| Plan Review Notes For Permit 04120193 |
| Permit Number |
04120193 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS, NOR DOES IT REFLECT | | | THE FLOOR PLAN. | | | A) DISHWASHER SHALL NOT CONNECT TO THE | | | BUILDING SANT. DRAIN. IT SHALL BE TIED | | | INTO THE TAILPIECE OF THE KITCHEN SINK | | | DRAIN UPSTREAM OF THE TRAP FOR THE | | | SINK. | | | B) THE WASH MACHINE IS NOT SHOWN ON THE | | | SANT. RISER DIAGRAM, A STANDPIPE IS | | | REQUIRED AND A CLEANOUT IS REQUIRED 4' | | | ABOVE THE FLOOR FOR ACCESS. SECTIONS | | | 104.2.1, 1002.1, 708.10. | | | C) THE BATHTUB REQUIRES A TRAP AND IS | | | NOT VENTED PIPED AS SHOWN, SECTION 902.1 | | | AND 1002.1. | | | D) TWO DISHWASHERS ARE SHOWN ON THE | | | SANT. RISER DIAGRAM. | | | 2) SEE ATTACHED SHEET FOR AN EXAMPLE OF | | | A SANT. RISER THAT MEETS CODE REQ. AND | | | REFLECT THE FLOOR PLAN. | | | 3)THE PERSONAL SIGNATUREAND THE DATE | | | THE PLANS ARE SIGNED AND SEALED ARE | | | REQUIRED. INITIALS ARE NOT ACCEPTABLE. | | | FAC 61G1-16.003, FS 481,2055. THIS IS | | | REQUIRED ON ALL SHEETS. | | | 4) A CERTIFICATE OF AUTHORIZATION IS | | | REQUIRED ON THE TITLE BLOCK PER FAC | | | 61G1-16.004(2) (FIRM LICENSE NUMBER) AND | | | FS 481.219 - THIS IS REQUIRED ON ALL | | | SHEETS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|