17 |
|
| Notes |
| Date |
Text |
| 2007-03-10 13:03:55 | ** UNSAT** | | | | | | 1) NOTE: PLEASE SEE THE SITE LIGHTING SHEET WITH | | | LIGHTING WHICH IS CONTAINED IN THE *RIGHT OF WAY* SHALL | | | BE UNDER A SEPARATE PERMIT AND CAN NOT BE INCLUDED IN | | | THE BASE BUILDING PLANS. THIS WILL GO THROUGH | | | ENGINEERING, BUILDING AND ELECTRICAL REVIEW ONCE | | | SUBMITTED. | | | * THIS SHEET WAS NOT STAMPED IN SETS AND VOIDED. | | | | | | 2) NOTE: PLEASE SEE NFPA-20, 1999 OR 2003. PLEASE KNOW | | | THE AMOUNT OF FUEL FOR THE FIRE PUMP SHALL BE REVISED | | | FOR THE ON-SITE POWER OF THE GENERATOR TO INDICATE THE | | | MINIMUM FUEL AS STATED. PLEASE KNOW THAT THE ACTUAL | | | LOAD ON THE GENERATOR WITH ALL ASSOCIATED OTHER LOADS | | | SHALL BE CONSIDERED THE BASIS FOR THE FUEL CONSUMPTION | | | PER HOUR. THE PLANS INDICATE 92.1 GALS PER HOUR AT THIS | | | TIME. | | | 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT TO | | | PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100 PERCENT | | | OF THE RATED PUMP CAPACITY IN ADDITION TO THE SUPPLY | | | REQUIRED FOR OTHER DEMANDS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|