Plan Review Notes
Plan Review Notes For Permit 04120005
Permit Number 04120005
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-03 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SEE 210.52C1 FOR
 COUNTERSPACE RECEPTS.
  
 2)NOTE: PLEASE SEE 210.8A6, ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
  
 3)NOTE: PLEASE SEE FBC/WPB
 ADMINISTRATIVEAMENDMENTS. 104.2.1
 PLANS/DRAWINGS SHALL BEAR THE PRINTED
 NAME AND SIGNATURE OF PERSON RESPONSIBLE
 FOR DESIGN/ PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717