| 2005-03-31 00:00:00 | DENIED:PLAN CHECK ONLY |
| | 1.2ND REQUEST - PROVIDE ENERGY AND |
| | MANUAL J CALCULATIONS IN ACCORDANCE WITH |
| | 2001 FBC CHAPTER 13 SUB-CHAPTER 4. |
| | |
| | 2.2ND REQUEST - PROVIDE OUTSIDE AIR |
| | CALCULATIONS PER 2001 FBC/M TABLE 403.3. |
| | |
| | 3.2ND REQUEST - PROVIDE RETURN AIR |
| | FROM THE OFFICE AREA. SHOW COMPLIANCE |
| | WITH 2001 FBC/M 601.4. |
| | |
| | 4.2ND REVIEW ADDTIONAL COMMENT FOR THE |
| | CONDENSATE.CONDENSATE TO TERMINATE |
| | INTO THE STORM SEWER AND NOT THE |
| | SANITARY PER CITY COD SEC. 90-125 (5). |
| | |
| | 5.2ND REQUEST - HOOD & FIRE |
| | SUPPRESSION PLANS ARE PROVIDED BY THE |
| | ENGINEER (PLAN SHEET M2.1) AND ALSO BY |
| | CAPTIVEAIRE (PLAN SHEET K7.0).PLEASE |
| | CLARIFY IF THE MECHANICAL ENGINEER WILL |
| | BE DESIGNING THE HOOD SYSTEM OR |
| | CAPTIVEAIRE.PLEASE NOTE, SHOULD |
| | CAPTIVEAIRE PLAN BE USED, PLANS SHALL BE |
| | SIGNED & DATED BY THE DESIGNER. |
| | |
| | 6.NEW COMMENT - PLAN SHEET M2.1 DETAIL |
| | #2 CONDENSATE UNIT CURB.DETAIL DOES |
| | NOT INDICATE ANCHORING OR TIE DOWN FOR |
| | THE CONDENSING UNIT TO THE CURB.PLEASE |
| | NOTE, CURBS ARE TO BE A MINIMUM OF 8" |
| | ABOVE THE ROOF SURFACE PER 2001 FBC |
| | 1511.7. |
| | |
| | SEE COMMENT #2 BY DEWEY PALMER, |
| | ELECTRICAL PLAN REVIEW. |
| | |