Plan Review Notes
Plan Review Notes For Permit 04120064
Permit Number 04120064
Review Stop B
Sequence Number 1
Notes
Date Text
2004-12-28 00:00:00****CORRECTIONS****
 ****PAID PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)CERTIFICATE OF AUTHORIZATION
 REQUIRED FOR ARCHITECT BUSINESS.
 INFORMATION REQUIRED BY FAC61G1-16.004
 IS TO BE ON THE TITLE BLOCK.
  
 2.)THE OCCUPANT LOAD PROVIDED F7-T1 IS
 NOT CONSISTENT WITH THE FLOOR PLAN A1.
 THE FLOOR PLAN DOES NOT SHOW AN OFFICE;
 SHOWS STORAGE AND A WORKROOM.REVISE SO
 THAT THE TWO ARE CONSISTENT AND PROVIDE
 OCCUPANCY SEPARATION AS NECESSARY
 FBC704.FBC 704.1.2.2(4) DOES NOT
 APPEAR TO APPLY EXEMPTING THE OCCUPANCY
 SEPARATION.
  
 3.)THE AREA CALCS ON F7-T1 APPEAR TO
 BE INCONSISTENT WITH THE FLOOR PLAN.IT
 SEEMS SHORT BY ABOUT 300SF.
  
 4.)WHAT WILL BE STORED IN THE STORAGE
 AREA?DECLARE S1 OR S2.
  