Plan Review Notes
Plan Review Notes For Permit 04120193
Permit Number 04120193
Review Stop P
Sequence Number 1
Notes
Date Text
2004-12-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS, NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) DISHWASHER SHALL NOT CONNECT TO THE
 BUILDING SANT. DRAIN. IT SHALL BE TIED
 INTO THE TAILPIECE OF THE KITCHEN SINK
 DRAIN UPSTREAM OF THE TRAP FOR THE
 SINK.
 B) THE WASH MACHINE IS NOT SHOWN ON THE
 SANT. RISER DIAGRAM, A STANDPIPE IS
 REQUIRED AND A CLEANOUT IS REQUIRED 4'
 ABOVE THE FLOOR FOR ACCESS. SECTIONS
 104.2.1, 1002.1, 708.10.
 C) THE BATHTUB REQUIRES A TRAP AND IS
 NOT VENTED PIPED AS SHOWN, SECTION 902.1
 AND 1002.1.
 D) TWO DISHWASHERS ARE SHOWN ON THE
 SANT. RISER DIAGRAM.
 2) SEE ATTACHED SHEET FOR AN EXAMPLE OF
 A SANT. RISER THAT MEETS CODE REQ. AND
 REFLECT THE FLOOR PLAN.
 3)THE PERSONAL SIGNATUREAND THE DATE
 THE PLANS ARE SIGNED AND SEALED ARE
 REQUIRED. INITIALS ARE NOT ACCEPTABLE.
 FAC 61G1-16.003, FS 481,2055. THIS IS
 REQUIRED ON ALL SHEETS.
 4) A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED ON THE TITLE BLOCK PER FAC
 61G1-16.004(2) (FIRM LICENSE NUMBER) AND
 FS 481.219 - THIS IS REQUIRED ON ALL
 SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]