Plan Review Notes
Plan Review Notes For Permit 04111429
Permit Number 04111429
Review Stop M
Sequence Number 1
Notes
Date Text
2005-01-03 00:00:00DENIED:
 1.PROVIDE ENERGY AND MANUAL J
 CALCULATIONS AS REQUIRED PER 2001 FBC
 CHAPTER 13 SUB-CHAPTER 4.
  
 2.PROVIDE MANUFACTURER SUBMITTAL &
 INSTALLATION INSTRUCTIONS FOR THE
 KITCHEN EQUIPMENT AND THE FIREPLACE.
  
 3.ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD, FIRE SUPPRESSION, WALK-IN
 COOLERS,
 AND GAS.
  
 4.PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC(M) TABLE
 403.3.
  
 5.RETURN AIR REQUIRED FROM ROOMS
 SEPARATED FROM THE CENTRALLY LOCATED
 RETURN AIR I.E., OFFICE AREA, LOCKER
 ROOM.2001 FBC(M)601.4.
  
 6.PROVIDE CONDENSATE LAYOUT &
 TERMINATION.
  
 7.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO A/ARM/STROBE
 REQUIRED PER 2001 FBC(M)606.2.1 &
 606.4.1 #2.
  
 HOOD/FIRE SUPPRESSION:
 PLEASE NOTE, PLANS SUBMITTED BY CAPTIVE
 AIR (K-7 & K-8) DO NOT HAVE ENOUGH
 DETAIL FOR A COMPLETE REVIEW.
 HOOD/SUPPRESSION PLANS ARE ALSO
 SUBMITTED BY THE MECHANICAL ENGINEER
 WHICH ARE MORE SPECIFIC.PLEASE
 PROVIDE
 THE FOLLOWING INFORMATION:
 1) PLAN SHEET M2.1 DETAIL #13, PROVIDE
 DETAIL FOR SPECFIC INSTALLATION AS
 SHOWN
 ON DETAIL #22.
 2) AIR VELOCITY WITHIN THE GREASE DUCT
 SYSTEM SHALL BE NOT LESS THAN 1,500 FPM
 & NOT GREATER THAN 2,500 FPM.
 3) FIRE MASTER DUCT WRAP INDICATED ON
 DETAIL 8, MANUFACTURER'S INSTALLATION
 INSTRUCTIONS SHALL BE ON THE JOBSITE AT
 THE TIME OF INSPECTION.
 4) PLAN REVIEW FOR THE HOOD & FIRE
 SUPPRESSION CAN BE APPROVED WITH THE
 BUILDING REVIEW OR PLANS MAY BE
 SUBMITTED AND REVIEWED AT THE TIME OF
 SUBMITTAL FOR THE HOOD/SUPPRESSION
 PERMITS.PLEASE DO NOT SUBMIT PLANS BY
 TWO DIFFERENT ENGINEERS.
  
 PLANS, SPECIFICATIONS AND REPORTS ARE TO
 BE SIGNED, SEALED AND DATED BY THE
 ARCHITECT/ENGINEER RESPONSIBLE FOR THE
 DESIGN PER FS 481.221, 471.025.PLANS
 SHALL ALSO COMPLY WITH 61G5-23.0002 &
 61G1-16.004.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved