Plan Review Notes
Plan Review Notes For Permit 04120256
Permit Number 04120256
Review Stop M
Sequence Number 2
Notes
Date Text
2005-03-02 00:00:00DENIED:
 1.LETTER PROVIDED FROM THE OWNER
 INDCIATING THE MECHANICAL CONTRACTOR IS
 ACCEPTABLE.THE PLANS SUBMITTED HAVE A
 TITLE BLOCK BY GORDON F. BUCK, P.E.PER
 THE FS 471.025 & FAC 61G15-23.002, WHEN
 A TITLE BLOCK IS DISPLAYED ON THE PLANS
 THE ENGINEER SHALL SIGN, SEAL AND DATE
 SAID PLANS.THE LETTER PROVIDED
 INDICATES THE MECHANICAL CONTRACTOR IS
 TO PROVIDE PLANS THEREFORE AN ENGINEER
 SHOULD NOT BE INDICATED ON THE PLAN.
 THE PERSON FROM THE MECHANICAL
 CONTRACTOR THAT DESIGNED THE SYSTEM IS
 THE PERSON RESPONSIBLE AND SHALL SIGN
 AND DATE PLANS.
  
 2.PLANS DO NOT INDICATE FIRE DAMPERS.
 THE ARCHITECTURAL PLANS INDICATE RATED
 WALLS FOR TENANT SEPARATION (A3).
  
 3.PLEASE CLARIFY RATING BETWEEN THE
 HALL AND TENANT ROOMS.
  
 4.THE MECHANICAL PLANS SUBMITTED
 INDICATE RETURN AIR JUMPERS FROM THE
 TENANT ROOMS INTO THE HALL AREA AND A
 FREE RETURN BACK TO THE AHU. PER 2001
 FBC(M)403.2.1, AIR SHALL NOT BE
 RECIRCULATED FROM ONE DWELLING TO
 ANOTHER OR DISSIMILAR OCCUPANCIES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  