| Plan Review Notes For Permit 04120064 |
| Permit Number |
04120064 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-29 00:00:00 | PLAN DENIED | | | 1) REFER TO SECTION 606.2.2 FBC (M) | | | COMMON SUPPLY,RETURN AIR AND SUPPLY | | | AIR. | | | 2) REFER TO SECYION 606.4.1 SUPERVISON | | | FBC(M) | | | 3) PLEASE SUPPLY INFORMATION ON GARAGE | | | WHAT WILL IT BE USED FOR. | | | 4) CAN NOT HAVE WORK ROOM IN RETURN AIR | | | PLENUM | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-6732 |
|