| Date |
Text |
| 2004-12-27 00:00:00 | 1. ALL DEMOLITION, RENOVATION AND |
| | CONSTRUCTION TO COMPLY WITH |
| | NFPA 241. |
| | |
| | 2. WHAT PROVISIONS MADE FOR FIRE |
| | AND PARAMEDICAL ACCESS THRU THE |
| | SLIDING GATE. |
| | |
| | 3. FLORIDA FIRE PREVENTION CODE |
| | NOT MENTIONED IN CODE COMPLIANCE |
| | BOX. |
| | |
| | 4. GENERAL NOTES AND CODE COMPLIANCE |
| | BOX WITH REGARDS TO FIRE SPRINKLERS |
| | DO NOT MATCH. |
| | |
| | 5. SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR ANY HOOD, DUCT, AND FIRE |
| | SUPPRESSION SYSTEMS. |
| | |
| | 6. HOW ARE PERSONS DIRECTED TO EXIT |
| | DOOR IN ENTRY AREA 100. |
| | |
| | 7. NO EMERGENCY LIGHTING COULD BE |
| | LOCATED IN THE KITCHEN. WHAT DIRECTS |
| | PERSONS TO THE EXITS SHOULD POWER |
| | FAIL. |
| | |
| | 8. PLEASE PROVIDE PRODUCT APPROVALS FOR |
| | GREASE DUCT WRAP. |
| | |
| | 9. PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATIONS FOR WALLS AND CEILINGS. |
| | |
| | 10. EXIT SIGN MISSING FROM REFLECTED |
| | CEILING PLAN ENTRY 100. |
| | |
| | 11. PANIC HARDWARE REQUIRED ON ALL |
| | EXIT DOORS. |
| | |
| | 12. BUILDING MAY BE LOCATED IN CITY |
| | FIRE LIMITS. CERTAIN RESTICTIONS |
| | MAY APPLY, SEE APPENDIX F, LOCAL |
| | AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE. |
| | |
| | 13. BUILDING ADDRESS REQUIRED. A |
| | MINIMUM OF 6" HIGH NUMBERS ARE |
| | REQUIRED. |
| | |
| | 14. PLEASE CLEARLY ILLUSTRATE PORTABLE |
| | FIRE EXTINGUISHER LOCATIONS. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |