| Date |
Text |
| 2005-01-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) PLANS SHALL BE SIGNED/SEALED/DATED |
| | BY |
| | THE ARCHITECT/ENGINEER OF RECORD, AND |
| | ALL TITLE BLOCK INFORMATION REQUIRED ON |
| | ALL SHEETS. FAC 61G1-16.002-.003-.004 & |
| | 61G15-23.002 & FS 481.219-.219 & |
| | 471.025 |
| | 2) SHT A2.01 PRIMARY ENTRY LEVEL SHALL |
| | COMPLY WITH FHA-98 DESIGN MANUAL |
| | REQUIREMENTS 1 THRU 7. |
| | 3) SHT A2.10 SUBMIT CALCULATIONS FOR |
| | MINIMUM FACILITIES PER TABLES 1003.2 |
| | AND |
| | 403.1. SHOW SQUARE FEET FOR EACH COMMON |
| | USE ROOM. |
| | 4) SHT A2.10 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY STORM DRAINS FOR |
| | THE 5TH FLOOR OPEN AREAS PER SECTIONS |
| | 1106 & 1107. SHOW THE LOCATION FOR ALL |
| | PRIMARY AND SECONDARY DRAINS. |
| | 5) SHTS A2.14, A2.15, A2.16, & A2.17. |
| | APPLICATION STATES 20 STORY BLDG., BUT |
| | PLANS INDICATE 21ST STORY AND HAS A |
| | ROOF |
| | LEVEL, POOL DECK LEVEL, ELEVATOR |
| | MACHINE |
| | ROOM LEVEL ECT. PLEASE CLARIFY. |
| | 6) SHT A4.11 UNIT 1 DOOR SWING INTO THE |
| | CLEAR FLOOR SPACE OF THE LAV. SECTION |
| | 11-4.22.2. |
| | 7) SHT A4.12 UNITS 5 & 6 DOOR SWING |
| | INTO |
| | THE CLEAR FLOOR SPACE OF THE LAV AND |
| | W/C |
| | SECTION 11-4.22.2. |
| | 8) SHT A4.13 UNIT 12 DOOR SWING INTO |
| | THE |
| | CLEAR FLOOR SPACE OF THE W/C. |
| | 11-4.22.2. |
| | 9) SHT A4.15 UNIT 17 DOOR SWING INTO |
| | THE |
| | CLEAR FLOOR SPACE OF THE LAV. |
| | 11-4.22.2. |
| | 10) ALL SHEETS FOR UNITS. SHOW THE |
| | OPENING SIZE FOR ALL W/C'S AND SHOW THE |
| | W/C TO BE 18" FROM THE CENTER LINE OF |
| | THE FIXTURE TO THE WALL WHERE |
| | APPLICABLE |
| | 11) ALL SHEETS FOR UNITS. INDICATE |
| | SPECIFICATION "A" OR "B" AS REQUIRED BY |
| | THE FHA-98 DESIGN MANUAL FOR EACH UNIT. |
| | 12) SHT A4.41 KITCHEN SINK & JUICE BAR |
| | SINK IN COMMON AREAS SHALL COMPLY WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | SUBMIT A DETAIL. |
| | 13) SHT A4.41 SUBMIT A DETAIL FOR THE |
| | TOILET ROOM IN THE COMMON AREA. SHOW |
| | COMPLIANCE WITH SECTIONS 11-4.16, |
| | 11-4.18, 11-4.19, 11-4.21 & 11-4.22 AND |
| | ALL SUBSECTIONS. ALSO SEE SECTION 2 OF |
| | THE FHA-98 DESIGN MANUAL. |
| | 14) SHT A4.41 A DRINKING FOUNTAIN IS |
| | REQUIRED PER TABLE 403.1 FOR THE COMMON |
| | AREA. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE |
| | WITH SECTION 11-4.15 AND ALL |
| | SUBSECTIONS. - ALSO SEE SECTION 410.1. |
| | 15) SHT SUBMIT CALCULATIONS FOR PRIMARY |
| | AND SECONDARY ROOF DRAINS PER SECTIONS |
| | 1106 & 1107 AND ALL SUBSECTIONS. SHOW |
| | THE SQUARE FOOTAGE OF EACH AREA DRAINED |
| | WITH 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS SHOWN ADDED TO THE |
| | ROOF AREA. ALSO SHOW THE AREA OF UPPER |
| | ROOFS DRAINING ONTO EACH AREA ADDED TO |
| | THE SF IN CALCULATIONS. SHOW THE |
| | LOCATION OF EACH PRIMARY ROOF DRAIN AND |
| | EACH SECONDARY ROOF DRAIN OR SCUPPER |
| | FOR |
| | EACH AREA BEING DRAINED FOR EACH ROOF. |
| | 16) SHT A4.51 A 60" DIA. TURNING AREA |
| | IS |
| | REQUIRED IN A "U" SHAPED KITCHEN THAT |
| | HAS A SINK, RANGE, OR COOKTOP AT IT'S |
| | BASE. PAGE 7.9 FHA DESIGN MANUAL. |
| | 17) SHTS A4.60 THRU A4.66 MORE |
| | INFORMATION IS REQUIRED FOR THE |
| | EXTENDED |
| | TERRACES. WILL |
| | A SCUPPER BE REQUIRED OR CAN THE WATER |
| | DRAIN FROM THE TERRACES IN CASE OF |
| | BLOCKAGE OF THE TERRACE DRAIN. SECTION |
| | 104.2.1. |
| | 18) SHT A4.71A INDICATE LOCATION OF |
| | SECONDARY ROOF DRAINS IN AREAS OF ROOF |
| | WHERE SCUPPERS ARE NOT AVAILABLE. |
| | SECTION 1107. |
| | 19) SHT A4.72A INDICATE LOCATION OF |
| | SECONDARY ROOF DRAINS FOR DECK DRAIN |
| | AREAS. SECTION 1107. |
| | 20) SHT A4.73A INDICATE LOCATION OF |
| | SECONDARY ROOF DRAINS FOR ALL AREAS. |
| | SECTION 1107. |
| | 21) SEPARATE PERMITS REQUIRED FOR POOL |
| | AND SPA. SECTION 104.1.1. |
| | 22) SHT A8.21 DETAIL B/A8.21 INDICATE |
| | OPENING SIZE REQUIRED PER SECTION |
| | 1107.3 |
| | 23) IRRIGATION PLANS & PERMIT REQUIRED. |
| | SECTION 104.2.1. |
| | 23) SHT L-2 MORE INFORMATION IS |
| | REQUIRED |
| | FOR THE WATER FEATURES. INDICATE HOW |
| | THE |
| | FEATURES ARE DRAINED AND IF THERE IS A |
| | WATER SERVICE FOR THESE FEATURES. |
| | SECTION 104.2.1. |
| | 24) THE FOLLOWING SHEETS SUBMITTED ARE |
| | NOT SHOWN ON THE DRAWING INDEX. A4.71A, |
| | A4.74A, A8.41B & A10.03. PLEASE |
| | CORRELATE THE DRAWING INDEX WITH |
| | SUBMITTED PLANS. |
| | 25) THE FOLLOWING SHEETS ON THE DRAWING |
| | INDEX WERE NOT SUBMITTED. A1.02, A3.11, |
| | A3.12, A3.14, A3.15, A3.24, A4.14, |
| | A5.01, A5.11, A6.53A, A6.56A, A8.12, |
| | A8.13, A8.14, A9.22, A10.10, AND |
| | LS0.00. |
| | PLEASE SUBMIT ALL SHEETS INDICATED ON |
| | THE DRAWING INDEX. SECTION 104.2.1. |
| | 26) PLANS SUBMITTED ARE NOT COMPLETE. |
| | MANY SHEETS APPEAR TO BE INCOMPLETE AND |
| | THE FOLLOWING SHEETS SHOWN ON THE INDEX |
| | WERE NOT SUBMITTED. P2.01, P2.05, P2.06, |
| | P2.27, P2.29, P2.30, P2.31, P2.32, |
| | P2.34, P2.35, P2.36, P2.62, P2.63, |
| | P2.64, P2.65, P2.66, P2.67, P2.68, |
| | P2.69, P3.03, P3.04, P3.05, P3.06, |
| | P3.07, P3.08, P3.09, P3.10, P3.11, |
| | P3.12, P3.13, AND P6.02. |
| | 27) SUBMIT A STORM BLDG DRAIN ISOMETRIC |
| | SHOWING ALL PIPE SIZES, AND SHOW THE |
| | LOCATION OF ALL STORM RISER DIAGRAMS AS |
| | THEY CONNECT TO THE BLDG. DRAIN AND SHOW |
| | SQUARE FOOTAGE AS IT ACCUMULATES IN THE |
| | SYSTEM. SECTIONS 1106, 1107 & 104.2.1. |
| | 28) SUBMIT STORM RISER DIAGRAMS SHOWING |
| | ALL PIPE SIZES AND SQ.FT. SECTIONS 1106, |
| | 1107 AND 104.2.1. |
| | 29) SUBMIT A CONDENSATE BLDG DRAIN |
| | ISOMETRIC SHOWING ALL PIPE SIZES. |
| | SECTION 104.2.1. |
| | 30) SUBMIT CONDENSATE RISER DIAGRAM. |
| | SECTION 104.2.1 |
| | 31) SUBMIT A SANITARY BLDG. DRAIN |
| | ISOMETRIC. SHOW ALL PIPE SIZES, LOCATION |
| | OF EACH RISER CONNECTING TO BLDG. DRAIN, |
| | AND DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. SECTION 104.3.1.1. |
| | 32) SHEETS FOR UNIT TYPES ARE INCOMPLETE |
| | AND REQUIRE MORE INFORMATION. SOME |
| | SHEETS SHOW SANT., VENT, WATER, COND., |
| | T/P, OR ANOTHER UNIDENTIFIED LINE, BUT |
| | ALL DO NOT HAVE ALL INFORMATION |
| | REQUIRED. |
| | 33) SHOW STACK NUMBERS FOR EACH STACK IN |
| | ALL UNIT SHEETS. SECTION 104.2.1. |
| | 34) SHT P2.11 IS MISLABELED AS M2.11, OR |
| | IT IS A MECH. SHEET. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 34) SHT P2.02 UNIT 2, INDICATE WHERE LAV |
| | RISER CONNECTS TO THE SANT. BRANCH LINE. |
| | SECTION 104.2.1. |
| | UNIT 3, THE VENT LINE IS SHOWN AS |
| | SANT. |
| | UNIT 4, NO SANT. TO W.M, NO VENT LINES |
| | SHOWN. SECTION 104.2.1. |
| | 35) SHT P2.03 ALL UNITS, NO VENT LINES |
| | SHOWN, NO WATER LINES SHOWN. |
| | UNIT 5, NO SANT. TO W/M. |
| | UNIT 8, ONLY THE FIXTURES WITHIN THE |
| | BATHROOM GROUP SHALL CONNECT TO THE |
| | WET-VENTED HORIZONTAL BRANCH DRAIN. THE |
| | KITCHEN SINK SHALL DISCHARGE DOWNSTREAM |
| | OF THE WET VENT. SECTION 909.1 |
| | 36) SHT P2.04 PIPING INCOMPLETE. SECTION |
| | 104.2.1. |
| | 37) SHT P2.07 PIPING INCOMPLETE. |
| | 104.2.1 |
| | 38) SHT P2.08 UNIT 4, LAV VENT SHOWN OUT |
| | OF THE WALL. SEC 104.2.1. |
| | 39) SHTS P2.09 & P2.10 PIPING |
| | INCOMPLETE. NO WATER LINES. SEC |
| | 104.2.1. |
| | 40) SHT P2.12 PIPING INCOMPLETE. |
| | UNIT 15 SHOWER NOT VENTED. SEC |
| | 901.2.1. |
| | 41) SHT P2.13 PIPING NOT COMPLETE. |
| | SECTION 104.2.1. |
| | 42) SHT P2.14 PIPING INCOMPLETE. |
| | UNIT HH1 MASTER BATH DOUBLE LAV SHOWS |
| | SANT PIPING FROM TWO DIFFERENT RISERS. |
| | PLEASE CLARIFY. SEC 104.2.1. |
| | TRASH CHUED LABELED AS PRIMARY AIR |
| | SHAFT #3. PLEASE CLARIFY. 104.2.1. |
| | 43) SHT P2.15 PIPING INCOMPLETE. |
| | UNIT VV1 SHOWS VENT UNDER M/B TUB. |
| | PLEASE CLARIFY. |
| | UNIT A1 IS LAV IN M/B ON A SEPARATE |
| | RISER STACK FROM OTHER M/B FIXTURES. |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | 44) SHTS P2.17 THRU P2.54 PIPING |
| | INCOMPLETE. SECTION 104.2.1. |
| | 45) P2.21 UNITS A1 & VV1 BATH #2 SHOWER |
| | NOT VENTED. SECTION 901.2.1. |
| | UNIT A1 WHAT TYPE OF VENT IS THE |
| | KITCHEN SINK UTILIZING? SECTION 901.2.1 |
| | 46) SHT P2.39 HAS A REFERENCE TO SHT |
| | P2. |
| | NO SHT P2. IS LOCATED. PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | 47) SHT 2.44 UNIT S MASTER BATH WATER |
| | CLOSET, MAX 10' FROM POINT OF VENT. |
| | TABLE 906.1. |
| | 48) SHT P2.50 UNTI P2 LAUNDRY SINK SHALL |
| | NOT DISCHARGE INTO THE WET VENT FOR THE |
| | BATHROOM FIXTURES. SECTION 909.1. |
| | 49) SHT P2.53 UNIT 0 BATH #2 KITCHEN |
| | SINK SHALL NOT DISCHARGE INTO THE WET |
| | VENT. SECTION 909.1. |
| | 50) SHT 2.57 WOMEN'S BATHROOM DOES NOT |
| | REFLECT THE SANT. RISER DIAGRAM. W/C IN |
| | WOMEN'S STALL MAX. 10' FROM POINT OF |
| | VENT. TABLE 906.1. INDICATE USE OF FLOOR |
| | DRAIN FOR FIXTURE NEXT TO SHOWER IN |
| | MEN'S BATHROOM. SECTION 104.2.1. |
| | 51) ALL SANT. RISERS WITH WASH MACHINES, |
| | REQUIRE A STANDPIPE AND THE CLEANOUT |
| | SHALL BE LOCATED 4' ABOVE THE FLOOR FOR |
| | ACCESS. SECTIONS 1002.1, 802.4 & |
| | 708.10. |
| | 52) SHT P3.01 DOMESTIC WATER RISER |
| | DIAGRAMS. AIR CHAMBERS ARE NOT APPROVED. |
| | DELETE FROM RISERS. SECTION 604.9. |
| | 53) SHT 3.14 RISER 21 MAX 4 FIXTURE |
| | UNITS ON 2" WET VENT. TAB 909.3 |
| | 54) SHT PE.15 RISERS 27/34 OFFSET VENT |
| | REQUIRED. SECTION 915. |
| | RISERS 55/56 IDENTIVY FIXTURE BY |
| | KITCHEN SINK. SEC 104.2.1 |
| | RISER 28 OFFSET VENT REQUIRED. 915. |
| | RISERS 29/31 OFFSET VENT REQUIRED. 915 |
| | - MASTER BATH 21ST FLOOR MAX 4 FU ON 2" |
| | WET VENT. TABLE 909.3. FLOORS 6 THRU 15, |
| | MAXIMUM 4 FU ON 2" WET VENT. TAB 909.3. |
| | RISERS 30/32 OFFSET VENT REQUIRED. |
| | 915. |
| | MAX 4 FU ON 2" WET VENT. TAB 909.3 |
| | RISER 38 OFFSET VENT REQUIRED. SEC 915 |
| | MAX. 4 FU ON 2" WET VENT TAB 909.3. |
| | 55) SHT P3.16 RISERS 39.75 OFFSET VENT |
| | REQUIRED SEC 915. |
| | RISER 39 MAX. 4 FU ON 2" WET VENT. |
| | TABLE 909.3. |
| | RISER 59 OFFSET VENT REQD. SEC 915. |
| | RISER 11 OFFSET VENT REQD. SECTION |
| | 915. |
| | RISER 12 OFFSET VENT REQD. SEC 915. - |
| | INDICATE WHICH FLOOR/FLOORS THE SANT. IS |
| | FOR ABOVE THE 15TH FLOOR. - MAX 4 FU ON |
| | 2" WET VENT. TABLE 909.3 |
| | 56) SHT P3.17 RISER 23 OFFSET VENT |
| | REQUIRED. SECTION 915. |
| | RISER 24 OFFSET VENT REQD. SEC. 915. - |
| | MAX. 4 FU ON 2" WET VENT. TABLE 909.3 |
| | RISERS 26/35 OFFSET VENT REQD. SEC. 915 |
| | - FIXTURE MISLABELED AS KITCHEN SINK IN |
| | BATHROOM GROUP. SECTION 104.2.1. |
| | 57) SHT P3.18 RISER 70 OFSET VENT REQD. |
| | SECTION 915. - MAX 4 FU ON 2" WET VENT. |
| | TABLE 909.3. |
| | RISER 15 MAX. 4 FU ON 2" WET VENT. |
| | TABLE 909.3 |
| | RISER 18 ABOVE 21ST FLOOR STATES VENT |
| | BACK DOWN TO 15TH FLOOR. PLEASE CLARIFY |
| | SECTIONS 104.2.1. & 903.1. |
| | RISER 19 ABOVE 21TH FLOOR STATES VENT |
| | BACK DOWN TO 15TH FLOOR. PLEASE CLARIFY |
| | SECTIONS 104.2.1. & 903.1. |
| | 58) SHT P3.19 RISER 1 OFFSET VENT |
| | REQUIRED. SECTION 915. |
| | RISERS 2/55 SOIL STACK AND VENT STACK |
| | ARE CROSSED. - OFFSET VENT REQUIRED. |
| | SECTION 915. |
| | RISER 3 VENT STACK SHALL CONTINUE AND |
| | NOT TIE BACK INTO THE SOIL STACK. |
| | SECTION 903.1 |
| | RISER 4 MAX 4 FU ON 2" WET VENT. |
| | 909.3. |
| | RISER 5 OFFSET VENT REQUIRED. SEC 915. |
| | 59) SHT P3.20 RISER 6 OFFSET VENT |
| | REQUIRED. SECTION 915. - MAX 4 FU ON 2" |
| | WET VENT. TABLE 909.3. |
| | RISER 54 MAX 4 FU ON 2" WET VENT. TABLE |
| | 909.3. |
| | RISER 7 OFFSET VENT REQUIRED. SEC 915. |
| | MAX. 4 FU ON 2" WET VENT. TABLE 909.3. |
| | RISER 8 OFFSET VENT REQUIRED. SEC 915. |
| | MAX 4 FU ON 2" WET VENT. TABLE 909.3. |
| | 60) SHT P3.21 RISER 40 OFFSET VENT |
| | REQUIRED. SECTION 915. |
| | RISER 41 OFFSET VENT REQD. SEC 915. |
| | RISER 44 OFFSET VENT REQD. SEC 915. - |
| | INDICATE IF THERE ARE BRANCH LINES |
| | CONNECTING TO STACK ON THE 17TH THRU |
| | 20TH FLOORS. SECTION 104.2.1. |
| | RISER 76 MAX 4 FU ON 2" WET VENT. TABLE |
| | 909.3. |
| | 61) SHT P3.22 RISER 45 OFFSET VENT REQD. |
| | SECTION 915. - INDICATE IF THERE ARE |
| | BRANCH LINES CONNECTING TO THE STACK ON |
| | THE 17TH THRU 20TH FLOORS. SEC 104.2.1. |
| | RISER 46 OFFSET VENT REQD. SEC 915. - |
| | MAXIMUM 4 FU ON 2" WET VENT. TABLE |
| | 909.3 |
| | RISER 47 OFFSEC VENT REQD. SEC 915. - |
| | MAXIMUM 4 FU ON 2" WET VENT. TABLE |
| | 909.3 |
| | RISER 49 OFFSET VENT REQD. SEC 915. - |
| | MAXIMUM 4 FU ON 2" WET VENT. TABLE |
| | 909.3 |
| | 62) SHT P3.23 RISER 63 MAXIMUM 4 FU ON |
| | 2" WET VENT. TABLE 909.3 |
| | RISER 43 OFFSET VENT REQD. SEC 915. - |
| | MAXIMUM 4 FU ON 2" WET VENT. TABLE |
| | 909.3 |
| | RISER 60 WASH MACHINE AND KITCHEN SINK |
| | SHALL CONNECT TO THE SANT. STACK NOT THE |
| | VENT STACK. SECTION 104.2.1. |
| | 63) SHT P6.01 COOLING TOWER MAKE UP |
| | DETAIL, INDICATE METHOD FOR REQUIRED |
| | BACKFLOW PROTECTION. SECTION 608.13.2. - |
| | WATER HEATER PIPING DETAIL, THERMAL |
| | EXPANSION CONTROL REQUIRED. SECTION |
| | 607.3.2. - TRASH CHUTE PIPING DIAGRAM. |
| | INDICATE METHOD FOR REQUIRED BACKFLOW |
| | PROTECTION. SECTION 608.13.2. |
| | 64) BACKFLOW PROTECTION REQUIRED FOR THE |
| | POOL MAKE UP WATER. SUBMIT A DETAIL. |
| | SECTION 608.13.2. |
| | 65) BECAUSE THE PLANS ARE INCOMPLETE, |
| | MORE COMMENTS MAY BE FOURTHCOMMING WHEN |
| | THE PLANS ARE RESUBMITTED. - PLEASE |
| | RETURN THE PLUMBING PLANS WITH THE RED |
| | LINE NOTES WHEN RESUBMITTING TO HELP |
| | REVIEWING PLANS FOR SECOND REVIEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |