2005-03-03 00:00:00********* UNSAT 2ND REVIEW ************
  
  
 ******** SWEET TOMATOES REST *********
 PLAN REVIEW ONLY, NOT SUBMITTED FOR
 PERMIT AT THIS TIME.
  
 PLEASE SEE THERE ARE MANY ITEMS FROM
 PREVIOUS REVIEW WHICH STILL NEED TO BE
 ADDRESSED.
  
  
 1)NOTE: NOTE #1 NO, IF PLANS WERE READY
 FOR PERMITTING, THIS WOULD NOT BE ABLE
 TO BE STAMPED AND PROCESSED DUE TO PLANS
 NOT BEING SIGNED, DATED AND SEALED BY
 ARCHITECT/ ENGINEER(S).
 PLEASE SEE FS 481.221,471.025
 PLANS ARE REQUIRED TO HAVE RAISED SEAL,
 SIGNATURE AND DATED.
 **PLEASE SEE ARCH SHEET CONTAINS A
 "RUBBER STAMP" FOR SEAL.
  
 2)NOTE: NOTE #2 NO,
 PLEASE SEE PREVIOUS NOTES: PLEASE SEE
 FAC 61G15-23.002, 61G1-16.004 FOR ALL
 INFORMATION REQUIRED ON TITLE BLOCKS FOR
 " ALL"SHEETS. REQUIRED UNDER FS
 471.023,481.219.
 PLEASE SEE MISSING LICENSE INFORMATION
 ON "S" SHEETS , "A" SHEETS AND ALL
 "P","M", AND "E" SHEETS.
 THE ABOVE COMMENT IS FOR ALL SHEETS AND
 FOR ALL TRADES WHEATHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWERS.
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 MOST, PLEASE SEE CIRCUIT
 B-16.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 MOST, PLEASE SEE LARGEST
 MOTOR LOADS (RTU) IS REQUIRED TO BE
 SHOWN AT 125%.
  
 8)NOTE: NOTE #8 NO, PLEASE SEE "ABOVE
 WINDOW RECEPTS" COULD NOT BE LOCATED.
 210.62 THIS IS TO ALLEVIATE UNSIGHTLY
 EXTENSION CORDS LIKELY TO CAUSE PHYSICAL
 INJURY. MANY TIMES SIGNAGE SUCH AS ONES
 FROM "VENDORS" ETC ARE INSTALLED IN
 WINDOW AREAS ETC. THE RECEPTACLES MUST
 BE INSTALLED DIRECTLY ABOVE A SHOW
 WINDOW, AND ONE RECEPTACLE IS REQUIRED
 FOR EVERY 12 LINEAR FT OR ?MAJOR
 FRACTION THEREOF? (6 FT OR MORE). SEE
 220.3(B)(7) AND 220.12(A) FOR
 INFORMATION REGARDING LOAD COMPUTATIONS
 FOR SHOW WINDOWS.
  
 9)NOTE: NOTE #9 NO,
 PLEASE SEE OCPFOR RTUS',125% ETC,
 PLEASE CORRELATE "LD" OCP WITH RISER AND
 EQUIPMENT SCHEDULE.
 PLEASE ALSO CORRELATE PANELS/ OCP AND
 RISER.
 PLEASE SEE "LD" IS SHOWN AS 1000A'S AND
 RISER SHOWS 1200A'S?
 PLEASE SEENOTE #15.
 PLEASE SEE SALAD BAR ON RISER SHOWS 150A
 BRKR ON #10 AWG.
 PLEASE SEE PANEL "C", 400A'S WITH A 200A
 BRKR AS FEED??
 ETC.
  
 10)NOTE: NOTE #10 OK, HOWEVER SEE
 PREVIOUS NOTE.
  
 11)NOTE: NOTE #11 NO, PLEASE SEE 424.3B
 AND PLEASE SEE NOTE #9.
  
 12)NOTE: NOTE #12 OK.
  
 13)NOTE: NOTE #13 NO, PLEASE SEE THERE
 IS EQUIPMENT SHOWN ON "EQUIPMENT
 SCHEDULE" BUT NOT LOCATED ON ANY PANEL
 SCHEDULE. PLEASE SEE EQUIPMENT ON PANEL
 SCHEDULES, BUT NOT ON EQUIPMENT
 SCHEDULE?
 WATER HEATER #2?
  
 14)NOTE: NOTE #14 OK, HOWEVER, NOW AN
 EQUIPMENT GROUNDING CONDUCTOR IS NOW
 SHOWN WITH SEC'S. PLEASE SEE
 250.6,250.24, EQUIIPMENT GROUNDING
 CONDUCTORS ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
 THIS WAS NOT IN FIRST REVIEW AS SEC'S
 WERE NOT SHOWN.
  
 15)NOTE: NOTE #15 OK.
  
 16)NOTE: NOTE #16 SEC'S ADDED, HOWEVER
 PLEASE SEE MIN SIZE REQUIRED PER 240.3,
 AND 310.16.
 PLEASE SEE DEVICES WHICH ARE RATED OVER
 800A'S THE AMPACITY OF THE CONDUCTORS IT
 PROTECTS SHALL BE EQUAL TO OR GREATER
 THAN THE RATING OF THE OVERCURRENT
 DEVICE DEFINED IN 240.6.
 PLEASE SEE NOTE #9.
  
 ****************************************
  
 PLEASE SEE NOTE #2 ON THIS AND PREVIOUS
 REVIEW.
 ***************************************
  
 PLEASE SEE ONE SETOF PLANS HAVE BEEN
 REDLINED FOR ITMES AS NOTED IN REVIEW.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  