| Plan Review Notes For Permit 04120353 |
| Permit Number |
04120353 |
|
| Review Stop |
M |
| Sequence Number |
10 |
|
| Notes |
| Date |
Text |
| 2006-09-07 00:00:00 | PROVISO: | | | | | | 1.PLEASE REVISE CALCULATIONS FOR THE | | | GARAGE VENTILATION.SHOW COMPLIANCE | | | WITH 2001 FBC 411.4.2 & 2001 FMC 501.4. | | | | | | 2.PLEASE INDICATE IF THE CO SENSORS | | | WILL BE TIED TO THE EMERGENCY POWER. | | | | | | 3.PLAN SHEET M2.04 - PLEASE VERIFY THE | | | LENGTH OF THE DRYER EXHAUST, DUE TO THE | | | RE-ROUTING OF THE DUCT.THIS COMMENT IS | | | IN RESPONSE TO NARRATIVE NOTE #15. | | | | | | 4.PLEASE NOTE, AIR HANDLER CLOSETS | | | SERVE AS A PLENUM AND SHALL COMPLY WITH | | | 2001 FMC 602.2.1, MATERIALS EXPOSED | | | WITHIN THE PLENUM SHALL BE | | | NON-COMBUSTIBLE.THIS INCLUDES THE DOOR | | | AND FRAME. | | | | | | 5.DRYER EXHAUST SHALL NOT EXCEED THE | | | MANUFACTURER'S SPECIFIED LENGTH OR | | | COMPLY WITH 2001 FMC 504.6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected] |
|