| 2005-01-21 00:00:00 | 1. CONSTRUCTION, DEMOLITION, AND |
| | RENOVATION TO COMPLY WITH NFPA 241. |
| | |
| | 2. TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN THE BUILDING REACHES THREE |
| | STORIES OR 30 FEET IN HEIGHT. |
| | |
| | 3. SINCE THE BUILDING WILL BE |
| | CONSIDERED HIGH-RISE IT MUST |
| | COMPLY WITH APPLICABLE BUILDING AND |
| | FIRE CODE REQUIREMENTS FOR HIGH-RISE |
| | BUILDINGS. |
| | |
| | 4. PLEASE EXPLAIN CONTROLLED ENTRY |
| | AND EXIT NOTES ON PAGE LS1.01. |
| | |
| | 5. PLEASE INDICATE WHAT ELEVATORS |
| | ARE STRETCHER ACCESSIBLE. |
| | |
| | 6. EXIT SIGN PLACEMENT SHALL NOT |
| | EXCEED 100 FEET. |
| | |
| | 7. PLEASE ILLUSTRATE ALL EXIT |
| | DISCHARGE LOCATIONS FROM THE |
| | BUILDING. EXIT DISCHARGE LOCATIONS |
| | SHALL COMPLY WITH APPLICABLE FIRE |
| | CODE REQUIREMENTS. |
| | |
| | 8. KNOX-BOXES WILL BE REQUIRED FOR |
| | THE BUILDING. |
| | |
| | 9. ON PAGE LS1.03 PLANS MAKE REFERENCE |
| | TO HORIZONTAL EXITS. PLEASE EXPLAIN |
| | HOW THE CODE REQUIREMENTS FOR |
| | HORIZONTAL EXITS ARE BEING MET. |
| | |
| | 10. ON PAGE LS1.03 EXITING IS SHOWN |
| | THRU TENANT STORAGE ROOM B. PLEASE |
| | EXPLAIN WHAT CODE ALLOWS THIS TO |
| | OCCUR. |
| | |
| | 11. EXIT PATH ON LS1.05 IS GOING |
| | BETWEEN TWO HANDICAP VEHICLES. PLEASE |
| | EXPLAIN. |
| | |
| | 12. PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATIONS FOR WALLS AND |
| | CEILINGS. |
| | |
| | 13. PLEASE INDICATE OCCUPANT LOAD |
| | FOR THE 5TH FLOOR LANAI SHOWN |
| | ON PAGE LS1.07. |
| | |
| | 14. PLEASE VERIFY OCCUPANT LOADS |
| | FOR THE HEALTH CLUB AND MULTI-PURPOSE |
| | ROOMS TO DETERMINE IF EXIT DOORS |
| | SWINGS ARE PROPER. LS1.07. |
| | |
| | 15. WHAT CODE REQUIREMENTS ARE BEING |
| | MET |
| | TO EXIT FROM THE DECK OF THE LANAI |
| | AREA. |
| | |
| | 16. IS THE AREA CALLED OUT ON PAGE |
| | LS1.10 "EXIT PATH OF TRAVEL-LIGHTED |
| | AND PAINTED LINES OF DEMARKATION" |
| | ALSO SLIP RESISTANT. |
| | |
| | 17. NO STORAGE OF ANY KIND WILL BE |
| | ALLOWED IN LOCATIONS NOTED FOR |
| | INSPECTION AND SERVICE ONLY. |
| | |
| | 18. THE FIRE PROTECTION FOR THE |
| | COOLING TOWERS SHALL COMPLY WITH |
| | NFPA 214. |
| | |
| | 19. PLEASE PROVIDE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR ALL |
| | HANDRAILS AND GUARDRAILS. |
| | |
| | 20. SOME DOOR SWINGS ON THE MEZZANINE |
| | LEVEL AND PARKING LEVEL P3 ON |
| | PAGE A2.03 MAY NOT SWING IN THE |
| | PROPER DIRECTION. |
| | |
| | 21. PARKING AREA TO COMPLY WITH |
| | NFPA 88A. |
| | |
| | 22. NO NOTE INDICATING THAT STAIR #6 |
| | IS PRESSURIZED. |
| | |
| | 23. PLANS ILLUSTRATE A 21ST FLOOR |
| | BUT IT IS BELIEVED THAT THE PERMIT |
| | APPLICATION INDICATES A 20 STORY |
| | BUILDING. |
| | |
| | 24. DOOR SWINGS ON STAIR # 2,7,AND 8 |
| | ARE SWINGING IN THE WRONG DIRECTION |
| | ON PAGE A2.16. |
| | |
| | 25. WRONG ADDRESS NOTED ON F10 NOTE |
| | ON PAGE A3.01. SAME CONDITION EXISTS |
| | ON A3.03. |
| | |
| | 26. TWO FIRE DEPARTMENT CONNECTIONS |
| | WILL BE REQUIRED SINCE IT IS A |
| | HIGH-RISE BUILDING. |
| | |
| | 27. NEW FIRE ALARM SYSTEM SHALL BE |
| | MONITORED UL LISTED CENTRAL STATION |
| | APPROVED FOR CENTRAL STATION SERVICE. |
| | |
| | 28. IS ANY ACCESS PROVIDED FOR |
| | MECHANICAL SPACES SHOWN ON PAGE A3.21. |
| | |
| | 29. A DOOR IS NOTED WITHIN THE EXIT |
| | ENCLOSURE FOR STAIR # 2 NEAR |
| | ELEVATOR # 3. PLEASE EXPLAIN CODE |
| | PROVISIONS THAT YOU MEET THAT |
| | ALLOWS FOR THIS. |
| | |
| | 30. PLEASE INDICATE SIZE OF PEDESTRIAN |
| | PASS DOOR ON PAGE A4.11. |
| | |
| | 31. KNOX-BOX LOCKING CAPS WILL BE |
| | REQUIRED ON FIRE DEPARTMENT |
| | CONNECTIONS. |
| | |
| | 32. ALL SMOKE DETECTORS SHALL BE |
| | INSTALLED A MINIMUM OF THREE FEET |
| | FROM AC DIFFUSERS. |
| | |
| | 33. WHAT IS THE ELEVATION OF THE |
| | TERRACE SHOWN ON PAGE A4.41. |
| | |
| | 34. HAND WRITTEN NOTES APPEAR ON |
| | SEVERAL PAGES OF THE PLAN. |
| | |
| | 35. EXIT STAIRS ARE TO BE KEPT UP |
| | WITH CONSTRUCTION. |
| | |
| | 36. NO COMBUSTIBLES ALLOWED IN ANY |
| | RETURN AIR PLENUM. NOTES LOCATED IN |
| | PLANS. |
| | |
| | 37. NO SMOKE DETECTOR SHOWN IN FIRE |
| | COMMAND ROOM. |
| | |
| | 38. ELEVATOR WARNING SIGNS REQUIRED |
| | AT ELEVATOR LOBBIES. |
| | |
| | 39. PLEASE INDICATE LOCATIONS OF |
| | SPEAKER STROBES FOR APARTMENTS |
| | PROVIDED FOR THE HANDICAPPED. |
| | |
| | 40. ANY SOFFITS THAT ARE PLANNED SHALL |
| | NOT INTERFERE WITH ANY FIRE PROTECTION |
| | EQUIPMENT OR DEVICES. |
| | |
| | 41. PLEASE PROVIDE FLAMESPREAD DETAILS |
| | ON HIGH-DENSITY STYROFOAM BLOCK |
| | SHOWN ON A7.02. PLEASE EXPLAIN |
| | PURPOSE OF MATERIAL. |
| | |
| | 42. STAIR PRESSURIZZATION DUCT SHOWN |
| | ON PAGE A7.11 MUST BE A MINIMUM 2 |
| | HOUR RATED SHAFT. |
| | |
| | 43. WHAT ACTIVITIES OCCUR IN OPEN |
| | AIR COVERED STRUCTURE SHOWN ON PAGE |
| | A8.11. |
| | |
| | 44. BUILDING IS LOCATED IN THE CITY |
| | FIRE LIMITS. CERTAIN RESTRICTIONS |
| | WILL APPLY SEE APPENDIX F, LOCAL |
| | AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE. |
| | |
| | 45. PLEASE EXPLAIN USE OF CARD READERS |
| | FOR THE BUILDING. WHAT ISSUES DO |
| | THEY RAISE IF ANY TO EXITING. |
| | |
| | 46. ALL FIRE DOORS AND WINDOWS TO |
| | COMPLY WITH NFPA 80, FIRE DOORS AND |
| | WINDOWS. PLEASE ADD NOTE TO |
| | DRAWINGS. |
| | |
| | 47. NO CUTTING OR WELDING OPERATIONS |
| | TO OCCUR WITHOUT APPROVAL OF THE |
| | FIRE PREVENTION BUREAU AND COMPLIANCE |
| | WITH NFPA 51B. |
| | |
| | 48. ALL SHAFTS THAT ARE LARGE ENOUGH |
| | FOR PERSONS TO FALL INTO MUST BE |
| | MARKED SHAFTWAY WITH 6" HIGH |
| | LETTERS. |
| | |
| | 49. ALL ARCHITECURAL TRIM LOCATED |
| | IN THE FIRE LIMITS SHALL BE |
| | NON-COMBUSTIBLE. |
| | |
| | 50. PAGE E0.01 INSERTED UPSIDE DOWN |
| | IN SET. |
| | |
| | 51. A SITE PLAN DETAILING ALL EXISTING |
| | OR NEW FIRE HYDRANTS AND WATER MAINS |
| | SHALL BE PROVIDED. |
| | |
| | 52. PLEASE INDICATE EMERGENCY LIGHTING |
| | FOR LANAI DECK, PAGE E1.03. |
| | |
| | 53. CLASS B FIRE ALARM CIRCUITS SHOWN |
| | ON PAGE E8.04. ONLY CLASS A, STYLE D |
| | OR FULLY ADDRESSABLE FIRE ALARM |
| | CIRCUITS |
| | SHALL BE PERMITTED. |
| | |
| | 54. FIRE ALARM SYSTEM SHALL MEET THE |
| | SURVIVABILITY REQUIREMENTS OF NFPA 72. |
| | |
| | 55. NOTE # 40 ON PAGE E8.04 IS |
| | INCORRECT. LIFE SAFETY CODE 2003 |
| | EDITION SHOULD BE REFERENCED. |
| | |
| | 56. BUILDING IS TO COMPLY WITH |
| | SECTON 11-8, LIFE SAFETY CODE, 2003 |
| | EDITION. |
| | |
| | 57. THE FIREFIGHTER SMOKE MANAGEMENT |
| | PANEL SHALL PROVIDE A GRAPHIC |
| | REPRESENTATION OF THE BUILDING. HOA |
| | SWITCHES WITH NO OVERLAY OF THE |
| | BUILDING WILL NOT BE ACCEPTABLE. |
| | |
| | 58. MORE DETAILS REQUIRED ON PROPOSED |
| | DRYER BOOSTER FANS. SHOWN ON |
| | ELECTRICAL PAGES. |
| | |
| | 59. EXIT SIGN SHOWN ON PAGE E2.01 |
| | DIRECTING PERSONS INTO LOADING |
| | AREA. PLEASE EXPLAIN. |
| | |
| | 60. EXIT SIGNS APPEAR TO BE MISSING |
| | ON SOME OF THE ELECTRICAL DRAWINGS. |
| | |
| | 61. MORE EXIT SIGNS APPEAR TO BE |
| | NEEDED ON PAGE E2.02. |
| | |
| | 62. MORE EXIT SIGNS APPEAR TO BE |
| | NEEDED ON PAGE E2.08. |
| | |
| | 63. ONLY TWO EXIT SIGNS SHOWN ON |
| | PAGE E2.11. |
| | |
| | 64. THE ANTICPATED STACK EFFECT NOTE |
| | WORDING SHALL BE ADDED TO THE |
| | MECHANICAL PLANS. |
| | |
| | 65. FIRE DAMPERS TO COMPLY WITH |
| | UL 555. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |