| Plan Review Notes For Permit 04120217 |
| Permit Number |
04120217 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-08-22 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | FROM PREVIOUS REVIEWS | | | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2. - | | | FRYER SHOWN 90,000 BTU ON RISER DIAGRAM, | | | BUT SHOWS 105,OOO BTU ON MANUF. SHEET. - | | | RANGE MANUF. SHEET NOT SUBMITTED. - | | | STEAM TABLE HAS NO LISTING AND BUT'S ARE | | | HAND WRITTEN ON SHEET. - PIZZA/DECK | | | OVENS SHOW 120,000 BTU ON RISER DIAGRAM, | | | BUT ONLY 80,000 BTU ON MANUF. SHEET. - | | | ROTISSERIE MANUF. SHEET SHOWS NO LISTING | | | AND NO MODEL NUMBER INDICATED. - NO | | | WATER HEATER MANUF. SHEET SUBMITTED. | | | PLEASE CLARIFY. | | | 1B. SHT A-1.1 EQUIPMENT SCHEDULE, ITEM | | | 21 SHOWS INDIRECT WASTE, BUT ITEM 21 WAS | | | NOT SHOWN ON THE EQUIPMENT PLAN, NOR ON | | | THE RISER DIAGRAM. PLEASE CLARIFY. | | | SECTION 104.2.1. | | | 3B. ARCHITECT AND ENGINEER SHALL AFFIX | | | THEIR SEAL, SIGN AND DATE ALL SHEETS | | | PREPARED BY THEM. SECTION 1-4.2.2. SEE | | | SHT A-4.0 IS NOT SIGNED/SEALED/DATED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|