Plan Review Notes
Plan Review Notes For Permit 04111429
Permit Number 04111429
Review Stop P
Sequence Number 2
Notes
Date Text
2005-03-12 00:00:001.WATER AND SEWER PLAN CE-5 GREASE
 INTERCEPTOR CANNOT BE 1600 GAL SEE FBC
 PLUMBING SEC. 1003.51250 GAL MAX. SECOND
 NOTICE.
 2.PLANS MUST BE REVIEW BY DEPTMENT OF
 HOTEL AND RESTURANTS BEFORE PLAN REVIEW
 BY WPB. SECOND NOTICE.
 3.NO APPROVAL HAS BEEN RECIEVED FROM
 UTILITY DEPARTMENT FOR GREASE INTERCETOR
 2ND NOTICE.
 4.SECONDARY ROOF DRAINS ARE NOT TO CODE
 SEE SEC. 1106.
 5.RAINWATER LEADERS MUST TIE INTO CATCH
 BASINS NOT TO PLASH BLOCKS. MUST RETAIN
 FIRST INCH. OF RAIN ON PROPERTY.
 6.VENT FROM GREASE INTERCEPTOR NOT
 REQUIRED AND IS A CODE VIOLATION NO
 HORIZONTAL DRY VENTS.
 7.CONDENSATE FROM A/C UNITS ON ROOF GO
 TO STORM SEWER NOT SANITARY SEWER.
 UTILITY DEPARTMENT ORD.
 8GW FIRST TWO FIXTURES ARE NOT VENTED,
 FLOOR SINK AND FLOOR DRAIN.
 9.INDIRECT WASTES TO GO TO FLOOR SINKS
 NOT FLOOR DRAINS.
 10.PLEASE SUBMIT MANUFACTORS SPECS. FOR
 REGULATORS.
 11.SHUTOFF VALVES TO BE INSTALLED BEFORE
 REGULATORS WITH UNION AFTER REGULATOR
 FOR REPLACEMENT IF NEEDED.
 12.INSTALL A UNION AT EMERGENCY SHUTOFF
 VALVE FOR REPLACEMENT IF NEEDED.
 13.PLEASE LIST COOKING EQUIPMENT BTU'S
 ON SAME PAGE AS RISER DIAGRAM AND TOTAL
 BTU'S SO I CAN CHECK PIPE SIZING.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  