| 2005-09-08 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)SEE PREVIOUS LISTS IN REGARDS TO |
| | OCCUPANCY AND OCCUPANT LOAD.THE INDEX |
| | SHEET STATES NUMBER OF SEATS AS 44, |
| | NUMBER OF PEOPLE AS 44 AND 6 EMPLOYEES, |
| | AND OCCUPANCY COUNTY AS 42, MERCANTILE |
| | OCCUPANCY.TO BE MERCANTILE IT REQUIRES |
| | AN OCCUPANT LOAD OF LESS THAN 50, THIS |
| | OCCUPANT LOAD IS 50 (NOT 42). |
| | |
| | 3.)TWO MEANS OF EGRESS MAY BE |
| | REQUIRED.CODE COMPLIANCE CANNOT BE |
| | DETERMINED WITHOUT REQUESTED |
| | INFORMATION. |
| | |
| | 4.)THE KEY PLAN, INDEX SHEET, SHOWS A |
| | DIFFERENT PARKING CONFIGURATION THAN S1. |
| | IS ONE EXISTING, THE OTHER PROPOSED? |
| | |
| | 5.)THE NEW SHEET, S1, SHOWS THE |
| | ACCESSIBLE ROUTE FROM THE HC PARKING |
| | SPACE TO THE FRONT DOOR OF THE |
| | RESTAURANT GOING ACROSS A CURB CUT. |
| | SHOW COMPLIANCE WITH FBC11-4.3.SHOW |
| | CROSS SLOPE. |
| | |
| | 6.)THE USE OF SHUTTERS ON COMMERCIAL |
| | BUILDINGS REQUIRES APPROVAL BY THE |
| | BUILDING OFFICIAL.SEE ATTACHED POLICY |
| | FOR MISSILE IMPACT PROTECTION, ITEM #13. |
| | SUBMIT AN INSTALLATION PLAN AND |
| | INSTALLATION SCHEDULE, ATTACHED. |
| | |
| | 7.)SEE PREVIOUS LISTS, FLORIDA STATE |
| | OR LOCAL PRODUCT APPROVAL REQUIRED IN |
| | ADDITION TO THE NOAS PROVIDED.PRODUCT |
| | APPROVALS NOT APPROVED PRIOR TO PERMIT |
| | ISSUANCE WILL REQUIRE SEPARATE PERMITS. |
| | |
| | 8.)SEE PREVIOUS LIST IN REGARDS TO |
| | INDICATING ON THE PRODUCT APPROVAL WHICH |
| | PRODUCT YOU ARE USING. |
| | |
| | 9.)A STATE PRODUCT APPROVAL FOR DOORS |
| | WAS SUBMITTED BUT DID NOT INDICATE WHICH |
| | DOOR ON THE PRODUCT APPROVAL WAS TO BE |
| | INSTALLED.THE EVALUATION REPORT OR |
| | TEST REPORT AND INSTALLATION |
| | INSTRUCTIONS ARE REQUIRED AS WELL. |
| | |
| | 10.)PLEASE CLEARLY INDICATE ALL |
| | CHANGES TO THE PLAN.FOR EXAMPLE, |
| | "REROOF" WAS REMOVED FROM INDEX SHEET, |
| | ITEM #9, BUT IS NOT CLOUDED. |
| | |
| | 11.)CHANGE OF USE MAY REQUIRE IMPACT |
| | FEES.561-233-5025 |
| | |
| | 12.)A 4X FEE HAS BEEN CHARGED AS |
| | REQUIRED BY FS553.80(2)(B). |