| Date |
Text |
| 2004-12-27 00:00:00 | ************* UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SHOW SEC'S ON RISER PER |
| | 310.16, 240.4B. NONE LOCATED ON RISER. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE 250.50 FOR GROUNDING |
| | ELECTRODE SYSTEM. PLEASE SEE 250.104 |
| | FOR METALPIPING SYSTEMS. |
| | |
| | 4)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EM/EXT LTS ON LOCAL BRANCH |
| | CIRCUIT. |
| | |
| | 5)NOTE: PLEASE SEE 210.62 FOR REQUIRED |
| | SHOW/DISPLAY WINDOW RECEPTS REQUIRED. |
| | PLEASE ALSO SEE 220.12A |
| | AT LEAST ONE RECEPTACLE OUTLET SHALL BE |
| | INSTALLED DIRECTLY ABOVE A SHOW WINDOW |
| | FOR EACH 3.7 LINEAR M (12 FT) OR MAJOR |
| | FRACTION THEREOF OF SHOW WINDOW AREA |
| | MEASURED HORIZONTALLY AT ITS MAXIMUM |
| | WIDTH. |
| | FOR SHOW-WINDOW LIGHTING, A LOAD OF NOT |
| | LESS THAN 660 VOLT-AMPERES/LINEAR METER |
| | OR 200 VOLT-AMPERES/LINEAR FOOT SHALL BE |
| | INCLUDED FOR A SHOW WINDOW, MEASURED |
| | HORIZONTALLY ALONG ITS BASE. |
| | |
| | 6)NOTE: PLEASE SEE PANEL LOCATION ON |
| | PLANS DO NOT SEEM TO MEET 110.26 FOR |
| | CLEARENCE REQUIREMENTS. |
| | PLEASE ALSO SHOW LOCATION OF SERVICE ON |
| | PLANS. |
| | |
| | 7)NOTE: PLEASE CORRELATE A/C SYSTEMS ON |
| | MECH PLANS WITH ELECTRICAL PLANS. ONE |
| | SHOWS 5KW, THE OTHER 10KW?? |
| | 215.5 |
| | |
| | 8)NOTE: PLEASE SEE 600.5 |
| | EACH COMMERCIAL BUILDING AND EACH |
| | COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| | PEDESTRIANS SHALL BE PROVIDED WITH AT |
| | LEAST ONE OUTLET IN AN ACCESSIBLE |
| | LOCATION AT EACH ENTRANCE TO EACH TENANT |
| | SPACE FOR SIGN OR OUTLINE LIGHTING |
| | SYSTEM USE. THE OUTLET(S) SHALL BE |
| | SUPPLIED BY A BRANCH CIRCUIT RATED AT |
| | LEAST 20 AMPERES THAT SUPPLIES NO OTHER |
| | LOAD. |
| | |
| | 9)NOTE: PLEASE SEE 2002 NEC FOR GFI |
| | PROTECTION OF RECEPTS IN KITCHENS OTHER |
| | THAN DWELLING UNITS. 210.8B3 |
| | |
| | 10 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 11)NOTE: PLEASE PROVIDE NOTE ON |
| | ELECTRICAL PLANS FOR SHUT-DOWN OF ALL |
| | ELECTRICAL EQUIPMENT UNDER HOOD. |
| | NFPA-96 |
| | |
| | 12)NOTE: PLEASE INCLUDE SIZE OF |
| | EQUIPMENT GROUNDING CONDUCTOR FROM MAINS |
| | TO PANELS. SIZE PER 250.122 |
| | |
| | 13)NOTE: PLEASE INDICATE GFI RECEPT |
| | REQUIRED AT ROOFTOP LOCATION PERE |
| | 210.63 |
| | |
| | 14)NOTE: NOTE: PLEASE SUBMIT AIC RATINGS |
| | FOR ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALL- ED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT. PER 110.9/215.5 |
| | PROVIDE RATINGS/TYPE FUSE FOR MAINS. |
| | |
| | PLEASE SEE POSSIBLE REVIEW COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO TWO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |