Plan Review Notes
Plan Review Notes For Permit 04111429
Permit Number 04111429
Review Stop P
Sequence Number 3
Notes
Date Text
2005-06-03 00:00:00DENIED;
 1.NOTE 1 NOT ADDRESSED,WATER AND SEWER
 PLAN CE-5 GREASE INTERCEPTOR CANNOT BE
 1600 GAL. SEE FBC PLUMBING SECTION
 1003.5(1200 GAL.MAX. THIRD
 NOTICE.PLEASE USE FBC PLUMBING TABLE
 1003.5.1 TO CALKULATE SIZE OF GREASE
 TRAP.
 2.NOTE 3 NOT ADDRESSED, PLEASE CONTACT
 RODNEY COMPO ENVIROMENT COMPLIANCE,
 FORAPPROVAL FOR GREASE TRAP. YOU CAN
 REACH RODNEY AT; [email protected], OR FAX
 (561)659-7458,
 OR CALL AT (561)659-4074.
 3.A/C CONDENSATE DRAINAGE MUST COMPLY TO
 FBC MECHANICAL SEC.307.2.1. (MUST GO TO
 STORM CATCH BASIN OR TO A DRYWELL.)
 4.2-WAY C.O. REQUIRED ON OUTLET SIDE OF
 GREASE TRAP.
 5.DWV ISOMETRIC,H/C LAVS. REQUIRE VENTS.
 6.SHOW TYPE OF PIPING MATERIAL BING
 INSTALLED AND METHOD.
 7.SHOW MANUFACTOR AND MODEL NUMBER OF
 REGULATORS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695