| 2005-03-03 00:00:00 | ********* UNSAT 2ND REVIEW ************ |
| | |
| | |
| | ******** SWEET TOMATOES REST ********* |
| | PLAN REVIEW ONLY, NOT SUBMITTED FOR |
| | PERMIT AT THIS TIME. |
| | |
| | PLEASE SEE THERE ARE MANY ITEMS FROM |
| | PREVIOUS REVIEW WHICH STILL NEED TO BE |
| | ADDRESSED. |
| | |
| | |
| | 1)NOTE: NOTE #1 NO, IF PLANS WERE READY |
| | FOR PERMITTING, THIS WOULD NOT BE ABLE |
| | TO BE STAMPED AND PROCESSED DUE TO PLANS |
| | NOT BEING SIGNED, DATED AND SEALED BY |
| | ARCHITECT/ ENGINEER(S). |
| | PLEASE SEE FS 481.221,471.025 |
| | PLANS ARE REQUIRED TO HAVE RAISED SEAL, |
| | SIGNATURE AND DATED. |
| | **PLEASE SEE ARCH SHEET CONTAINS A |
| | "RUBBER STAMP" FOR SEAL. |
| | |
| | 2)NOTE: NOTE #2 NO, |
| | PLEASE SEE PREVIOUS NOTES: PLEASE SEE |
| | FAC 61G15-23.002, 61G1-16.004 FOR ALL |
| | INFORMATION REQUIRED ON TITLE BLOCKS FOR |
| | " ALL"SHEETS. REQUIRED UNDER FS |
| | 471.023,481.219. |
| | PLEASE SEE MISSING LICENSE INFORMATION |
| | ON "S" SHEETS , "A" SHEETS AND ALL |
| | "P","M", AND "E" SHEETS. |
| | THE ABOVE COMMENT IS FOR ALL SHEETS AND |
| | FOR ALL TRADES WHEATHER OR NOT COMMENT |
| | IS MADE BY OTHER REVIEWERS. |
| | |
| | 3)NOTE: NOTE #3 OK. |
| | |
| | 4)NOTE: NOTE #4 OK. |
| | |
| | 5)NOTE: NOTE #5 MOST, PLEASE SEE CIRCUIT |
| | B-16. |
| | |
| | 6)NOTE: NOTE #6 OK. |
| | |
| | 7)NOTE: NOTE #7 MOST, PLEASE SEE LARGEST |
| | MOTOR LOADS (RTU) IS REQUIRED TO BE |
| | SHOWN AT 125%. |
| | |
| | 8)NOTE: NOTE #8 NO, PLEASE SEE "ABOVE |
| | WINDOW RECEPTS" COULD NOT BE LOCATED. |
| | 210.62 THIS IS TO ALLEVIATE UNSIGHTLY |
| | EXTENSION CORDS LIKELY TO CAUSE PHYSICAL |
| | INJURY. MANY TIMES SIGNAGE SUCH AS ONES |
| | FROM "VENDORS" ETC ARE INSTALLED IN |
| | WINDOW AREAS ETC. THE RECEPTACLES MUST |
| | BE INSTALLED DIRECTLY ABOVE A SHOW |
| | WINDOW, AND ONE RECEPTACLE IS REQUIRED |
| | FOR EVERY 12 LINEAR FT OR ?MAJOR |
| | FRACTION THEREOF? (6 FT OR MORE). SEE |
| | 220.3(B)(7) AND 220.12(A) FOR |
| | INFORMATION REGARDING LOAD COMPUTATIONS |
| | FOR SHOW WINDOWS. |
| | |
| | 9)NOTE: NOTE #9 NO, |
| | PLEASE SEE OCPFOR RTUS',125% ETC, |
| | PLEASE CORRELATE "LD" OCP WITH RISER AND |
| | EQUIPMENT SCHEDULE. |
| | PLEASE ALSO CORRELATE PANELS/ OCP AND |
| | RISER. |
| | PLEASE SEE "LD" IS SHOWN AS 1000A'S AND |
| | RISER SHOWS 1200A'S? |
| | PLEASE SEENOTE #15. |
| | PLEASE SEE SALAD BAR ON RISER SHOWS 150A |
| | BRKR ON #10 AWG. |
| | PLEASE SEE PANEL "C", 400A'S WITH A 200A |
| | BRKR AS FEED?? |
| | ETC. |
| | |
| | 10)NOTE: NOTE #10 OK, HOWEVER SEE |
| | PREVIOUS NOTE. |
| | |
| | 11)NOTE: NOTE #11 NO, PLEASE SEE 424.3B |
| | AND PLEASE SEE NOTE #9. |
| | |
| | 12)NOTE: NOTE #12 OK. |
| | |
| | 13)NOTE: NOTE #13 NO, PLEASE SEE THERE |
| | IS EQUIPMENT SHOWN ON "EQUIPMENT |
| | SCHEDULE" BUT NOT LOCATED ON ANY PANEL |
| | SCHEDULE. PLEASE SEE EQUIPMENT ON PANEL |
| | SCHEDULES, BUT NOT ON EQUIPMENT |
| | SCHEDULE? |
| | WATER HEATER #2? |
| | |
| | 14)NOTE: NOTE #14 OK, HOWEVER, NOW AN |
| | EQUIPMENT GROUNDING CONDUCTOR IS NOW |
| | SHOWN WITH SEC'S. PLEASE SEE |
| | 250.6,250.24, EQUIIPMENT GROUNDING |
| | CONDUCTORS ARE ONLY INSTALLED AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | THIS WAS NOT IN FIRST REVIEW AS SEC'S |
| | WERE NOT SHOWN. |
| | |
| | 15)NOTE: NOTE #15 OK. |
| | |
| | 16)NOTE: NOTE #16 SEC'S ADDED, HOWEVER |
| | PLEASE SEE MIN SIZE REQUIRED PER 240.3, |
| | AND 310.16. |
| | PLEASE SEE DEVICES WHICH ARE RATED OVER |
| | 800A'S THE AMPACITY OF THE CONDUCTORS IT |
| | PROTECTS SHALL BE EQUAL TO OR GREATER |
| | THAN THE RATING OF THE OVERCURRENT |
| | DEVICE DEFINED IN 240.6. |
| | PLEASE SEE NOTE #9. |
| | |
| | **************************************** |
| | |
| | PLEASE SEE NOTE #2 ON THIS AND PREVIOUS |
| | REVIEW. |
| | *************************************** |
| | |
| | PLEASE SEE ONE SETOF PLANS HAVE BEEN |
| | REDLINED FOR ITMES AS NOTED IN REVIEW. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |