Plan Review Notes
Plan Review Notes For Permit 04111429
Permit Number 04111429
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-12-27 00:00:001. ALL DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH
 NFPA 241.
  
 2. WHAT PROVISIONS MADE FOR FIRE
 AND PARAMEDICAL ACCESS THRU THE
 SLIDING GATE.
  
 3. FLORIDA FIRE PREVENTION CODE
 NOT MENTIONED IN CODE COMPLIANCE
 BOX.
  
 4. GENERAL NOTES AND CODE COMPLIANCE
 BOX WITH REGARDS TO FIRE SPRINKLERS
 DO NOT MATCH.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY HOOD, DUCT, AND FIRE
 SUPPRESSION SYSTEMS.
  
 6. HOW ARE PERSONS DIRECTED TO EXIT
 DOOR IN ENTRY AREA 100.
  
 7. NO EMERGENCY LIGHTING COULD BE
 LOCATED IN THE KITCHEN. WHAT DIRECTS
 PERSONS TO THE EXITS SHOULD POWER
 FAIL.
  
 8. PLEASE PROVIDE PRODUCT APPROVALS FOR
 GREASE DUCT WRAP.
  
 9. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 10. EXIT SIGN MISSING FROM REFLECTED
 CEILING PLAN ENTRY 100.
  
 11. PANIC HARDWARE REQUIRED ON ALL
 EXIT DOORS.
  
 12. BUILDING MAY BE LOCATED IN CITY
 FIRE LIMITS. CERTAIN RESTICTIONS
 MAY APPLY, SEE APPENDIX F, LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 13. BUILDING ADDRESS REQUIRED. A
 MINIMUM OF 6" HIGH NUMBERS ARE
 REQUIRED.
  
 14. PLEASE CLEARLY ILLUSTRATE PORTABLE
 FIRE EXTINGUISHER LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL