| 2005-03-12 00:00:00 | 1.WATER AND SEWER PLAN CE-5 GREASE |
| | INTERCEPTOR CANNOT BE 1600 GAL SEE FBC |
| | PLUMBING SEC. 1003.51250 GAL MAX. SECOND |
| | NOTICE. |
| | 2.PLANS MUST BE REVIEW BY DEPTMENT OF |
| | HOTEL AND RESTURANTS BEFORE PLAN REVIEW |
| | BY WPB. SECOND NOTICE. |
| | 3.NO APPROVAL HAS BEEN RECIEVED FROM |
| | UTILITY DEPARTMENT FOR GREASE INTERCETOR |
| | 2ND NOTICE. |
| | 4.SECONDARY ROOF DRAINS ARE NOT TO CODE |
| | SEE SEC. 1106. |
| | 5.RAINWATER LEADERS MUST TIE INTO CATCH |
| | BASINS NOT TO PLASH BLOCKS. MUST RETAIN |
| | FIRST INCH. OF RAIN ON PROPERTY. |
| | 6.VENT FROM GREASE INTERCEPTOR NOT |
| | REQUIRED AND IS A CODE VIOLATION NO |
| | HORIZONTAL DRY VENTS. |
| | 7.CONDENSATE FROM A/C UNITS ON ROOF GO |
| | TO STORM SEWER NOT SANITARY SEWER. |
| | UTILITY DEPARTMENT ORD. |
| | 8GW FIRST TWO FIXTURES ARE NOT VENTED, |
| | FLOOR SINK AND FLOOR DRAIN. |
| | 9.INDIRECT WASTES TO GO TO FLOOR SINKS |
| | NOT FLOOR DRAINS. |
| | 10.PLEASE SUBMIT MANUFACTORS SPECS. FOR |
| | REGULATORS. |
| | 11.SHUTOFF VALVES TO BE INSTALLED BEFORE |
| | REGULATORS WITH UNION AFTER REGULATOR |
| | FOR REPLACEMENT IF NEEDED. |
| | 12.INSTALL A UNION AT EMERGENCY SHUTOFF |
| | VALVE FOR REPLACEMENT IF NEEDED. |
| | 13.PLEASE LIST COOKING EQUIPMENT BTU'S |
| | ON SAME PAGE AS RISER DIAGRAM AND TOTAL |
| | BTU'S SO I CAN CHECK PIPE SIZING. |
| | PLUMBING PLAN REVIEW BY; |
| | JOHN LEECH |
| | 805-6695 |
| | |