| Plan Review Notes For Permit 04120069 |
| Permit Number |
04120069 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMGING | | | | | | 1) A WASHING MACHINE HOOK UP IS REQUIRED | | | PER TABLE 403.1 FOR EACH DWELLING. | | | PLEASE INDICATE THE LOCATION FOR THE | | | CONNECTION. SANITARY AND WATER. | | | 2) SHT A-1 DRAINAGE DIAGRAM. THE KITCHEN | | | SINK IS NOT SHOWN ON THE RISER DIAGRAM. | | | | | | THE WATER CLOSET SHALL NOT BE TRAPPED IN | | | THE SANT. PIPING AS THE FIXTURE HAS AN | | | INTEGRAL TRAP BUIILT INTO THE W/C. | | | SECTION 1002.1 | | | 3) INDICATE THE EXTENT OF THE PLUMBING | | | WORK BEING DONE. IF NEW SANITARY PIPING | | | UNDER THE SLAB, PLEASE INDICATE. IF | | | FIXTURE CHANGE-OUT PLEASE INDICATE. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|