| 2006-08-12 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | |
| | 1. SHT P2.01 FLOOR DRAIN NOT APPROVED IN |
| | THE STAIRWELL. (SEE REVIEW NOTE #1 FROM |
| | REVIEW #9). NFPA 101, 2003 CHAPTER 7 |
| | SECTION 7.1.3.2.1(6). |
| | |
| | 2. SHT P2.02 W/H PAN DRAIN NOT APPROVED |
| | TO TERMINATE IN PARKING GARAGE. SECTION |
| | 504.8.2. |
| | |
| | 3. SHT P2.03 W/H PAN DRAIN NOT APPROVED |
| | TO TERMINATE IN THE PARKING GARAGE. |
| | SECTION 504.8.2. - VENT REQUIRED FOR 2" |
| | FLOOR DRAIN IN TRASH TERMINATION ROOM. |
| | SECTION 901.2.1 AND TABLE 906.1. |
| | |
| | 4. SHT P2.04 REVISION #5 SHOWN ON SHEET |
| | WAS NOT APPROVED. |
| | |
| | 5. SHT P2.06 REVISION #5 NOT APPROVED. - |
| | VENT REQUIRED FOR FLOOR DRAIN THE THE |
| | TRASH TERMINATION ROOM. SECTION 901.2.1 |
| | AND TABLE 906.1. - UNIT 14 SHOWS NO WASH |
| | MACHINE & PTR/PD LINES NOT SHOWN TO W/H. |
| | PLEASE CLARIFY. SECTION 104.2.1. - FLOOR |
| | DRAIN NOT APPROVED IN THE STAIRWELL. |
| | NFPA 101, 2003 CHAPTER 7 SECTION |
| | 7.1.3.2.1(6). |
| | |
| | 6. SHT P2.11 WATER HEATER PAN DRAIN NOT |
| | APPROVED TO TERMINATE IN THE PARKING |
| | GARAGE. SECTION 504.8.2. |
| | |
| | 7. SHT P2.18 UNITS H3 & HD WATER LINE |
| | OFFSETS FOR RISERS W10 THRU W14 HAVE |
| | BEEN DELETED, BUT RISER DESIGNATION ARE |
| | STILL SHOWN. PLEASE CLARIFY. SECTION |
| | 104.2.1. - WATER PIPING LAYOUTS DELETED |
| | FROM UNITS V1 & HD. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | |
| | 8. SHT P3.27 FLOOR DRAIN NOT APPROVED IN |
| | THE STAIRWELL. NFPA 101 2003. |
| | |
| | 9. SHT P3.28 WASTE REMOVAL SYSTEM. A |
| | GATE VALVE AND CHECK VALVE ARE REQUIRED |
| | ON THE DISCHARGE LINE FROM THE PUMP. |
| | SECTION 712.2. - A VENT IS REQUIRED ON |
| | THE 2" FLOOR DRAIN. SECTION 901.2.1 AND |
| | TABLE 906.1. - NOTE READS ALL SANT. |
| | PIPING TO BE RUN 1/8"/FT. 2-1/2" AND |
| | SMALLER PIPE TO BE RUN 1/4"/FT PER TABLE |
| | 704.1. - RISER SHOWS ONLY RISERS 10/56 |
| | DOWN, BUT RISER 59 CONNECTS TO THE |
| | COMMON RISER ALSO. PLEASE CORRELATE. |
| | SECTION 104.2.1. |
| | |
| | 10. SHT P3.30 FLOOR DRAIN NOT APPROVED |
| | IN STAIRWELL. NFPA 101, 2003 SECTION |
| | 7.1.3.2.1(6). - VENT REQUIRED FOR FLOOR |
| | DRAIN TO SPRINKLER SYSTEM DRAIN. SECTION |
| | 901.2.1 AND TABLE 906.1. |
| | |
| | 11. SHT P3.31 FLOOR DRAIN NOT APPROVED |
| | IN THE STAIRWELL. NFPA 101 2003. |
| | |
| | 12. SHT P3.32 WASTE REMOVAL SYSTEM. (SEE |
| | COMMENT #8). |
| | |
| | 13. SHT P3.36 FLOOR DRAIN NOT APPROVED |
| | IN THE STAIRWELL. NFPA 101, 2003 |
| | |
| | 14. SHT P6.01 TRASH CHUTE PIPING |
| | SCHEMATIC DETAIL. INDICATE BACKFLOW |
| | PROTECTION METHOD AND LOCATION. (MINIMUM |
| | N-36 VACUUM BREAKER. |
| | |
| | 15. THE FOLLOWING SHEETS WERE APPROVED. |
| | P0.01, P2.05, P2.07 THRU P2.10, P2.13 |
| | THRU P2.17, P2.19 THRU P2.30, P2.32 THRU |
| | P2.39, P2.41 THRU P2.54, P2.56 THRU |
| | P2.60, P2.64, P3.00 THRU P3.04, P3.12, |
| | P3.17 THRU PE.26, P3.29, P3.33 THRU |
| | P3.35, P3.37 THRU P3.39. |
| | |