| 2005-04-08 00:00:00 | ************ UNSAT 2ND REVIEW ********* |
| | |
| | PLEASE SEE MANY NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | PLEASE ALSO SEE NEW NOTES DUE TO PLANS |
| | CONTAINING MORE INFORMATION THAN |
| | SUBMITTED ON PREVIOUS REVIEW. |
| | |
| | *************************************** |
| | PLEASE SEE FIRST PART OF REVIEW IS A |
| | DIRECT OVERVIEW OF PREVIOUS NOTES, NEW |
| | NOTES WILL BE FOLLOWING. |
| | *************************************** |
| | |
| | 1)NOTE: NOTE #1, OK, HOWEVER PLEASE SEE |
| | NOTE #19 IN THIS AND PREVIOUS REVIEW. |
| | |
| | 2)NOTE: NOTE #2 NO, PLEASE SEE REQUIRED |
| | WIND LOADING INFORMATION IS NOT NOTED ON |
| | ELECTRICAL PLANS FOR POLES. IF THIS |
| | INFORMATION IS PROVIDED ON ADDITIONAL |
| | SHEETS FOR BLDG REVIEW, THIS IS FINE AND |
| | REQUIRED, HOWEVER THIS INFORMATION WILL |
| | NEED TO BE ELECTRICAL SHEET FOR |
| | ELECTRICAL CONTRACTOR ETC. |
| | WINB LOADING NOTE(S) SHOULD REFERENCE |
| | FBC 140 MPH. |
| | |
| | 3)NOTE: NOTE #3 NO, PLEASE SEE SHEET |
| | ATTACHED WHICH IS A PRINT OUT FROM |
| | DBPR'S WEBSITE. PLEASE SEE LICENSE |
| | INFORMATION PROVIDED ON TITLE BLOCKS FOR |
| | ARCHITECTUAL FIRM DOES NOT APPEAR TO BE |
| | ACCURATE. PLEASE SEE ATTACHED SHEET |
| | WHICH SHOWS BC ARCHITECTS INC. WITH AN |
| | ARCHITECTUAL BUS/FIRM LICENSE NUMBER OF |
| | AA#0003360. PLEASE SEE TITLE BLOCKS FOR |
| | ALL SHEETS AND FOR ALL TRADES APPEARS TO |
| | INDICATE THIS FIRM LICENSE NUMBER AS |
| | 0008129???. |
| | PLEASE SEE FAC 61G1-16.004, FS 481.219. |
| | PLEASE SEE THIS IS REQUIRED ON ALL |
| | SHEETS AND FOR ALL TRADES WHEATHER OR |
| | NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | PLEASE SEE ENGINEERING FIRM'S TITLE |
| | BLOCK HAS BEEN CORRECTED. |
| | |
| | 4)NOTE: NOTE #4, OK. NOTE ADDED FOR "NO |
| | SWIMMING" AFTER DUSK. |
| | |
| | 5)NOTE: NOTE #5 OK. |
| | |
| | 6)NOTE: NOTE #6 OK, FIRE RATING VERIFIED |
| | FOR DIRECT ACCESS TO MAIN ELECTRICAL |
| | ROOM. HOWEVER, NOTES FOR SIGNAGE, MAPS |
| | AND/OR DIRECTORY COULD NOT BE LOCATED ON |
| | PLANS. |
| | 230.2E 700.8A,701.9,702.8 ETC. |
| | A SIGN SHALL BE PLACED AT THE SERVICE |
| | ENTRANCE EQUIPMENT INDICATING TYPE AND |
| | LOCATION OF ON-SITE EMERGENCY POWER |
| | SOURCES. |
| | PLEASE SEE ALL SIGNAGE REQUIRED TO BE 1" |
| | MIN WITH CONTRASTING BACKGROUND. |
| | SIGNAGE/MAPPINGALSO REQUIRED AT FIRE |
| | COMMAND RM AND AT ACCESS DOOR CLOSEST TO |
| | MAIN ELECTRICAL ROOM. |
| | SIGNAGE FOR ALL ELECTRICAL ROOMS. |
| | PLEASE ALSO SEE 110.16 |
| | 110.16 FLASH PROTECTION. |
| | SWITCHBOARDS, PANELBOARDS, INDUSTRIAL |
| | CONTROL PANELS, AND MOTOR CONTROL |
| | CENTERS THAT ARE IN OTHER THAN DWELLING |
| | OCCUPANCIES AND ARE LIKELY TO REQUIRE |
| | EXAMINATION, ADJUSTMENT, SERVICING, OR |
| | MAINTENANCE WHILE ENERGIZED SHALL BE |
| | FIELD MARKED TO WARN QUALIFIED PERSONS |
| | OF POTENTIAL ELECTRIC ARC FLASH HAZARDS. |
| | THE MARKING SHALL BE LOCATED SO AS TO BE |
| | CLEARLY VISIBLE TO QUALIFIED PERSONS |
| | BEFORE EXAMINATION, ADJUSTMENT, |
| | SERVICING, OR MAINTENANCE OF THE |
| | EQUIPMENT. |
| | SEE FIRE COMMENTS FOR "KNOW BOX" |
| | LOCATIONS. |
| | |
| | 7)NOTE: NOTE #7,OK HOWEVER PLEASE SEE |
| | SHEETS E 2.11,2.12, MANY ELECTRICAL |
| | DEVICES/FIXTURES APPEAR TO BE SHOWN WITH |
| | OUT CIRCUITS. ARE THESE MISPRINTED AND |
| | REPEATED ON OTHER SHEETS. |
| | |
| | 8)NOTE: NOTE #8 NO, PLEASE SEE 620.23.24 |
| | ETC. |
| | PLEASE SEE ELEVATOR EQUIPMENT RMS. |
| | A SEPARATE BRANCH CIRCUIT SHALL SUPPLY |
| | THE MACHINE ROOM OR CONTROL |
| | ROOM/MACHINERY SPACE OR CONTROL SPACE |
| | LIGHTING AND RECEPTACLE(S). |
| | A SEPARATE BRANCH CIRCUIT SHALL SUPPLY |
| | THE HOISTWAY PIT LIGHTING AND |
| | RECEPTACLE(S). |
| | |
| | 9)NOTE: NOTE #9 NO, PLEASE SEE RECETPS |
| | WERE ADDED HOWEVER, ID SCALE IS CLOSE AS |
| | INDICATED, SOME RECEPTS APPEAR TO BE |
| | WITHIN THE RESTRICATED 10' AREA. |
| | PLEASE SEE 620.22A3 |
| | PLEASE ALSO SEE NEW NOTE FOR LIGHTING |
| | AROUND POOLS. |
| | |
| | 10)NOTE: NOTE #10 OK, REFERENCES |
| | CHANGED. |
| | |
| | 11)NOTE: NOTE #11 OK, HOWEVER PLEASE SEE |
| | NEW NOTES FOR BATH/TUB/JACUZZI FIX. |
| | |
| | 12)NOTE: NOTE #12 NO, PLEASE SEE UNITS |
| | ARE STILL SHOWN WITHOUT ACCESS TO |
| | GARAGE. |
| | AS PER CONVERSATION WITH MR. RAPL BAEZA, |
| | NO ACCESS WAS GOING TO BE INSTALLED FROM |
| | GARAGE IN DESIGN. |
| | PLEASE SEE BLDG REVIEW COMMENTS BY MR. |
| | ROBERT BROWN, ACCESSIBILTY FROM GARAGE |
| | MAY BE REQUIRED. |
| | IF SO, PLEASE SEE 210.70 AND LS101 5-8. |
| | |
| | 13)NOTE: NOTE #13 NO, PLEASE SEE GRADE |
| | LEVEL ACCESS REQUIRES MEANS OF EGRESS |
| | LIGHTING/CONTROL. PLEASE ALSO SEE |
| | EXCEPTIONS. |
| | |
| | 14)NOTE: NOTE #14, OK, HOWEVER PLEASE |
| | SEE NOTE #7. |
| | |
| | 15)NOTE: NOTE #15 OK FOR SD'S HOWEVER |
| | PLEASE SEE NEW COMMENTS FOR CIRCUITING |
| | AND ARC FAULT PROTECTION. |
| | |
| | 16)NOTE: NOTE #16 OK. |
| | |
| | 17)NOTE: NOTE #17 NO, PLEASE SEE 210.52D |
| | FOR GFI REQUIRED WITHIN 3' OF SINK/LAV |
| | EDGE. |
| | PLEASE SEE PLANS AHVE SOME REDLINED AT |
| | LOCATION(S) MISSING. |
| | |
| | 18)NOTE: NOTE #18 NO, PLEASE SEE |
| | ELECTRICLA PANELS NOT PERMITTED ON |
| | CLOSETS. PLEASE SEE 110.26,408.7,240.24 |
| | ETC. |
| | PLEASE SEE 240.24OVER CURRENT |
| | PROTECTION IS NOT TO BE LOCATED IN THE |
| | VICINITY OF EASILY IGNITIBLE MATERIAL. , |
| | SUCH AS IN CLOTHES CLOSETS. |
| | PLEASE ALSO SEE NEW NOTES BAOUT CATV AND |
| | TELEPHONE CABINETS. |
| | |
| | 19)NOTE: NOTE #19 NO, PLEASE SEE SOME |
| | UNITS STILL SHOW A COUPLE OF ELECTRICAL |
| | PANELS IN "LT GRAY". THIS APPEARS TO BE |
| | MISPRINTS . PLEASE SEE UNIT HD FOR ONE. |
| | |
| | 20)NOTE: NOTE #20 OK, HOWEVER PLEASE SEE |
| | NOTE #28 FOR 110.26 |
| | |
| | 21)NOTE: NOTE #21 OK. |
| | |
| | 22)NOTE: NOTE #22 NO, PLEASE SEE MANY |
| | UNITS HAVE BEEN REDLINED FOR AREAS IN |
| | QUESTION. PLEASE SEE 210.52C1-5 FOR |
| | REQUIRED LOCATIONS OF GFI RECEPTS ALONG |
| | KITCHEN COUNTERSPACES, INCLUDING |
| | PENINSULARS AND " SEPARATE SPACES". |
| | 210.52C2,4 |
| | |
| | 23)NOTE: NOTE #23 NO, CPULD NOT LOCATE |
| | NOTE REQUESTED FOR SD PLACEMENT ON |
| | PLANS. |
| | PLEASE CLARIFY WHERE THIS IS. |
| | PLEASE SEE NFPA-72 8-1.4.2 FOR THESE |
| | LOCATIONS. |
| | |
| | 24)NOTE: NOTE #24 NO, PLEASE SEE GFI |
| | RECEPTS WERE ADDED TOLOWER TERRACE |
| | LEVELS BUT NONE TO UPPER TERRACES. |
| | PLEASE SEE UPPER TERRACE ON ELECTRICAL |
| | PLANS APPEAR TO BE SHOWN MUCH LARGER |
| | THAN TERRACES SHOWN ON ARCH SHEETS. |
| | THIS IS ONLY A NOTE AND LIGHTING OR GFI |
| | RECEPTS ARE NOT REQUIRED ON THE SMALLER |
| | OR LARGE TERRACES, HOWEVER OF THEY ARE |
| | GOING TO BE INSTALLED, PLEASE SHOW ON |
| | PLANS AT THIS TIME OR PLANS WILL BE |
| | REQUIRED TO BE REVISED AT A LATER DATE. |
| | |
| | 25)NOTE: NOTE #25 YES/NO , GFI BRKR |
| | NOTED AT PANEL SCHEDULES,HOWEVER A |
| | POWER/RECEPT COULD NOT BE LOCATED ON |
| | PLANS AT THESE UNITS. |
| | PLEASE SHOW. |
| | |
| | 26)NOTE: NOTE #26NO. PLEASE SEE NO |
| | INFORMATION EXCEPT THAT FIRE PUMP IS |
| | GOING TO BE 250 HP. PLEASE SEE KEYNOTES |
| | K-23 DOES NOT PROVIDE ENOUGH |
| | INFORMATION. |
| | PLEASE ALSO SEE NEW NOTES PERTAINING TO |
| | FIRE PUMP/CONTROLLER ETC. |
| | PLEASE SEE PREVIOUS REQUEST WAS TO HAVE |
| | ALL MANUFACTURE SPEC SHEETS SUBMITTED |
| | FOR FIRE PUMP, FIRE PUMP CONTROLLER, ETC |
| | NONE COULD BE LOCATED IN SPECS, |
| | SUBMITTALS??? |
| | SEE NEW NOTES: |
| | |
| | 27)NOTE: NOTE #27 NO, PLEASE SEE ABOVE |
| | NOTE. PLEASE SE NO SPECS FOR GENERATOR, |
| | SUB BASE FUEL TANK ATS WERE SUBMITTED. |
| | 215.5 |
| | PLEASE SEE NEW NOTES FOLLOWING. |
| | |
| | 28)NOTE: NOTE #28 NO, PLEASE SEE NOTE |
| | WAS ADDED TO ONE SHEET ONLY. PLEASE SEE |
| | SPECIFICS NOTES FOR 110.26 WILL BE |
| | REQUIRED ON ALL SHEETS SHOWING |
| | ELECTRICAL ROOMS AND ELECTRICAL CLOSETS. |
| | |
| | PLEASE SEE THIS NOTE SHOULD REFLECT "ALL |
| | ELECTRICAL ROOMSAND ELECTRICAL CLOSETS |
| | SHALL MEETS ALL THE REQUIREMENTS OF |
| | 110.26 AND ALL OTHER REQUIREMENT OF |
| | 2002 NEC" PLEASE SEE WE ARE HAVING MANY |
| | ISSUES WHERE WIDTHS ARE BEING MET, |
| | HOWEVER HEIGHT REQUIREMENTS ARE NOT. |
| | SEE NEW NOTES ALSO. |
| | |
| | 29)NOTE: NOTE #29 OK. |
| | |
| | 30)NOTE: NOTE #30 NO, PLEASE SEE MORE |
| | THAN ONE "K" NOTE LOCATED ON KEYNOTES DO |
| | NOT CORRELATE OR SHOWN "BLANK" OR NOTED |
| | AS NOT BEING USED, HOWEVER PLANS DO NOT |
| | MATCH THESE. |
| | PLEASE SEE K26,K35, ETC. |
| | PLEASE SEE NEW NOTES FOR F AND K NOTES |
| | WHICH DO NOT CORRELATE WITH PLANS. |
| | PLEASE SEE NEW NOTES: |
| | |
| | 31)NOTE: NO, PLEASE SEE RESPONSE LTR |
| | MENTIONS "WILL COMPLY" HOWEVER PLEASE |
| | SEE NEW NOTES PERTAINING TO NOTES ON |
| | PLANS AND SPECS. |
| | |
| | 32)NOTE: NOTE #32 OK, NOTE ADDED , GEN |
| | WILL NOT BE SEPARATELY DEREVED. THIS |
| | WILL BE VERIFIED ONCE MANUFACTURE SPECS |
| | ARE SUBMITTED. |
| | SEE NEW NOTES ALSO; |
| | |
| | 33)NOTE: NOTE #33 OK, HOWEVER PLEASE SEE |
| | NEW NOTES PERTAINING TO FEEDER SIZES. |
| | |
| | 34)NOTE: NOTE #34 NO, PLEASE SEE RISER |
| | DIAGRAM STILLDOES NOT INCLUDE A |
| | REDUCED "KEYED NOTES" OR RECDUCED |
| | "FEEDER SCHEDULE FOR REFERENCE WITHOUT |
| | HAVING TO TURN BACK AND FORTH FROM RISER |
| | DIAGRAM PAGE TO E-6.13. |
| | 215.5. |
| | PLEASE SEE NEW NOTES FOR250.30 |
| | PLEASE SEE RISER INDICATES 3000A |
| | BUS-STAB INTO FPL VAULT FEEDING 4000A |
| | MAINS?? PLEASE CORRELATE. |
| | PLEASE SEE RISER SHOWS 3000A MAIN |
| | FEEDING 4000A BUS-DUCT THEN CHANGES BACK |
| | TO 3000A BUS DUCT?? |
| | |
| | 35)NOTE: NOTE #35 OK, HOWEVER SEE NEW |
| | NOTES FOR CORRELATIONOF METER CENTERS |
| | AND LOAD CALCULATIONS/ EQUIPMENT. |
| | |
| | 36)NOTE: NOTE # 36 OK, OVEN ADDED, |
| | RANGES CHANGED. |
| | |
| | 37)NOTE: NOTE #37 PLEASE SEE "FEEDER |
| | HOME RUN SCHEDULE" WAS ADDED TO MOST |
| | SHEETS CONTAINING PANEL SCHEDULE, BUT |
| | SEE PLANS FOR MISSING DETAIL. PLEASE |
| | ALSO SEE NEW NOTES PERTAINING TO PANELS |
| | SIZES. |
| | |
| | 38)NOTE: NOTE #38 NO, PLEASE SEE |
| | PANELS STILL SHOWN AS 200A WITH 225A OCP |
| | FEEDING PANEL(S). PLEASE SEE THE 250A |
| | OCP WAS REMOVED. |
| | |
| | 39)NOTE: NOTE #39 NO, PLEASE SEE WATER |
| | HEATERS SHOWN WITH 2P50A OCP FOR 4500VA |
| | UNITS ON #10 AWG. |
| | PLEASE ALSO SEE 6KW WITH 30A OCP. |
| | PLEASE SEE MIN OCP IS 125% AND MAX OCP |
| | IS 150%. |
| | PLEASE SEE 422.13,422.11,240.4, 310.16 |
| | ETC. |
| | |
| | *************************************** |
| | NEW NOTES FOR REVIEW. |
| | |
| | 40)NOTE: PLEASE SEE MIN REQUIREMENTS FOR |
| | ELECTRICAL LIGHT FIXTURES FORM SWIMMING |
| | POOL. IF SCALE IS USED AS INDICATED ON |
| | PLANS, SOME FIXTURES SHOWN AS CLOSE AS |
| | 3' FROM WATER'S EDGE. |
| | PLEASE SEE 680.22 AND PREVIOUS NOTES FOR |
| | RECEPT PLACEMENT. |
| | |
| | 41)NOTE: PLEASE CLARIFY MANY |
| | ELECTRICAL/GENERATOR RMS CONTAIN EM LT |
| | FIXTURES ON EM CIRCUIT BUT YET THESE ARE |
| | ALSO BATTERY BACK UP? PLEASE SEE THEN |
| | ARE MANY ELECTRICAL RMS WHICH DO NOT |
| | CONTAIN BATTERY BACK UP? |
| | THIS IS ONLY A NOTE. |
| | |
| | 42)NOTE: PLEASE SEE MANY UNITS, 5,6,8 |
| | ETC FOR REQUIRED RECEPTS PER 210.52. |
| | PLEASE SEE 2' OF WALL SPACES INT |
| | KITCHENS, BEDROOMS(EVEN IF BEHIND |
| | DOORS). |
| | PLEASE SEE MANY REDLINED AT LOCATIONS ON |
| | PLANS. |
| | |
| | 43)NOTE: PLEASE SEE MOST DRYER LOCATIONS |
| | INDICATE A MANUAL SWITCH FOR DRYER |
| | "BOOST FAN" YET MANY DO NOT CONTAIN THIS |
| | SAME SW? |
| | HOWEVER, PLEASE SEE NOTES LOCATED ON |
| | EACH SHEET WHICH MENTIONS THAT THESE |
| | WILL BE AUTOMATICALLY INTERCONNECTED? |
| | PLEASE SEE MECHANICAL NOTES FOR THIS |
| | SAME ITEM. IT APPEARS INTERCONNECTING |
| | ANY DEVICES IN THESE FANS/ DRYERS MAY |
| | VOIDED WARRANTIES AND/OR VOIDED LISTINGS |
| | FROM MANUFACTURE. |
| | |
| | 44)NOTE: PLEASE SEE AS MENTIONED ON |
| | ORIGINAL NOTES, ARC FAULT PROTECTION |
| | REQUIRED PER 2002 NEC 210.12, HOWEVER |
| | THERE ARE NUMEROUS AREAS IN MOST UNITS |
| | IN WHICH CIRCUITING FOR LIGHTING ETC |
| | DOES NOT HAVE THE "* " ON THE CIRCUIT |
| | #'S ON PANEL SCHEDULE FOR THE |
| | PROTECTION. |
| | PLEASE SEE ALL "OUTLETS" INCLUDING SD'S, |
| | LTS, FANS AND RECEPTS REQUIRED THIS. |
| | PLEASE SEE MANY OF THESE CIRCUIT #'S |
| | HAVE BEEN REDLINED ON PLANS, BUT NOT |
| | ALL. |
| | |
| | 45)NOTE: PLEASE SEE SOME UNITS ARE |
| | SHOWING FIXTURES IN SOME UTILITY/CLOTHES |
| | CLOSETS WHICH DO NOT APPEAR TO MEET |
| | 410.8 FOR MIN CLEARENCE. PLEASE VERIFY. |
| | |
| | 46)NOTE:PLEASE VERIFY FIXTURE |
| | CLEARENCE OVER TUBS/HYDRO ETC. AN |
| | ELEVATION IS NOT SHOWN FOR MIN CLEARENCE |
| | AND WE HAVE ENCOUNTERED MANY WHICH FALL |
| | BELOW MIN CLEARENCE EVEN FOR A RECESSED |
| | LT WITH AN ENCLOSED COVER. |
| | THIS IS ONLY A NOTE: |
| | |
| | 47)NOTE: SEE PREVIOUS/UPPER NOTES, UNIT |
| | # H-7 FOR MISSING GFI W/IN 3' OF SINK. |
| | 210.52 |
| | |
| | 48)NOTE: PLEASE SEE UNIT A-1 WHICH |
| | INDICATES A THIRD SMALL APPL CIRCUIT , |
| | HOWEVER THIS COULD NOT BE LOCATED ON |
| | PLANS? |
| | |
| | 49)NOTE: PLEASE SEE UNIT V-1 THIS |
| | APPEARS TO HAVE "ALL" DEVICES SHIFTED |
| | AND REVIEW FOR PLACEMENT FOR THESE |
| | DEVICES CAN NOT BE DONE AT THIS TIME. |
| | |
| | 49)NOTE: PLEASE SEE MANY CLOTHES CLOSETS |
| | CONTAINING COMBUSTIBLES ARE SHOWN WITH |
| | CATV AND TELEPHONE CABINETS. PLEASE SEE |
| | IF THESE UNITS WILL REQUIRE ANY "LV |
| | PLUG-IN" TYOE TRANSFORMERS THEN THESE |
| | RECEPTS WHICH ARE NOT SHOWN AT THIS TIME |
| | WOULD ONLY BE ALLOWED DIRECTLY OVER |
| | DOORS. |
| | PLEASE SEE PLANS DO NOT INDICATE ANY LV |
| | ALARM PANELS AT THIS TIME AND SAME WOULD |
| | BE REQUIED IF LOCATED IN A CLOTHES |
| | CLOSET. THIS IS ONLY A NOTE: |
| | |
| | 50)NOTE: PLEASE SEE 2002 210.8B3 FOR |
| | KITCHENS IN OTHER THAN DWELLING UNITS. |
| | THIS WOULD BE FOR "HOUSE KITCHEN". |
| | |
| | 51)NOTE: PLEASE SEE SOME UNITS WHICH DO |
| | NOT SHOW DEVICES, MENTIONS TO SEE OTHER |
| | SIMILAR UNITS, HOWEVER PLEASE SSE SOME |
| | ARE MSSING OR DO NOT CORRELATE. |
| | PLEASE SEE "B" UNIT, 3.23, "D-1"AND |
| | "D" UNIT ON 3.25. |
| | |
| | 52)NOTE: PLEASE SEE FIRE COMMAND ROOM |
| | LAYOUT DO NOT NOT CORRLETATE FOR LAYOUT |
| | AND EQUIPMENT IN ROOMS AS NOTED. |
| | 8.05,4.01 |
| | |
| | 53)NOTE: PLEASE SEE RISER AND PLANS DO |
| | NOT INDICATE ANY INFORMATION FOR |
| | DISC/BRKRS/OCP LOCATED ON GENERATOR FOR |
| | FEED/FEEDS TO GUTTER AND ON TO |
| | DISCONNECTS LOCATE DIN GEN RM. |
| | 215.5 COMPLIANCE CAN NOT BE VERIFIED AT |
| | THIS TIME. |
| | |
| | 54)NOTE: PLEASE SEE GROUND FUALT |
| | PROTECTION FOR SHN CAN NOT BE VERIFIED. |
| | CAN NOT LOCATE ON PLANS, RISER OR PANEL |
| | DETAIL/SCHEDULE. |
| | PLEASE SEE 240, GROUND-FAULT PROTECTION |
| | OF EQUIPMENT SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THE PROVISIONS OF 230.95 |
| | FOR SOLIDLY GROUNDED WYE ELECTRICAL |
| | SYSTEMS OF MORE THAN 150 VOLTS TO GROUND |
| | BUT NOT EXCEEDING 600 VOLTS |
| | PHASE-TO-PHASE FOR EACH INDIVIDUAL |
| | DEVICE USED AS A BUILDING OR STRUCTURE |
| | MAIN DISCONNECTING MEANS RATED 1000 |
| | AMPERES OR MORE. |
| | |
| | 55)NOTE: PLEASE SEE K-27 MENTIONS TO SEE |
| | TRANSFORMER GROUNDING DETAIL, HOWEVER |
| | THIS COULD NOT BE LCOATED ON PLANS.? |
| | PLEASE SHOW EITHER A TYPICAL DETAIL OR |
| | SHOW EACH. 250.30,215.5 |
| | |
| | 56)NOTE:PLEASE SEE KEYNOTE K-31, |
| | MENTIONS PER NAMEPLATE, HOWEVER |
| | DISCONNETC SIZES ETC, ARE REQUIRED AT |
| | THIS TIME A S MIN. 215.5 |
| | PLEASE ALSO SEE K-NOTE FOR ELEVATOR |
| | CONTROLLER. |
| | |
| | 57)NOTE: PLEASE SEE GUTTER SHOWN AT |
| | GENERATOR ROOM REFERENCES TO MEET 366. |
| | PLEASE SEE FBC 104.2.1, CODES FOR |
| | SPECIFIC DESIGNS ARE NOT TO BE REFERNECD |
| | IN WHOLE OR IN-PART. PLEASE SHOWN MIN |
| | GUTTER SIZE. |
| | PLEASE ALSO SEE NO CONDUCTORS SIZES ARE |
| | SHOWN, NO CONDUIT SIZES AND NO OCP |
| | (PREVIOUS NOTE) ARE SHOWN TO VERIFY |
| | COMPLIANCE. 310.16,215.5 240.4 ETC. |
| | |
| | 58)NOTE: PLEASE SEE K-24, K25, NO SIZE |
| | FOR CONDUIT, FEEDER ETC FROM FIRE PUMP |
| | CONTROLLER TO FIRE PUMP. PLEASE SEE |
| | PLANS INDUCATE A "MAGNETIC TYPE" BRKR, |
| | HOWEVER NO SIZE IS GIVEN? |
| | 215.5,310.16 ETC. |
| | PLEASE SEE PREVIOUS NOTES. |
| | |
| | 59)NOTE: PLEASE SEE "SPEC BOOK", 16465 |
| | 2.2C WHICH MENTIONS ALUM BUS-DUCT. |
| | PLEASE SEE PREVIOUS NOTES IN REFERENCE |
| | TO EQUIPMENT GROUNDING METHOD OF |
| | BUS-DUCT. DOES THIS BUS-DUCT CONTAIN A |
| | SEPARATE ALUM BUS FOR GROUNDING? OR IS |
| | THE EQUIPMENT GROUNDING THAT IS GOING TO |
| | BE USED "PART" OF THE BUS-DUCT. |
| | PLEASE ALSO PLACE NOTE ON PLANS FOR |
| | REQUIRED CURBS FOR FLOOR PENATRATIONS. |
| | PER 368.6BFLOOR PENETRATIONS SHALL |
| | COMPLY WITH (1) AND (2): |
| | BUSWAYS SHALL BE PERMITTED TO BE |
| | EXTENDED VERTICALLY THROUGH DRY FLOORS |
| | IF TOTALLY ENCLOSED (UNVENTILATED) WHERE |
| | PASSING THROUGH AND FOR A MINIMUM |
| | DISTANCE OF 1.8 M (6 FT) ABOVE THE FLOOR |
| | TO PROVIDE ADEQUATE PROTECTION FROM |
| | PHYSICAL DAMAGE. |
| | IN OTHER THAN INDUSTRIAL ESTABLISHMENTS, |
| | WHERE A VERTICAL RISER PENETRATES TWO OR |
| | MORE DRY FLOORS, A MINIMUM 100 MM (4 |
| | IN.) HIGH CURB SHALL BE INSTALLED AROUND |
| | ALL FLOOR OPENINGS FOR RISER BUSWAYS TO |
| | PREVENT LIQUIDS FROM ENTERING THE |
| | OPENING. THE CURB SHALL BE INSTALLED |
| | WITHIN 300 MM (12 IN.) OF THE FLOOR |
| | OPENING. ELECTRICAL EQUIPMENT SHALL BE |
| | LOCATED SO THAT IT WILL NOT BE DAMAGED |
| | BY LIQUIDS THAT ARE RETAINED BY THE |
| | CURB. |
| | |
| | 60)NOTE: PLEASE SEE "SPEC BOOK" 16120 |
| | 2.3A5, PLEASE SEE COLOR CODING FOR |
| | 277/480V SHALL BE BROWN, PURPLE, YELLOW. |
| | 215.8 LOCAL AMENDMENTS. |
| | |
| | 61)NOTE: THIS IS ONLY A NOTE: PLEASE SEE |
| | LOAD ON HGMN SHOWN AT 197A'S WITH 200A |
| | BRKR FEEDING THIS. |
| | |
| | 62)NOTE: PLEASE SEE PLANS INDICATE "SHN" |
| | FEEDING"H5MN" WITH 125A BRKR, YET H5MN |
| | IS ONLY 100A'S.? |
| | PLEASE ALSO SEE RISER , APPEARS TO SHOW |
| | THIS AS "H5MH"? |
| | |
| | 63)NOTE: PLEASE SEE DPHRN 150A BRKR TO |
| | 100A FEEDERS (F-19). |
| | |
| | 64)NOTE: PLEASE CORRELATE LOADS SHOWN ON |
| | "HRHN" AND TWO OTHER LOADS SHOWN ON |
| | "LRHN" |
| | 215.5 |
| | |
| | 65)NOTE: PLEASE CORRELATE F-7, F-9 TO |
| | DPHE ON PANEL AND RISER. |
| | PLEASE SEE NO FEEDER SHOWN K? FOR HGMN |
| | ON RISER. |
| | |
| | 66)NOTE: PLEASE CORRELATE "P-4" METER |
| | CENTER LOAD ANALYSIS AND NOT SHOWN ON |
| | ANY "SWITCH BOARD"? |
| | PLEASE ALSO SEE 2-W NEEDS TO CORRELATE |
| | WITH "SMCW". PLEASE ALSO SEE "MW" NOT |
| | SHOWN?? |
| | 215.5 |
| | |
| | 67)NOTE: PLEASE SEE "FUEL NOTE" MENTIONS |
| | 277 GALS OF FUEL PER HR??? RUNNING A MIN |
| | OF 2.? HRS. |
| | PLEASE CLARIFY THIS NOTE: PLEASE SEE |
| | SIZING, CONSUMPTION OF GEN ETC CAN NOT |
| | BE VERIFIED. PLEASE SEE PREVIOUS NOTES |
| | PERTAINNG TO INFORMATION REQUIRED FOR |
| | GENERATOR ETC. |
| | |
| | 68)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | AIC RATINGS SHOULD BE NOTED ON ALL |
| | EQUIPMENT. |
| | |
| | 69)NOTE: PLEASE SEE ALL INFORMATION FOR |
| | AS SHOWN ON PLANS FOR LIGHTNING |
| | PROTECTION SYSTEMCAN BE INCLUDED UNDER |
| | BASE BLDG'S ELECTRICAL PERMIT. HOWEVER |
| | ANY CHANGES IN SYSTEM WOULD NEED |
| | REVISION. THIS SYSTEM WILL BE THE |
| | RESPONSIBILITY OF THE ELECTRICAL |
| | CONTRACTOR. IF THIS WORK IS "SUBBED' |
| | OUT, A SEPARATE PERMIT MUST BE PULLED BY |
| | LIGHTNING PROTECTION CONTRACTOR. SINCE |
| | THESE PLANS CONTAIN INFORMATION FOR |
| | SYSTEM, SUB CONTRACTOR MAY REFERENCE |
| | THESE PLANS AND A MIN $50 PERMIT FEE |
| | WILL BE DUE. |
| | |
| | 70)NOTE: PLEASE ALSO SEEIF ALL |
| | INFORMATION FOR FIRE PUMP, FIRE PUMP |
| | CONTROLLER,GENERATOR, ATS, ETC IS NOT |
| | SUBMITTED FOR REVIEW WITH BASE BLDG |
| | PLANS, ALL OF THESE ITEMS WILL BE |
| | REQUIRED TO BE UNDER SEPARATE PERMIT |
| | ALONG WITH ALL FEES BASED ON VALUE OF |
| | ALL OF THOSE ITEMS. |
| | PLEASE SEE FIRE REVIEW COMMENTS. |
| | |
| | 71)NOTE: PLEASE SEE MANY OF THE ABOVE |
| | ITEMS ARE REDLINED ON PLANS FOR AREAS OF |
| | NOTES. NOT "ALL" ITEMS ARE REDLINED. |
| | |
| | 72)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | PLEASE SEE "ONE" SET OF ALL OLD/VOIDED |
| | REMOVED SHEETS SHOULD BE SUBMITTED FOR |
| | REFERENCE ONLY. |
| | |
| | 73)NOTE: PLEASE KNOW, AS NOTED IN SOME |
| | NOTES, DUE TO SOME INFORMATION MISSING |
| | ON PLANS AND WITH PLANS, A COMPLETE |
| | REVIEW FOR CODE COMPLIANCE CAN NOT BE |
| | DONE AT THIS TIME. |
| | PLEASE BE SURE TO INCLUDE ALL |
| | INFORMATION AS REQUESTED/NEEDED. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |