| Date |
Text |
| 2005-01-06 00:00:00 | *************** UNSAT ***************** |
| | |
| | PLAN REVIEW ONLY FOR "TWO CITY PLAZA" |
| | PLANS NOT SUBMITTED FOR PERMIT AT THIS |
| | TIME, ONLY IN FOR "PLAN REVIEW". |
| | |
| | |
| | **************************************** |
| | *************************************** |
| | |
| | PLEASE SEE THAT DUE TO PLANS NOT BEING |
| | COMPLETE AT THIS TIME, A FULL REVIEW |
| | FOR 2002 NEC CODE COMPLIANCE CAN NOT BE |
| | DONE. |
| | **************************************** |
| | *************************************** |
| | |
| | THE FOLLOWING NOTES ARE ONLY BASED ON |
| | WHAT INFORMATION IS AVAIBLAE AT THIS |
| | TIME. |
| | **************************************** |
| | *************************************** |
| | |
| | 1)NOTE: PLEASE SEE SOME SHEETS HAVE THE |
| | ELECTRICAL PRINTED WITH DARKEN LINES |
| | AND MANY OF THE SHEETS ARE LT GRAY FOR |
| | ELECTRICAL. PLEASE DARKEN FOR EASE OF |
| | REVIEW PROCESS. |
| | |
| | 2)NOTE: PLEASE SUBMIT WIND-LOADING FOR |
| | SITE/POLE LIGHTING AT THIS TIME. THIS |
| | IS REQUIRED FOR REVIEW AT THIS TIME. |
| | WIND LOADS 140MPH PER FBC. |
| | |
| | 3)NOTE: PLEASE SEE FAC 61G15-23.002, |
| | 61G1-16.004 FOR MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCKS FOR BOTH |
| | ENGIEERING FIRM AND ARCH FIRM. |
| | FS 471.023,481.219 |
| | PLEASE ALSO SEE PLANS ARE REQUIRED TO |
| | BE SIGNED, DATED AND SEALED BY ENGINEER |
| | WHEN SUBMITTING FOR PERMIT. |
| | |
| | 4)NOTE: PLEASE PROVIDE NOTE ON POOL |
| | PLANS: POOL TO BE UNDER SEPARATE: |
| | PLEASE PROVIDE NOTE FOR HOURS OF |
| | SWIMMING. IF AFTER DUSK SWIMMING IS TO |
| | TAKE PLACE AND COMPLETE PHOTOMETRICS |
| | WILL NEED TO BE SUBMITTED FOR REVIEW |
| | AND STAMPING BY THE PALM BEACH COUNTY |
| | HEALT DEPT. AND WILL BE REQUIRED TO BE |
| | IN THIS PLAN REVIEW. |
| | |
| | 5)NOTE: PLEASE SEE FPL VAULT ROOM IS |
| | ALSO NOTED AS BEING ELECTRICAL ROOM FOR |
| | GARAGE. PLEASE SEE FPL VAULT |
| | REQUIREMENTS SET FORTH BY FPL AND |
| | PERMITTING NO OTHER ELECTRICAL |
| | EQUIPMENT |
| | IN THEIR VAULT. |
| | |
| | 6)NOTE: ELECTRICAL PLANS DO NOT CLEARLY |
| | SHOW A DIRECT FIRE RATE ACCESS TO MAIN |
| | ELECTRICAL RM WHICH APPEARS TO BE |
| | LOCATED ABOVE GRADE LEVEL. PLEASE |
| | PROVIDE INFORMATION/DIRECTIONAL FOR |
| | ACCESS FOR FIRE DEPT PERSONNEL FOR |
| | SHUTTING DOWN OF MAINS. PLEASE ALSO |
| | PROVIDE NOTE ON PLANS FOR REQUIRED |
| | "KNOX BOX" FOR FIRE DEPT. PLEASE SEE |
| | FIRE REVIEW NOTES FOR THIS. |
| | |
| | 7)NOTE: PLEASE SEE MANY AREAS OF PLANS |
| | FOR COMMON AREAS/COMMON HALLWAYS ETC DO |
| | NOT INDICATE ANY ELECTRICAL FOR |
| | LIGHTING, RECEPTS, FIRE DEVICES ETC. |
| | PLEASE SUBMIT COMPLETED COMMON AREAS. |
| | |
| | 8)NOTE: PLEASE SEE 620.23,620.24 FOR |
| | REQUIREMENTS IN ELEV RMS/ PITS ETC. |
| | |
| | 9)NOTE: PLEASE CLARIFY RECEPTS W/IN 20' |
| | OF POOL ON ROOF.620.22A3 WHERE A |
| | PERMANENTLY INSTALLED POOL IS INSTALLED |
| | AT A DWELLING UNIT(S), NO FEWER THAN |
| | ONE 125-VOLT 15- OR 20-AMPERE RECEPTACLE |
| | ON A GENERAL-PURPOSE BRANCH CIRCUIT |
| | SHALL BE LOCATED NOT LESS THAN 3.0 M (10 |
| | FT)FROM AND NOT MORE THAN 6.0 M (20 FT) |
| | FROM THE INSIDE WALL OF THE POOL. |
| | |
| | 10)NOTE: PLEASE SEE GENERAL NOTES ON |
| | UNIT ELECTRICLA PLANS REFERENCE 1999 |
| | NEC. PLEASE SEE AS OF JULY 1ST, 2003, |
| | WE ARE UNDER THE 2002 NEC. PLEASE |
| | ADJUST |
| | NOTES AND PLEASE ALSO ADJUST ALL OTHER |
| | SHEETS WHERE CODES ARE REFERENCED. |
| | |
| | 11)NOTE: PLEASE PROVIDE A COMPLETE |
| | FIXTURE SCHEDULE. PLEASE ALSO CORRELATE |
| | WITH PLANS. |
| | |
| | 12)NOTE: PLEASE CLARIFY UNITS, |
| | 1,2,3,AND 4. IT APPEARS THERE IS NO |
| | ACCESS TO UNITS FROM GARAGE? |
| | |
| | 13)NOTE: PLEASE SEE 210.70 FOR CONTROL |
| | OF EGRESS LIGHTING FOR UNITS W/ ACCESS |
| | FROM OUTSIDE WITH WHAT APPEARS TO HAVE |
| | NO CONTROL/SWICTHING OF LIGHTING WHEN |
| | ENTERING THE UNITS. |
| | PLEASE ALSO SEE ANY OTHER GRADE LEVEL |
| | ACCESS UNITS WHICH 3-WAY SWITCHING MAY |
| | BE REQUIRED. LS-101 5-8 |
| | |
| | 14)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. |
| | PLEASE SEE UNITS #6, 17 |
| | |
| | 15)NOTE: PLEASE SEE SD'S APPEAR TO BE |
| | SHOWN ON LITCHEN/BATH LIGHTING |
| | CIRCUITS. |
| | THIS IS FINE, HOWEVER ARC FAULT |
| | PROTECTION WOULD ALSO BE REQUIRED FOR |
| | THISE CIRCUITS AND NEED TO BE NOTED ON |
| | PANEL SCHEDULES. (NOTE 6) ON PANEL |
| | SCHEDULES. |
| | PLEASE SEE 2002 NEC 210.12 |
| | |
| | 16)NOTE: PLEASE SEE SOME UNITS, IN SOME |
| | BEDRMS, SD'S ARE MISSING. ( #11) |
| | NFPA-72 8-1.4.1.6.2 |
| | |
| | 17)NOTE: PLEASE SEE 210.52D FOR GFI |
| | RECEPTS REQUIRED WITHIN 3' OF THE EDGE |
| | OF LAVS. PLEASE SEE AREAS WITH TWO |
| | SINKS. GFI MAY BE MOVED TO CENTER OF |
| | SINKS OR MAYHAVE AN ADDITIONAL GFI |
| | ADDED. |
| | |
| | 18)NOTE:PLEASE SEE PANEL NOT PERMITTED |
| | IN STORAGE/CLOTHES CLOSET. 240.24 |
| | OVERCURRENT DEVICES SHALL NOT BE |
| | LOCATED IN THE VICINITY OF EASILY |
| | IGNITIBLE MATERIAL, SUCH AS IN CLOTHES |
| | CLOSETS. |
| | PLEASE ALSO SEE 408.7 |
| | |
| | 19)NOTE:PLEASE SEE SOME UNITS APPEAR TO |
| | BE SHOWING TWO PANELS. UNIT VV. |
| | |
| | 20)NOTE: PLEASE SEE 110.26 FOR MIN |
| | CLEARENCE REQUIREMENTS FOR PANELS SHOWN |
| | IN SOME UNITS. ONE SHOWN FACING |
| | COUNTERSPACE/ DISHWASHER. UNIT M. |
| | |
| | 21)NOTE: PLEASE SEE 210.70 FOR LT |
| | REQUIRED FOR AHU'S IN HALL CLOSETS, |
| | PLEASE ALSO SEE 210.63 |
| | |
| | 22)NOTE: PLEASE SEE 210.52C1-4 |
| | PENINSULAR COUNTER SPACES. AT LEAST ONE |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT |
| | EACH PENINSULAR COUNTER SPACE WITH A |
| | LONG DIMENSION OF 600 MM (24 IN.) OR |
| | GREATER AND A SHORT DIMENSION OF 300 MM |
| | (12 IN.) OR GREATER. A PENINSULAR |
| | COUNTERTOP IS MEASURED FROM THE |
| | CONNECTING EDGE.COUNTERTOP SPACES |
| | SEPARATED BY RANGE TOPS, REFRIGERATORS, |
| | OR SINKS SHALL BE CONSIDERED AS |
| | SEPARATE COUNTERTOP SPACES IN APPLYING |
| | THE REQUIREMENTS OF 210.52(C)(1), (2), |
| | AND (3). UNITS D, G, A ETC. |
| | |
| | 23)NOTE: PLEASE PLACE NOTE ON PLANS FOR |
| | SD LOCATION REQUIREMENTS PER NFPA-72 |
| | 8-1.4.2 |
| | |
| | 24)NOTE: PLEASE VERIFY IF THERE ARE |
| | GOING TO BE ANY TERRACE LTS/GFI'S? |
| | PLEASE SEE ARCH SHEETS, ELEVATION PLANS |
| | SHOWS LTS. PLEASE CORRLELATE. |
| | PLEASE ALSO CORRELATE LAYOUT OF TERRACE |
| | ON ELECTRICAL PLANS WITH LAYOUT AS |
| | SHOWN ON FLR PLANS ON ARCH. |
| | |
| | 25)NOTE:PLEASE VERIFY IF UNITS WITH |
| | JACUZZI/SPA UNITS. PANEL SCHEDULES |
| | INDICATE SOME AS FUTURE AND SOME APPEAR |
| | TO BE INSTALLED AT THIS TIME, HOWEVER |
| | THE FLR LAYOUTS DO NOT INDICATE THIS OR |
| | GFI RECEPTS OR GFI BRKRS.680.62A THE |
| | OUTLET(S) THAT SUPPLIES A |
| | SELF-CONTAINED THERAPEUTIC TUB OR |
| | HYDROTHERAPEUTIC TANK, A PACKAGED |
| | THERAPEUTIC TUB OR HYDROTHERAPEUTIC |
| | TANK, OR A FIELD-ASSEMBLED THERAPEUTIC |
| | TUB OR HYDROTHERAPEUTIC TANK SHALL BE |
| | PROTECTED BY A GROUND-FAULT CIRCUIT |
| | INTERRUPTER. |
| | |
| | 26)NOTE: PLEASE SEE OCP FOR FIRE PUMP |
| | IS TO BE PER LOCKED ROTOR AS NOTED ON |
| | RISER. PLEASE SUBMIT ALL INFORMATION |
| | FOR FIRE PUMP, FIRE PUMP CONTROLLER. |
| | ETC |
| | SUBMIT ALL MANUFACT SPECS. |
| | PLEASE SPECIFY CODE LTR FOR PUMP. |
| | |
| | |
| | 27)NOTE: PLEASE ALSO SUBMIT ALL |
| | MANUFACTURER SPECS FOR GENERATOR, ALL |
| | TRANSFER SWITCHES AND FUEL TANK, SHOWING |
| | ALL LISTINGS BY THE NRTL. |
| | |
| | 28)NOTE: PLEASE SEE 110.26 FOR ALL |
| | CLEARENCE REQUIREMENTS FOR ELECTRICAL |
| | RMS AND CLOSETS. MANY OF THE LAYOUTS |
| | SHOWN DO NOT MEET 110.26 FOR CLEARENCE |
| | OF EQUIPMENT. |
| | PLEASE ALSO SEE 110.26 FOR DOOR SWING, |
| | AND REQUIREMENTS FOR PANIC HARDWARE ON |
| | DOORS. A NOTE NEEDS TO BE PLACED ON |
| | PLANS FOR THIS REQUIREMT. |
| | |
| | 29)NOTE:PLEASE CORRELATE ELECTRICAL |
| | RISER WITH ELECTRICAL EQUIPMENT SHOWN |
| | IN |
| | ELECTRICAL RMS. PLEASE SEE MISSING |
| | "SHE". |
| | |
| | 30)NOTE: PLEASE CORRELATE "K" NOTES ON |
| | RISER WITH THE ACTUAL SCHEDULE OF KEYED |
| | NOTES ON PLANS. K-10 ETC. |
| | |
| | 31)NOTE: PLEASE VERIFY COPPER EQUIPMENT |
| | GROUNDING IN BUS-DUCT. PLEASE SEE LOAL |
| | AMENDMENTS WHICH DOES NOT PERMIT ALUM |
| | FOR GROUNDING OR BONDING.310.2,250.62 |
| | |
| | 32)NOTE: PLEASE PROVIDE NOTE WHEATHER |
| | OR NOT GENERATOR WILL BE SEPARATELY |
| | DERIVED OR NOT. IF YES, PLEASE SEE ATS, |
| | TO 4-POLE. |
| | |
| | 33)NOTE: PLEASE SEE RISER FOR ATS SIZES |
| | AND OCP FEEDING ATS SWITCHES. PLEASE |
| | SEE 900A OCP FEEDING 800A ATS. |
| | |
| | 34)NOTE: PLEASE COMPLETE RISER DIAGRAM |
| | WITH SIZE OF EQUIPMENT SHOWN ON RISER. |
| | PLEASE PROVIDE SIZES OF ALL EQUIPMENT , |
| | TRANSFORMERS, GROUNDING FOR |
| | TRANSFORMERS, KEYED NOTES ON RISER ETC. |
| | 215.5,250.30, ETC. |
| | PLEASE SUBMIT PANEL SCHEDULES FOR ALL |
| | EQUIPMENT SHOWN ON SERVICE RISER. |
| | PLEASE SEE RISER/NOTES APPEAR TO HAVE |
| | 4000A MAINS/OCP FEEDING 3000A BUS-DUCT. |
| | MANY OF THESE ITEMS CAN NOT BE VERIFIED |
| | AT THIS TIME, DUE TO NONE OFTHIS |
| | INFORMATION SUBMITTED. |
| | |
| | 35)NOTE: PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS FOR BUILDING. THE ONLY |
| | LOAD CALCS SUBMITTED WERE FOR |
| | INDIVIDUAL |
| | UNITS AND METER CNTRS. |
| | 215.5,220 |
| | |
| | 36)NOTE: PLEASE VERIFY MANY UNITS ONLY |
| | SHOWING A "COOKTOP". ARE THESE RANGES, |
| | CONTAINING AN OVEN ALSO? |
| | SOME UNITS SHOW SEPARATE COOKTOPS AND |
| | OVENS, BUT IT APPEARS UNITS ONLY WITH |
| | "COOKTOP" WILL HAVE NO OVENS?? |
| | |
| | 37)NOTE: PLEASE SEE FEEDERS SCHEDULE |
| | SET UP FOR UNITS SHOWN FOR 125A,150A |
| | AND |
| | 175A ONLY. PLEASE SEE LOADS CALCS/MTR |
| | CNTRS SHOW SOME UNITS FED WITH 200A OCP |
| | AND 250A OCP. PLEASE SEE MIN CONDUCTORS |
| | FOR 250A PER 310.16 |
| | |
| | 38)NOTE: PLEASE VERIFY SIZE OF PANELS. |
| | PANELS ARE SHOWN AS 200A , HOWEVER SOME |
| | SHOWN W/ 250A OCP FROM METER CNTRS. |
| | |
| | 39)NOTE: PLEASE VERIFY OCP FOR SOME |
| | WATER HEATERS ( 6KW) MAX OCP 150%, PER |
| | 422.11, MIN 125% 422.13.A BRANCH |
| | CIRCUIT |
| | SUPPLYING A FIXED STORAGE-TYPE WATER |
| | HEATER THAT HAS A CAPACITY OF 450 L |
| | (120GAL) OR LESS SHALL HAVE A RATING |
| | NOT |
| | LESS THAN 125 PERCENT OF THE NAMEPLATE |
| | RATING OF THE WATER HEATER. |
| | |
| | PLEASE SEE MANY OF THESE NOTES ARE |
| | REDLINED ON ONE SET OF REVIEWED PLANS |
| | FOR AREAS OF CONCERN. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | SUBMIT COMPLETED SETS FOR REVIEW. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE ANY |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| 2005-01-03 00:00:00 | IN ELECTRICAL FOR REVIEW. |
| | NOTES TO FOLLOW. |