| Plan Review Notes For Permit 04111429 |
| Permit Number |
04111429 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-06-03 00:00:00 | DENIED; | | | 1.NOTE 1 NOT ADDRESSED,WATER AND SEWER | | | PLAN CE-5 GREASE INTERCEPTOR CANNOT BE | | | 1600 GAL. SEE FBC PLUMBING SECTION | | | 1003.5(1200 GAL.MAX. THIRD | | | NOTICE.PLEASE USE FBC PLUMBING TABLE | | | 1003.5.1 TO CALKULATE SIZE OF GREASE | | | TRAP. | | | 2.NOTE 3 NOT ADDRESSED, PLEASE CONTACT | | | RODNEY COMPO ENVIROMENT COMPLIANCE, | | | FORAPPROVAL FOR GREASE TRAP. YOU CAN | | | REACH RODNEY AT; [email protected], OR FAX | | | (561)659-7458, | | | OR CALL AT (561)659-4074. | | | 3.A/C CONDENSATE DRAINAGE MUST COMPLY TO | | | FBC MECHANICAL SEC.307.2.1. (MUST GO TO | | | STORM CATCH BASIN OR TO A DRYWELL.) | | | 4.2-WAY C.O. REQUIRED ON OUTLET SIDE OF | | | GREASE TRAP. | | | 5.DWV ISOMETRIC,H/C LAVS. REQUIRE VENTS. | | | 6.SHOW TYPE OF PIPING MATERIAL BING | | | INSTALLED AND METHOD. | | | 7.SHOW MANUFACTOR AND MODEL NUMBER OF | | | REGULATORS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|