| 2005-05-13 00:00:00 | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED.THE NOC IS |
| | EXPIRED; OVER 90 DAYS WITHOUT COMMENCING |
| | WORK, FS713.13.THE NOC IS FOR A |
| | DIFFERENT LOT THAN REFERENCED ON YOUR |
| | PERMIT APPLICATION.TWO DIFFERENT |
| | PARCEL ID NUMBERS ARE ON THE NOC. |
| | |
| | 2.)TO EXPEDITE PLAN REVIEW, ALL |
| | CHANGES SHOULD BE CLOUDED WITH OLD |
| | SHEETS SUBMITTED SEPARATELY.NO CHANGES |
| | ARE INDICATED AND THE OLD SHEETS ARE NOT |
| | IN THE PACKAGE. |
| | |
| | 3.)SEE THE PREVIOUS LIST, ITEM #1. |
| | RESTAURANT IS A OCCUPANCY (WAS M FOR |
| | FIRST REVIEW, NOW IS B ON THE INDEX |
| | SHEET).FBC304. |
| | |
| | 4.)SEE THE PREVIOUS LIST, ITEM #2. |
| | THE TOTAL OCCUPANT LOAD CANNOT BE LESS |
| | THAN SPECIFIED IN FBC TABLE 1003.1 AS |
| | PER FBC1003.1.1.YOU CAN STATE THE |
| | OCCUPANCY FOR THE FIXED SEATING AREA BUT |
| | THE REMAINING AREA MUST BE CALCULATED |
| | AND OCCUPANCY PER FBC TABLE 1003.1 IS TO |
| | BE APPLIED. |
| | |
| | 5.)INDEX SHEET, ITEM #9 STATES ?REROOF |
| | BUILDING?.THIS WILL NOT BE INCLUDED IN |
| | THIS REVIEW UNLESS PRODUCT APPROVALS ARE |
| | SUBMITTED. |
| | |
| | 6.)THE DUPLICATE APPLICATION IS |
| | INCOMPLETE.INCLUDE THE PARCEL ID AS |
| | REQUIRED BY FLORIDA STATUTE. |
| | |
| | 7.)PROVIDE A SURVEY FOR THIS PROPERTY. |
| | |
| | |
| | 8.)INDEX SHEET DECLARES TYPE IV |
| | CONSTRUCTION.A1 SHOWS EXISTING 2X10S |
| | WHICH APPEAR TO BE ROOF JOISTS.TYPE IV |
| | REQUIRES NONCOMBUSTIBLE ROOF. |
| | |
| | 9.)SEE PREVIOUS LIST, SHOW COMPLIANCE |
| | FOR THE ADA PARKING SPACE.SEE ATTACHED |
| | DETAIL. |
| | |
| | 10.) A MINIMUM OF TWO INDEPENDENT EXITS |
| | REQUIRED, FBC1004.2, IN ACCORDANCE WITH |
| | FBC1004.1.4. |
| | |
| | 11.)PRODUCT APPROVALS REQUIRED: |
| | ROOF |
| | EXTERIOR DOORS |
| | SHUTTERS |
| | WINDOWS |
| | |
| | ANY PRODUCT APPROVALS NOT SUBMITTED AND |
| | REVIEWED PRIOR TO ISSUANCE WILL REQUIRE |
| | SEPARATE PERMITS FOR THOSE ITEMS. |
| | |
| | VARIOUS PRODUCT APPROVALS WERE |
| | SUBMITTED.THE NOAS DID NOT HAVE A |
| | FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | AND THE FLORIDA STATE PRODUCT APPROVAL |
| | DID NOT HAVE A TEST REPORT/INSTALLATION |
| | INSTRUCTIONS ATTACHED AS PREVIOUSLY |
| | REQUESTED. |
| | |
| | 12.)SHEET A1 STATES ?RECONDITION |
| | WINDOWS?,APPLICATION STATES INSTALLING |
| | NEW WINDOWS. |
| | |
| | 13.)THE PLANS STATES ?ACOUSTICAL |
| | CEILING, SEE PLAN?.WHAT PLAN? |
| | |
| | 14.)SHOW MANEUVERING CLEARANCE FOR |
| | DOORS #2 AND #3, FBC11 FIGURE 25. |
| | |
| | 15.)THE FIRE EXTINGUISHER APPEARS TO |
| | BE IN THE MANEUVERING CLEARANCE REQUIRED |
| | FOR DOOR #1, FBC11 FIGURE 25. |
| | |
| | 16.)PROVIDE A DIMENSION FOR THE GRAB |
| | BAR BEHIND THE TOILET.NONE OF THE GRAB |
| | BARS SHOWN HAVE AN ACTUAL DIMENSION AND |
| | ARE SHOWN GRAPHICALLY AS SMALLER THAN |
| | THE 36 IN MINIMUM REQUIRED.THE FLOOR |
| | PLAN GRAPHIC IS IN CONFLICT WITH YOUR |
| | FIGURE 29. |
| | |
| | 17.)THE APPLICATION INDICATES THAT |
| | DRYWALL WILL BE INSTALLED.ON ALL |
| | EXTERIOR WALLS? SCOPE OF WORK NOT CLEAR. |
| | INSULATION REQUIRED, FBC13-402. |
| | |
| | 18.)SEE ATTACHED FS553. |
| | |