| 2005-01-18 00:00:00 | DENIED: |
| | 1.THE FOLLOWING PLANS ARE INDICATED |
| | ON THE "INDEX" BUT WERE NOT INCLUDED: |
| | A1.02, A3.11, A3.12, A3.14, A3.15, |
| | A3.24, A4.14, A5.01, A5.11, A6.53A, |
| | A6.56A, A8.12, A8.13, A8.22, A8.23, |
| | A8.41A, A8.44, A9.22, A10.01, M1.14, |
| | M2.05, M2.07, M2.11, M2.19, M2.20, |
| | M2.33, M2.34, M2.35, M3.02, M4.00, |
| | M4.02, M4.03, M5.04, M6.01 THROUGH |
| | M6.09, M7.02.PLEASE NOTE, PLAN SHEET |
| | M7.02 IS MISSING BUT THERE ARE TWO |
| | M7.01 SHEETS THAT ARE NOT IDENTICAL, |
| | ONE |
| | MAY BE JUST MISMARKED. |
| | |
| | 2.PLANS ARE NOT COMPLETE THEREFORE |
| | ADDITIONAL COMMENTS MAY ARRISE DUE TO |
| | THE RESPONSE TO 1ST REVIEW AND ANY NEW |
| | DETAILS ADDED. |
| | |
| | 3.PLAN SHEET A1.03 GENERATOR RM. |
| | PLEASE PROVIDE ELEVATION FOR THE |
| | TERMINATION OF THE MUFFLER EXHAUST, |
| | SHOW |
| | CLEARANCES TO FRESH AIR INTAKES I.E., |
| | DOORS, WINDOWS, LOUVERS, ETC. |
| | |
| | 4.PROVIDE DETAILS FOR VENTILATION FOR |
| | THE GENERATOR ROOM.PLAN ALSO |
| | INDICATES |
| | A FUEL TANK.PROVIDE DETAILS FOR THE |
| | CAPACITY OF THE FUEL TANK, VENTING |
| | REQUIREMENTS AND FILL PIPE INFORMATION. |
| | |
| | 5.PROVIDE SUBMTTIALS FOR THE |
| | GENERATOR |
| | AND FUEL TANK. |
| | |
| | 6.PLAN SHEET 7.14 INDICATES TRASH |
| | CHUTE WITH THE SMOKE EXHAUST IN THE |
| | SAME |
| | SHAFT.PLEASE CLARIFY, INDICATE RATING |
| | OF SEPARATION. |
| | |
| | 7.PLAN SHEET M1.05 (AND SUBSEQUENT |
| | SHEETS), INDICATE HPU-X OR EF-X.THESE |
| | ARE NOT IDENTIFIED ON THE RESPECTIVE |
| | EQUIPMENT SCHEDULES. |
| | |
| | 8.EF-X DOES NOT INDICATE ANY |
| | TERMINATION, PLEASE CLARIFY.PLEASE |
| | NOTE, PER 2001 FBC(M)503.1 ARE REMOVED |
| | BY EVERY MECHANICAL EXHAUST SYSTEM |
| | SHALL |
| | BE DICHARGED TO THE OUTDOORS. |
| | |
| | 9.PLANS DO NOT INDCLUDE DETAILS FOR |
| | COMMON AREAS. |
| | |
| | 10. PLAN SHEETS M2.02, 2.03, 2.04, ETC, |
| | INDICATE DRYER EXHAUST & TOILET EXHAUST |
| | PENTRATING AND RUNNING THROUGH THE |
| | RETURN AIR PLENUM.PER 2001 |
| | FBC(M)601.3, EXHAUST DUCTS UNDER |
| | POSITIVE PRESSURE SHALL NOT EXTEND INTO |
| | OR PASS THROUGH A RETURN AIR PLENUM. |
| | |
| | 11.NO COMBUSTIBLES ALLOWED IN THE |
| | RETURN AIR PLENUM.PLEASE NOTE |
| | CONSTURCITON OF THE RETURN AIR PLENUM |
| | SHALL COMPLY WITH 2001 FBC(M) 603.8. THE |
| | DOOR TO THE MECHANICAL CLOSET HAVING A |
| | RETURN AIR PLENUM SHALL BE NON |
| | COMBUSTIBLE. |
| | |
| | 12. PLANS INDICATE THE USE OF BOOSTER |
| | FANS FOR THE DRYER.PLEASE SUBMIT ALL |
| | DOCUMENTATION I.E., DRYER MANUFACTURER, |
| | BOOSTER FAN SUBMITTAL AND ENGINEERING |
| | DATA.THIS WILL BE REVIEWED UNDER 2001 |
| | FBC 103.7.1, ALTERNATE MEANS AND |
| | METHODS |
| | AND WILL REQUIRE REVIEW AND APPROVAL BY |
| | THE BUILDING OFFICIAL/DIRECTOR. |
| | |
| | 13.CW RISERS AND BRANCH LINES ARE NOT |
| | SIZED.(INCOMPLETE) |
| | |
| | 14.PROVIDE SUBMITTALS FOR THE PUMPS, |
| | COOLING TOWERS, HEAT EXCHANGERS, HEAT |
| | PUMPS, EXHAUST FANS, AIR SEPARATOR, |
| | EXPANSION TANK AND ALL PERTINANT VALVES |
| | AND CONTROLS REQUIRED TO COMPLETE AND |
| | OPERATE SYSTEM. |
| | |
| | 15.PROVIDE OUTSIDE AIR CALCULATIONS |
| | FOR ALL COMMON AREAS AS WELL AS THE |
| | RESIDENCE.SHOW COMPLIANCE WITH 2001 |
| | FBC(M) TABLE 403.3 AND 402. |
| | |
| | 16. CONDENSATE RISER ON PLAN SHEET |
| | P3.13 |
| | & P3.14.PLAN SHEET P3.13 IS NOT IN |
| | THE |
| | SUBMITTAL AND PLAN SHEET P3.14 SHOWS A |
| | SANITARY RISER. |
| | |
| | 17.PROVIDE PLANS FOR VENTILATION FOR |
| | ALL COMMON HABITABLE AREAS AS WELL AS |
| | NON HABITABLE (EQUIPMENT RMS, |
| | MECHANICAL |
| | ROOMS, ETC.)INDICATE ALL LOUVERS, |
| | DUCTS, EXAUST AND FRESH AIR INTAKES ON |
| | THE PLAN AND IDENTIFY ACCORDINGLY. |
| | |