| Date |
Text |
| 2005-01-07 00:00:00 | DENIED; |
| | 1.GREASE TRAPSARE REQUIRED TO HAVE |
| | UTILITY DEPARTMENT APPROVAL. PLEASE |
| | CONTACT RODNEY COMPO AT 561-837-4074. |
| | 2.MANUFACTOR'S SPECIFICATIONS ARE |
| | REQUIRED FOR GREASE TRAP (WADE #5120. |
| | 3.THREE COMPARTMENT SINK TO DUMP INTO A |
| | FLOOR SINK WITH AN AIR GAP NOT SHOWN ON |
| | FLAT DRAWING. |
| | 4.FLOOR DRAINS NOT PERMITED IN WALKIN |
| | COOLERS. |
| | 5.PLANS TO BE APPROVEDBY THE DEPARTMENT |
| | OF HOTEL AND RESTAURANT, BEFOREREVIEW BY |
| | THE CITY OF WEST PALM BEACH. |
| | 6.HAND SINK REQUIRED IN FOOD PREP AREA. |
| | 7.MOP SINK,AND FLOORDRAINS IN KICHEN AND |
| | PREP AREA ARE REQUIRED TO GO TO GREASE |
| | TRAP. |
| | 8.PLEASE SHOW A DETAIL OF BATHROOM SHOW |
| | ALL MESUREMENTS TO COMPLY WITH FHC |
| | CHAPTER 11. TOILET, LAV, GRAB BARS, |
| | ETC. |
| | GAS |
| | 1.SHOW ALL CUT SECTIONS OF PIPE AND |
| | CORRESPONDING LENTHS OER. FBC 2001 FUEL |
| | GAS. |
| | 2.SHOW BTU'S LOAD OF EACH APPLIANCE. |
| | (MISSING BTU'S FOR STEAM TABLE) AND |
| | TOTAL BTU'S AND TOTAL LENTH ( LONGEST |
| | RUN) |
| | 3.SHUTOFF VALVES TO BE ACCESSABLE. |
| | 4.A UNION IS REQUIRED ON THE DOWN STREAM |
| | SIDE OF THE ENSUL VALVE FOR SERVICE. |
| | 5.INDICATE THE DELIVERY PRESSURE PER. |
| | FBC FUEL GAS 402.2. SPECIFY .5 OR 2 |
| | PSI. |
| | 6.SUBMIT MANUFACTURES SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDERDS FUEL GAS SEC. 402.2. |
| | 7.PLEASE USE GAS SIZING CHARTS CHAPTER 4 |
| | OF THE FBC FUEL GAS AND NOTE ON PLANS |
| | WHAT TABLE WAS USED. |
| | PLUMBING PLAN REVIEW BY; |
| | |
| | JOHN LEECH |
| | |
| | 805-6695 |