2005-03-31 00:00:00DENIED:PLAN CHECK ONLY
 1.2ND REQUEST - PROVIDE ENERGY AND
 MANUAL J CALCULATIONS IN ACCORDANCE WITH
 2001 FBC CHAPTER 13 SUB-CHAPTER 4.
  
 2.2ND REQUEST - PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC/M TABLE 403.3.
  
 3.2ND REQUEST - PROVIDE RETURN AIR
 FROM THE OFFICE AREA. SHOW COMPLIANCE
 WITH 2001 FBC/M 601.4.
  
 4.2ND REVIEW ADDTIONAL COMMENT FOR THE
 CONDENSATE.CONDENSATE TO TERMINATE
 INTO THE STORM SEWER AND NOT THE
 SANITARY PER CITY COD SEC. 90-125 (5).
  
 5.2ND REQUEST - HOOD & FIRE
 SUPPRESSION PLANS ARE PROVIDED BY THE
 ENGINEER (PLAN SHEET M2.1) AND ALSO BY
 CAPTIVEAIRE (PLAN SHEET K7.0).PLEASE
 CLARIFY IF THE MECHANICAL ENGINEER WILL
 BE DESIGNING THE HOOD SYSTEM OR
 CAPTIVEAIRE.PLEASE NOTE, SHOULD
 CAPTIVEAIRE PLAN BE USED, PLANS SHALL BE
 SIGNED & DATED BY THE DESIGNER.
  
 6.NEW COMMENT - PLAN SHEET M2.1 DETAIL
 #2 CONDENSATE UNIT CURB.DETAIL DOES
 NOT INDICATE ANCHORING OR TIE DOWN FOR
 THE CONDENSING UNIT TO THE CURB.PLEASE
 NOTE, CURBS ARE TO BE A MINIMUM OF 8"
 ABOVE THE ROOF SURFACE PER 2001 FBC
 1511.7.
  
 SEE COMMENT #2 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.
  