2004-12-23 00:00:00******** UNSAT **********
  
  
 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE AIC RATING IS SHOWN FOR ALL
 BUT MAIN #2.
  
 2)NOTE: PLEASE PROVIDE CLEAR SPCE AND
 NOTES FOR CLEARENCES FOR ELECTRICAL
 PANELS AND MAINS PER 110.26.
 THESE ARE ALSO NOT PERMITTED IN "STORAGE
 AREAS/RMS. PLEASE SPECIFY
 STORAGE.WITCHBOARDS SHALL BE PLACED SO
 AS TO REDUCE TO A MINIMUM THE
 PROBABILITY OF COMMUNICATING FIRE TO
 ADJACENT COMBUSTIBLE MATERIALS. WHERE
 INSTALLED OVER A COMBUSTIBLE FLOOR,
 SUITABLE PROTECTION THERETO SHALL BE
 PROVIDED.
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING FROM PANEL "DPA" TO "B"
 PLEASE SIZE PER 250.122
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 THREE COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  