| 2005-06-01 00:00:00 | PROVISO:PLAN CHECK ONLY | | | 1.ADDITIONAL PERMITS REQUIRED FOR THE | | | HOOD, FIRE SUPPRESSION, AND WALK-IN | | | COOLERS. | | | | | | 2.PROVIDE MANUFACTURER'S CUT SHEETS | | | FOR THE WAL-IN COOLER. | | | | | | 3.PROVIDE DETAIL OF GREASE DUCT | | | LAYOUT.SHOW CLEARANCES TO | | | COMBUSTIBLES. | | | | | | 4.PROVIDE FPM IN THE GREASE DUCT. | | | SHOW COMPLAINCE WITH NFPA 96 & 2001 | | | FBC(M) CHAPTER 5. | | | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|