| 2005-01-06 00:00:00 | DENIED; |
| | PLANS MUST BE REVIEW BY THE DEPARTMENT |
| | OF HOTEL AND RESTAURANTS BEFORE PLAN |
| | REVIEW BY THE CITY OF WEST PALM BEACH. |
| | GREASE TRAP; PAGE CE-5, FBC PLUMBING SEC |
| | 1003.5 THE LARGEST TANK PERMITED IS 1250 |
| | GAL. GREASE TANKS CAN BE INSTALLED IN |
| | SERIES. SITE PLANS CALL FOR 1600 GAL |
| | CALCULATIONS ON PLUMBING PAGES INDICATE |
| | A 2000 GAL. REQUIRED. ALSO GREASE TRAPS |
| | MUST BE APPROVED BY THE UTILITY |
| | DEPARTMENT.CONTACT RODNEY COMPO AT |
| | 561-837-4074. |
| | RISER DIAGRAMS REQUIRED FOR WARER, |
| | SANITARY, GREASY WASTE, RAINWATER. |
| | SIZE RAIN WATER PIPING USING CHAPTER 11 |
| | OF THE FBC PLUMBING |
| | PLEASE SIZE EMERGENCY OVERFLOW |
| | SCUPPERS. |
| | GAS; |
| | ISOMETRIC TO CLEARLY SHOW ALL CUT |
| | SECTIONS OF PIPE AND CORRESPONDING |
| | LEAGHS PER FBC FUEL GAS. |
| | CUT SHEETS REQURED FOR REGULATORS. |
| | SHUTOFF VALVES REQUIRED UP STREAM OF |
| | REGULATORS AND EMERGENCY HOOD SHUTOFF |
| | FOR REPAIR PURPOSES. |
| | GAS RISER DIAGRAM PAGE P2.3. PIPE FROM |
| | METER TO FIRST TEE NOT SIZED. PIPE FROM |
| | WARER HEATER TEE TO ROOF RISER TEE NOT |
| | SIZED. PLEASE USE FBC FUEL GAS TO SIZE |
| | ALL GAS PIPE TABLES ARE IN CHAPTER 4. |
| | PLUMBING PLANREVIEW BY |
| | JOHN LEECH |
| | 805-6695 |