| Notes |
| Date |
Text |
| 2005-05-30 00:00:00 | DENIED: | | | PLAN SHEET A-4.0 IS NOT SIGNED, SEALED | | | AND DATED BY THE ARCHITECT/ENGINEER AS | | | REQUIRED BY FS 481 & 471 RESPECTIVELY. | | | | | | PROVISO: | | | GREASE HOOD EXHAUST TERMINATION SHALL | | | COMPLY WITH 2001 FBC/M 506.3.14.1 & | | | 506.3.14.3. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | HOOD SUPPRESSION AND WALK-IN COOLERS. | | | PROVIDE PLANS AND MANUFACTURER'S | | | SUBMITTAL DATA WITH PERMIT APPLICATIONS. | | | | | | FAN SHUTDOWN REQUIRED FOR FINAL | | | INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 |
|