| 2005-04-19 00:00:00 | DENIED: |
| | RESPONSE COMMENTS FROM REVIEW DATED |
| | 1/18/05: |
| | COMMENT #3 RESPONSE - SEE M2.01. PLAN |
| | DOES NOT PROVIDE DISTANCES FROM EXHAUST |
| | TERMINATION TO FRESH AIR INTAKES, |
| | WINDOWS, DOORS, LOUVERS, ETC.PROVIDE |
| | ELEVATION FROM GRADE.PLAN ALSO |
| | REFERENCES PLAN SHEET M6.01 FOR DETAILS. |
| | NO DETAILS PROVIDED ON SAID SHEET. |
| | |
| | COMMENT #4 - PROVIDE FILL PIPE |
| | INFORMATION FOR THE FUEL TANK INDICATED |
| | ON PLAN SHEET M2.01.PLAN SHEET A4.01 |
| | INDICATES THE CAPACITY AS 500 GAL. |
| | PLEASE NOTE, ADDITIONAL PERMIT REQUIRED |
| | FOR FUEL. |
| | |
| | COMMENT #5 - PROVIDE SUBMITTALS; |
| | RESPONSE INDICATES SUBMITTALS TO BE |
| | PROVIDE WITH "SHOP DRAWING" REVIEW. |
| | EQUIPMENT SUBMITTALS ARE TO BE SUBMITTED |
| | WITH THE ENGINEERED PLANS. |
| | |
| | COMMENTS #10, 11 & 12 - EXHAUST DUCTS |
| | ARE RUNNING THROUGH THE RETURN AIR |
| | PLENUM. RESPONSE - REFER TO DRAWING |
| | M2.02, NOTES INDICATE WRAPPING DUCT. |
| | PLAN STILL INDICATES THE INSTALLATION OF |
| | DRYER BOOSTER FANS.THIS WILL NOT BE |
| | ACCEPTED UNTIL THE AN ENGINEER FROM |
| | DRYER MANUFACTURER ACCEPTS THIS ASSEMBLY |
| | AND VERIFIES THAT IT WILL NOT VOID THE |
| | WARRANTY ON THE DRYER.DUCTS THAT CARRY |
| | PRODUCTS OF COMBUSTION AND PRODUCE HEAT |
| | & MOISTURE SHALL NOT RUN THROUGH THE |
| | PLENUM. 2001FBC/M 504.1, 504.4, 601.3. |
| | |
| | COMMENT #14 - PROVIDE SUBMITTALS FOR ALL |
| | EQUIPMENT - RESPONSE "CORRECTED" BUT NO |
| | SUBMITTALS WERE PROVIDED. |
| | |
| | COMMENT #15 - O.A. CALCULATIONS - |
| | RESPONSE REFER TO DRAWING M5.04. OUTSIDE |
| | AIR CALCULATIONS WERE NOT PROVIDED FOR |
| | THE RESIDENTIAL UNITS. |
| | |
| | NEW COMMENTS: |
| | 16. RETURN AIR FROM THE BEDROOM AREAS |
| | ARE NOT SIZED PROPERLY.PER 2001 FBC/M |
| | 601.4 EXCEPTION 1, WHEN TRANSFER DUCTS |
| | ARE USED FOR RETURN AIR THE RETURN AIR |
| | DUCT SHALL BE A MINIMUM OF 1 1/2 TIMES |
| | THE SQUARE INCHES OF THE SUPPLY AIR INTO |
| | THAT SPACE.WHEN CALCULATING RETURN AIR |
| | FROM THE MASTER SUITE ALL AIR INTO THE |
| | MASTER SUITE IS TO BE INCLUDED. |
| | |