Plan Review Notes
Plan Review Notes For Permit 04120193
Permit Number 04120193
Review Stop B
Sequence Number 1
Notes
Date Text
2004-12-22 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN
 AND DATE THE ENERGY CALCULATION FORM PER
 FBC CHAPTER 13.
  
 4) CITY OF WPB AMENDMENTS TO FBC
 2111.1.9 REQUIRES A 1.5 INCH RECESS
 WHERE EXTERIOR MASONRY WALLS BEAR ON A
 CONCRETE FLOOR SURFACE.
  
 5) FBC 1804.1.3 REQUIRES THE BOTTOM OF
 FOOTERS TO BE A MINIMUM OF 12" BELOW
 FINAL GRADE. SPECIFY ON PLANS.
  
 6) SPECIFY THE TRUSS CONNECTORS ON THE
 PLANS.
  
 7) SPECIFY THE WINDOW SIZES ON THE
 PLANS.
  
 8) SPECIFY THE NEGATIVE AND POSITIVE
 WINDLOAD PRESSURES FOR ALL EXTERIOR
 WINDOW AND DOOR OPENINGS.
  
 9) SAFETY GLAZING IS REQUIRED IN THE
 BATHROOM WINDOW AND WINDOWS WITH THE 8"
 SILL HEIGHT PER FBC 2405.2.1.
  
 10) BEDROOM WINDOWS ARE REQUIRED TO
 COMPLY WITH FBC 1005.4 FOR EMERGENCY
 EGRESS.
  
 11) GUTTER DOWNSPOUTS ARE REQUIRD TO
 DISCHARGE AT LEAST 12" AWAY FROM THE
 STRUCTURE PER FBC 1503.4.4.
  
 12) SPECIFY ON THE PLAN THE SLOPE OF THE
 BUILT UP FLAT ROOF. SEE FBC 1508.3.1 FOR
 MINIMUM PITCHES.
  
 13) SPECIFY THE LENGTH/EMBED DEPTH OF
 THE 3/4" EXPANSION BOLTS FASTENING THE
 TRUSS LEDGERS TO THE STRUCTURE.
  
 14) THE ENERGY CALC. FORM LISTS A
 CONCRETE ROOF DECK AND THE PLANS SPECIFY
 A PLYWOOD DECK. PLEASE CORRECT.
  
 15) FBC TABLE 600 IS USED TO DETERMINE
 THE PERCENTAGE OF WALL AREA ALLOWED AS
 OPENINGS BASED ON THE DISTANCE TO THE
 PROPERTY LINE OR ASSUMED PROPERTY LINE
 (WHEN TWO STRUCTURES ARE ON THE SAME
 PROPERTY). SPECIFY THE LOCATION OF THE
 ASSUMED PROPERTY LINE BETWEEN THE TWO
 STRUCTURES BASED ON THE OPENINGS IN THE
 EXISTING AND NEW STRUCTURES.
  
 16) SUBMIT 2 COPIES OF ALL PRODUCT
 APPROVALS.
  
 17) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 WWW.FLORIDABUILDING.ORG
  
 18) SUBMIT STATE/LOCAL PRODUCT APPROVALS
 FOR THE FOLLOWING:
 - ROOFING (OR SEPARATE PERMIT WILL BE
 REQUIRED)
 - TRUSS CONNECTORS
 - OUTSWING GLAZED DOORS (SINGLE AND
 DOUBLE WITH AND WITHOUT SIDELITES)
  
 19) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE FASTENERS, SPACING AND MOUNT TYPE
 THAT WILL BE USED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714