Plan Review Notes
Plan Review Notes For Permit 04120220
Permit Number 04120220
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-12-30 00:00:001) WHERE BUILDINGS ARE SUBJECT TO AN
 OCCUPANT LOAD OF 100 OR MORE, PANIC
 HARDWARE IS REQUIRED.
 2) PLANS DON'T SHOW AN ADDRESS NUMBER ON
 THE FRONT ELEVATION. NUMBER IS TO BE AT
 LEAST 6" IN HEIGHT AND CONTRASTING TO
 BACKGROUND.
 3) SHOP DRAWINGS WILL BE REQUIRED FOR
 FIRE ALARM SYSTEM.
 4) SHOP DRAWINGS FOR SPRINKLER SYSTEM
 WILL BE REQUIRED.
 5) PLEASE CLARIFY LOCATIONS OF EXIT
 SIGNS AND EMERGENCY LIGHTING FOR MEANS
 OF EGRESS.
  
  
 M.R. WENNERGREN, A/CAPT
 WPBFR(561) 835-2910