACK SHALL CONNECT AT THE |
| | BASE OF THE STACK, NO HORIZONTAL DRY |
| | VENT, OFFSET VENT REQUIRED, 5TH FLOOR |
| | DOES NOT REFLECT THE FLOOR PLAN, FIXTURE |
| | MISLABELED AND 4 FU MAX. ON 2" WET VENT |
| | 4TH FLOOR, UNABLE TO FIND CONTINUATION |
| | OF RISER. - RISER 36 SHOWS TYPICAL |
| | PIPING FOR 3RD & 4TH FLOORS, BUT FLOOR |
| | PLANS ARE DIFFERENT. SECTIONS 104.2.1. |
| | 915, 903.4, 905.3, 905.4. |
| | 131B) SHT P3.37 CHECK ADDITION FOR |
| | SQUARE FOOTAGE AT DRAINS. 4" @ 1665 SF |
| | TO BE A MINIMUM OF 5" PIPE RWL 4 TABLE |
| | 1106.3. SOME FITTINGS NOT DIRECTING |
| | STORM WATER IN DIRECTION OF FLOW. - SHOW |
| | SF FOR TD'S GROUND FLOOR DRAINAGE RISER. |
| | 132B) SHT O3.38 CHECK ADDITION ON RWL |
| | 2&3. IS 3" PD 680SF OR 80 SF? PLUS CHECK |
| | ADDITION OF PD'S & DD'S = 963 SF BUT |
| | 2320 SF SHOWN. 5TH FLOOR RISER 2/3 DOES |
| | NOT REFLECT THE FLOOR PLAN. DD @603 SF & |
| | PD @ 1018 SF NOT SHOWN. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 133B) SHT P3.39 RECHECK ADDITION OF SF |
| | AS IT ACCUMULATES IN THE SYSTEM, SOME |
| | DRAIN SF DOES NOT REFLECT ROOF PLAN SF |
| | AT DECK DRAINS, & PLANTER DRAINS, PIPE |
| | SIZING NOT CORRECT, SHOW SF AS IT |
| | ACCUMULATES IN THE SYSTEM, SHOW SLOPE OF |
| | PIPE REQUIRED. SECTION 104.2.1, 1106, & |
| | 1107. |
| | 134B) THE FOLLOWING UNITS WERE NOT |
| | LOCATED. "C2", 'D2" & "BT" PLEASE |
| | INDICATE LOCATION FOR THESE UNITS. |
| | 135B) THE FOLLOWING WATER RISER DIAGRAMS |
| | WERE NOT FOUND: SHTS P2.16/P2.22 "B7", |
| | SHTS P2.29 "B", SHT P2.33 "J1", P2.35 |
| | "B", P2.41 "B", P2.46 "S1", P2.52 "S1" |
| | 135B) PLANS STILL SEEM TO BE INCOMPLETE |
| | AND MORE COMMENTS MAY BE FORTHCOMING |
| | WHEN PLANS ARE RESUBMITTED. RED LINE |
| | PLANS WERE REQUESTED TO BE RETURNED TO |
| | HELP THE REVIEW PROCESS FOR THE SECOND |
| | REVIEW. THESE WERE NOT RETURNED. I WILL |
| | BE KEEPING THE RED LINE SET OF PLANS IN |
| | ORDER TO HELP THE REVIEW PROCESS ON NEXT |
| | RESUBMIT. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. - |
| | THIS ALSO WAS NOT DONE WHEN PLANS WERE |
| | RESUBMITTED. MOST RESPONSE NOTES WERE NO |
| | MORE THAN A FEW WORDS AND NO INDICATION |
| | OF WHERE CORRECTION COULD BE FOUND, |
| | RESULTING IN MANY HOURS REVIEWING THE |
| | PLANS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |