| 2004-12-23 00:00:00 | ******** UNSAT ********** |
| | |
| | |
| | 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLEASE SEE AIC RATING IS SHOWN FOR ALL |
| | BUT MAIN #2. |
| | |
| | 2)NOTE: PLEASE PROVIDE CLEAR SPCE AND |
| | NOTES FOR CLEARENCES FOR ELECTRICAL |
| | PANELS AND MAINS PER 110.26. |
| | THESE ARE ALSO NOT PERMITTED IN "STORAGE |
| | AREAS/RMS. PLEASE SPECIFY |
| | STORAGE.WITCHBOARDS SHALL BE PLACED SO |
| | AS TO REDUCE TO A MINIMUM THE |
| | PROBABILITY OF COMMUNICATING FIRE TO |
| | ADJACENT COMBUSTIBLE MATERIALS. WHERE |
| | INSTALLED OVER A COMBUSTIBLE FLOOR, |
| | SUITABLE PROTECTION THERETO SHALL BE |
| | PROVIDED. |
| | |
| | 3)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING FROM PANEL "DPA" TO "B" |
| | PLEASE SIZE PER 250.122 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | THREE COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWERS WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |