2005-01-06 00:00:00DENIED;
 PLANS MUST BE REVIEW BY THE DEPARTMENT
 OF HOTEL AND RESTAURANTS BEFORE PLAN
 REVIEW BY THE CITY OF WEST PALM BEACH.
 GREASE TRAP; PAGE CE-5, FBC PLUMBING SEC
 1003.5 THE LARGEST TANK PERMITED IS 1250
 GAL. GREASE TANKS CAN BE INSTALLED IN
 SERIES. SITE PLANS CALL FOR 1600 GAL
 CALCULATIONS ON PLUMBING PAGES INDICATE
 A 2000 GAL. REQUIRED. ALSO GREASE TRAPS
 MUST BE APPROVED BY THE UTILITY
 DEPARTMENT.CONTACT RODNEY COMPO AT
 561-837-4074.
 RISER DIAGRAMS REQUIRED FOR WARER,
 SANITARY, GREASY WASTE, RAINWATER.
 SIZE RAIN WATER PIPING USING CHAPTER 11
 OF THE FBC PLUMBING
 PLEASE SIZE EMERGENCY OVERFLOW
 SCUPPERS.
 GAS;
 ISOMETRIC TO CLEARLY SHOW ALL CUT
 SECTIONS OF PIPE AND CORRESPONDING
 LEAGHS PER FBC FUEL GAS.
 CUT SHEETS REQURED FOR REGULATORS.
 SHUTOFF VALVES REQUIRED UP STREAM OF
 REGULATORS AND EMERGENCY HOOD SHUTOFF
 FOR REPAIR PURPOSES.
 GAS RISER DIAGRAM PAGE P2.3. PIPE FROM
 METER TO FIRST TEE NOT SIZED. PIPE FROM
 WARER HEATER TEE TO ROOF RISER TEE NOT
 SIZED. PLEASE USE FBC FUEL GAS TO SIZE
 ALL GAS PIPE TABLES ARE IN CHAPTER 4.
 PLUMBING PLANREVIEW BY
 JOHN LEECH
 805-6695