Plan Review Notes
Plan Review Notes For Permit 04120064
Permit Number 04120064
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-03 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE CLARIFY NEW OR EXISTING
 REQUIRED SIGN CIRCUIT PER 600.5
 PLEASE SEE EACH COMMERCIAL BUILDING AND
 EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT
 LEAST ONE OUTLET IN AN ACCESSIBLE
 LOCATION AT EACH ENTRANCE TO EACH
 TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING
 SYSTEM USE. THE OUTLET(S) SHALL BE
 SUPPLIED BY A BRANCH CIRCUIT RATED AT
 LEAST 20 AMPERES THAT SUPPLIES NO OTHER
 LOAD.
  
 2)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING INFORMATION ON TITLE BLOCKS FOR
 ENGINEER(S)/FIRM.
 FS 471.023
 PLEASE ALSO SEE FAC 61G1-16.004 FOR
 MISSING INFORMATION ON ARCH'S TITLE
 BLOCK.
 FS 481.219
 THIS IS REQUIRED ON ARCH AND ENG SHEETS
 AND OF ALL TRADES WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONE
 COPY/SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 *** PLEASE SEE THESE PLANS ARE IN FOR
 REVIEW ONLY AND HAVE NOT BEEN SUBMITTED
 FOR PERMIT. ****
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  