| 2004-12-14 00:00:00 | NOTES TO FOLLOW. |
| | ************** UNSAT****************** |
| | SWEET TOMATOES |
| | ********** PLAN REVIEW ONLY************ |
| | *******NOT SUBMITTED FOR |
| | PERMIT.******** |
| | |
| | 1)NOTE: PLEASE HAVE PLANS SIGNED, DATED |
| | AND SEALED BY THE ARCH'S AND ENGINEERS |
| | OF RECORD WHEN SUBMITTING FOR PERMIT. |
| | PER FS 481.221,471.025 |
| | |
| | 2)NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCKS FOR ARCHITECT |
| | AND ENGINEERING FIRMS. |
| | FAC 61G15-23.002, FAC 61G1-16.004 |
| | FS 481.219,471.023. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR |
| | ALL TRADES WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 3)NOTE: PLEASE SEE 600.5 EACH |
| | COMMERCIAL |
| | BUILDING AND EACH COMMERCIAL OCCUPANCY |
| | ACCESSIBLE TO PEDESTRIANS SHALL BE |
| | PROVIDED WITH AT LEAST ONE OUTLET IN AN |
| | ACCESSIBLE LOCATION AT EACH ENTRANCE TO |
| | EACH TENANT SPACE FOR SIGN OR OUTLINE |
| | LIGHTING SYSTEM USE. THE OUTLET(S) |
| | SHALL |
| | BE SUPPLIED BY A BRANCH CIRCUIT RATED |
| | AT |
| | LEAST 20 AMPERES THAT SUPPLIES NO OTHER |
| | LOAD. SERVICE HALLWAYS OR CORRIDORS |
| | SHALL NOT BE CONSIDERED ACCESSIBLE TO |
| | PEDESTRIANS. THIS CIRCUIT COULD NOT BE |
| | LOCATED ON PANEL SCHEDULE. |
| | |
| | 4)NOTE: PLEASE PROVIDE ROOM/AREA |
| | DESIGNATION ON PLANS. |
| | |
| | 5)NOTE: PLEASE SEE SECTION 210.8(B)(3) |
| | IN THE 2002 CODE WHICH REQUIRES ALL 15- |
| | AND 20-AMPERE, 125-VOLT RECEPTACLES IN |
| | NONDWELLING-TYPE KITCHENS TO BE GFCI |
| | PROTECTED. THIS REQUIREMENT APPLIES TO |
| | EACH AND EVERY 15- AND 20-AMPERE, |
| | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR |
| | NOT THE RECEPTACLE SERVES COUNTERTOP |
| | APPLIANCES. |
| | |
| | 6)NOTE: PLEASE SEE 220.12 FOR TRK |
| | LIGHTING CALCULATIONSTO BE SHOWN. |
| | |
| | 7)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 8)NOTE: PLEASE SEE 210.62 FOR REQUIRED |
| | MISSING RECEPTS.AT LEAST ONE RECEPTACLE |
| | OUTLET SHALL BE INSTALLED DIRECTLY |
| | ABOVE |
| | A SHOW WINDOW FOR EACH 3.7 LINEAR M (12 |
| | FT) OR MAJOR FRACTION THEREOF OF SHOW |
| | WINDOW AREA MEASURED HORIZONTALLY AT |
| | ITS |
| | MAXIMUM WIDTH. |
| | |
| | 9)NOTE: PLEASE CORRELATE RISER "LD" |
| | WITH |
| | EQUIPMENT SHOWN ON E0.1. PLEASE SEE |
| | OCP, |
| | AWG ETC. |
| | |
| | 10)NOTE: PLEASE SEE PROVIDE A "PANEL |
| | SCHEDULE" FOR LD SHOWING OVERCURRENT |
| | PROTECTION, CONDUCOTR SIZES, CONDUIT |
| | ETC. |
| | PLEASE SEE THERE ARE MANY ITEMS ON LD |
| | WHICH CONDUCTOR SIZES ETC COULD NOT BE |
| | LOCATED. |
| | 215.5 |
| | |
| | 11)NOTE: PLEASE IDENTIFY KW OF HEAT ON |
| | A/C, RTU'S. |
| | PLEASE SEE 424.3B FOR OCP.THE AMPACITY |
| | OF THE BRANCH-CIRCUIT CONDUCTORS AND |
| | THE |
| | RATING OR SETTING OF OVERCURRENT |
| | PROTECTIVE DEVICES SUPPLYING FIXED |
| | ELECTRIC SPACE-HEATING EQUIPMENT |
| | CONSISTING OF RESISTANCE ELEMENTS WITH |
| | OR WITHOUT A MOTOR SHALL NOT BE LESS |
| | THAN 125 PERCENT OF THE TOTAL LOAD OF |
| | THE MOTORS AND THE HEATERS. |
| | |
| | 12)NOTE: PLEASE SEE PANEL SCHEDULES, |
| | SOME ARE SHOWN WHERE ARE CIRCUITS ARE |
| | INDICATED AS 1-POLE BRKRS? PLEASE SEE |
| | SOME 2-P CIRCUITS. |
| | |
| | 13)NOTE: PLEASE SEE SOME EQUIPMENT ON |
| | EQP SCH DOES NOT APPEAR ON PANEL |
| | SCHEDULES OR RISER? |
| | PLEASE CORRRELATE. |
| | 215.5 |
| | |
| | 14)NOTE: PLEASE PROVIDE EQUIPMENT |
| | GROUNDING CONDUCTORS FOR ALL AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | 250.24,250.110,250.122 |
| | |
| | 15)NOTE: PLEASE SEE 250.66 FOR SIZING |
| | OF |
| | GROUNDING ELECTRODE CONDUCTOR. THIS IS |
| | TO BE BASED ON SEC'S PER NEC. |
| | |
| | 16)NOTE: PLEASE VERIFY WITH FPL IF |
| | SEC'S |
| | (SERVICE ENTRANCE CONDUCTORS) WILL BE |
| | BROUGHT INTO 1200A MAIN "LD" BY FPL? |
| | PLEASE SEE RISER DIAGRAM DOES NOT |
| | INDICATE AN METERING DEVICE, CT , ETC. |
| | PLEASE SEE 2004 FPL SERVICE |
| | SPECIFICATIONS AND REQUIREMENTS. |
| | |
| | ************ PLEASE NOTE ************* |
| | DUE TO ABOVE COMMENTS AND MISSING |
| | INFORMATION, A COMPLETE REVIEW FOR CODE |
| | COMPLIANCE MAY NOT BE DONE AT THIS |
| | TIME. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWS WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SEE MANY OF THE ABOVE ITEMS HAVE |
| | BEEN REDLINED ON PLANS FOR AREAS OF |
| | CONCERN AND NOTES. |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW |
| | AND |
| | STAMPING. |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |