Plan Review Notes
Plan Review Notes For Permit 04111429
Permit Number 04111429
Review Stop E
Sequence Number 3
Notes
Date Text
2005-05-10 00:00:00******** UNSAT 3RDREVIEW********
  
 ** SWEET TOMATOES**
 PLANS SUBMITTED FOR PLAN REVIEW ONLY.
 NOT SUBMITTED FOR PERMIT AT THIS TIME.
  
 PLEASE SEE SOME OF THE COMMENTS FROM
 PREVIOUS TWO REVIEWS STILL NEED TO BE
 ADDRESSED.
 PLEASE SEE NOTES #'S:
 2,8,AND 9.
  
 2)NOTE: NOTE#2 NO, PLEASE SEE TITLE
 BLOCKS FOR ARCHITECTUAL FIRM STILL DOES
 NOT CONTAIN THE REQUIRED LICENSE
 INFORMAION AS REQUIRED UNDER FAC
 61G1-16.004 AS "REQUIRED" PER "FLORIDA
 STATUES". FS 481.219
 PLEASE SEE THIS INFORMATION IS REQUIRED
 FOR ALL SHEETS AND FOR ALL TRADES
 WHEATHER OR NOT COMMENTS ARE MADE BY
 OTHER REVIEWER(S).
 PLEASE SEE A -SHEETS, S- SHEETS ETC.
  
 8)NOTE: NOTE#8 NO, PLEASE SEE RECEPTS
 HAVE NOW BEEN ADDED AND ARE OK, HOWEVER
 THESE WERE ADDED"BELOW" WINDOWS.
 PLEASE SEE THESE ARE REQUIRED "ABOVE"
 WINDOWS AS SHOWN.
 210.62
  
 9)NOTE: NOTE#9 NO, PLEASE SEE PREVIOUS
 NOTES MENTIONED MANY ITEMS WHERE LOADS,
 EQUIPMENT PANELS ETC DID NOT CORRELATE
 ON RISERS OR PANELS OR EQUIPMENT
 SCHEDULE.
 PLEASE SEE MANY OF THESE ITEMS WERE
 REDLINED ON PLANS WHICH CAME THROUGH FOR
 REVIEW AND NOT EACH AND EVERY ITEM WAS
 TYPED INTO NOTES.
 PLEASE SEE MANY ITEMS HAVE BEEN
 CORRECTED , HOWEVER PLEASE SEE THERE ARE
 A SOME WHICH STILL NEED TO BE ADDRESSED.
 1) PLEASE SEE CU-15 ON EQUIPMENT
 SCHEDULE, HOWEVER CU-20 ON PANEL LD?
 PLEASE SEE LOAD SHOWN ON LD DOES NOT
 CORRELATE WITH EQUIPMNET SCHEDULE OR
 RISER DIAGRAM. 81A;S SHOWN ON TWO AND
 64A'S SHOWN ON LD.
 2) PLEASE SEE LOAD SHOWN ON LD FOR PANEL
 "A". THIS DOES NOT CORRELATE WITH LOAD
 ON PANEL "A".
 3)PLEASE SEE LOAD CALCULATIONS DO NOT
 CORRELATE WITH LOAD SHOWN ON PANEL "LD".
 4)PLEASE SEE AIC RATING OF PANEL "C" IS
 SHOWN AS 10K, HOWEVER RISER SHOWS 31,532
 AVAILABLE.
  
 PLEASE SEE THE ABOVE COMMENTS.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  