| Date |
Text |
| 2005-05-10 00:00:00 | ******** UNSAT 3RDREVIEW******** |
| | |
| | ** SWEET TOMATOES** |
| | PLANS SUBMITTED FOR PLAN REVIEW ONLY. |
| | NOT SUBMITTED FOR PERMIT AT THIS TIME. |
| | |
| | PLEASE SEE SOME OF THE COMMENTS FROM |
| | PREVIOUS TWO REVIEWS STILL NEED TO BE |
| | ADDRESSED. |
| | PLEASE SEE NOTES #'S: |
| | 2,8,AND 9. |
| | |
| | 2)NOTE: NOTE#2 NO, PLEASE SEE TITLE |
| | BLOCKS FOR ARCHITECTUAL FIRM STILL DOES |
| | NOT CONTAIN THE REQUIRED LICENSE |
| | INFORMAION AS REQUIRED UNDER FAC |
| | 61G1-16.004 AS "REQUIRED" PER "FLORIDA |
| | STATUES". FS 481.219 |
| | PLEASE SEE THIS INFORMATION IS REQUIRED |
| | FOR ALL SHEETS AND FOR ALL TRADES |
| | WHEATHER OR NOT COMMENTS ARE MADE BY |
| | OTHER REVIEWER(S). |
| | PLEASE SEE A -SHEETS, S- SHEETS ETC. |
| | |
| | 8)NOTE: NOTE#8 NO, PLEASE SEE RECEPTS |
| | HAVE NOW BEEN ADDED AND ARE OK, HOWEVER |
| | THESE WERE ADDED"BELOW" WINDOWS. |
| | PLEASE SEE THESE ARE REQUIRED "ABOVE" |
| | WINDOWS AS SHOWN. |
| | 210.62 |
| | |
| | 9)NOTE: NOTE#9 NO, PLEASE SEE PREVIOUS |
| | NOTES MENTIONED MANY ITEMS WHERE LOADS, |
| | EQUIPMENT PANELS ETC DID NOT CORRELATE |
| | ON RISERS OR PANELS OR EQUIPMENT |
| | SCHEDULE. |
| | PLEASE SEE MANY OF THESE ITEMS WERE |
| | REDLINED ON PLANS WHICH CAME THROUGH FOR |
| | REVIEW AND NOT EACH AND EVERY ITEM WAS |
| | TYPED INTO NOTES. |
| | PLEASE SEE MANY ITEMS HAVE BEEN |
| | CORRECTED , HOWEVER PLEASE SEE THERE ARE |
| | A SOME WHICH STILL NEED TO BE ADDRESSED. |
| | 1) PLEASE SEE CU-15 ON EQUIPMENT |
| | SCHEDULE, HOWEVER CU-20 ON PANEL LD? |
| | PLEASE SEE LOAD SHOWN ON LD DOES NOT |
| | CORRELATE WITH EQUIPMNET SCHEDULE OR |
| | RISER DIAGRAM. 81A;S SHOWN ON TWO AND |
| | 64A'S SHOWN ON LD. |
| | 2) PLEASE SEE LOAD SHOWN ON LD FOR PANEL |
| | "A". THIS DOES NOT CORRELATE WITH LOAD |
| | ON PANEL "A". |
| | 3)PLEASE SEE LOAD CALCULATIONS DO NOT |
| | CORRELATE WITH LOAD SHOWN ON PANEL "LD". |
| | 4)PLEASE SEE AIC RATING OF PANEL "C" IS |
| | SHOWN AS 10K, HOWEVER RISER SHOWS 31,532 |
| | AVAILABLE. |
| | |
| | PLEASE SEE THE ABOVE COMMENTS. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |