| Plan Review Notes For Permit 04120081 |
| Permit Number |
04120081 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-17 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE INDICATE IF THE ELECTRICAL | | | SERVICE IS NEW AND PART OF THE SCOPE OF | | | THIS APPLICATION. IF SO ADD TO | | | DESCRIPTION ON APPLICATION. | | | | | | 2} INDICATE THE SIZE OF THE GEC.INDICATE | | | THE GROUNDING SYSTEM IN COMPLIANCE WITH | | | 250.52 ALL, IF NEW SERVICE. | | | | | | 3} THE BATH CIRCUIT MUST COMPLY WITH | | | 210.11(C)(3). 20AMP WITH #12 WIRE. | | | | | | 4} PLEASE NOTE THAT PER CHAPTER 34 OF | | | THE FLORIDA BLDG CODE, SMOKE DETECTORS | | | AND GFI'S MUST BE BROUGHT TO CURRENT | | | CODE. | | | | | | 5} INCREASE THE VALUATION ON THE | | | APPLICATION PER 104.6.5.FBC PRIOR TO | | | RESUBMITTING ANY PLANS. | | | | | | | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|