Plan Review Notes
Plan Review Notes For Permit 04111429
Permit Number 04111429
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-14 00:00:00NOTES TO FOLLOW.
 ************** UNSAT******************
 SWEET TOMATOES
 ********** PLAN REVIEW ONLY************
 *******NOT SUBMITTED FOR
 PERMIT.********
  
 1)NOTE: PLEASE HAVE PLANS SIGNED, DATED
 AND SEALED BY THE ARCH'S AND ENGINEERS
 OF RECORD WHEN SUBMITTING FOR PERMIT.
 PER FS 481.221,471.025
  
 2)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS FOR ARCHITECT
 AND ENGINEERING FIRMS.
 FAC 61G15-23.002, FAC 61G1-16.004
 FS 481.219,471.023.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3)NOTE: PLEASE SEE 600.5 EACH
 COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY
 ACCESSIBLE TO PEDESTRIANS SHALL BE
 PROVIDED WITH AT LEAST ONE OUTLET IN AN
 ACCESSIBLE LOCATION AT EACH ENTRANCE TO
 EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING SYSTEM USE. THE OUTLET(S)
 SHALL
 BE SUPPLIED BY A BRANCH CIRCUIT RATED
 AT
 LEAST 20 AMPERES THAT SUPPLIES NO OTHER
 LOAD. SERVICE HALLWAYS OR CORRIDORS
 SHALL NOT BE CONSIDERED ACCESSIBLE TO
 PEDESTRIANS. THIS CIRCUIT COULD NOT BE
 LOCATED ON PANEL SCHEDULE.
  
 4)NOTE: PLEASE PROVIDE ROOM/AREA
 DESIGNATION ON PLANS.
  
 5)NOTE: PLEASE SEE SECTION 210.8(B)(3)
 IN THE 2002 CODE WHICH REQUIRES ALL 15-
 AND 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.
  
 6)NOTE: PLEASE SEE 220.12 FOR TRK
 LIGHTING CALCULATIONSTO BE SHOWN.
  
 7)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 8)NOTE: PLEASE SEE 210.62 FOR REQUIRED
 MISSING RECEPTS.AT LEAST ONE RECEPTACLE
 OUTLET SHALL BE INSTALLED DIRECTLY
 ABOVE
 A SHOW WINDOW FOR EACH 3.7 LINEAR M (12
 FT) OR MAJOR FRACTION THEREOF OF SHOW
 WINDOW AREA MEASURED HORIZONTALLY AT
 ITS
 MAXIMUM WIDTH.
  
 9)NOTE: PLEASE CORRELATE RISER "LD"
 WITH
 EQUIPMENT SHOWN ON E0.1. PLEASE SEE
 OCP,
 AWG ETC.
  
 10)NOTE: PLEASE SEE PROVIDE A "PANEL
 SCHEDULE" FOR LD SHOWING OVERCURRENT
 PROTECTION, CONDUCOTR SIZES, CONDUIT
 ETC.
 PLEASE SEE THERE ARE MANY ITEMS ON LD
 WHICH CONDUCTOR SIZES ETC COULD NOT BE
 LOCATED.
 215.5
  
 11)NOTE: PLEASE IDENTIFY KW OF HEAT ON
 A/C, RTU'S.
 PLEASE SEE 424.3B FOR OCP.THE AMPACITY
 OF THE BRANCH-CIRCUIT CONDUCTORS AND
 THE
 RATING OR SETTING OF OVERCURRENT
 PROTECTIVE DEVICES SUPPLYING FIXED
 ELECTRIC SPACE-HEATING EQUIPMENT
 CONSISTING OF RESISTANCE ELEMENTS WITH
 OR WITHOUT A MOTOR SHALL NOT BE LESS
 THAN 125 PERCENT OF THE TOTAL LOAD OF
 THE MOTORS AND THE HEATERS.
  
 12)NOTE: PLEASE SEE PANEL SCHEDULES,
 SOME ARE SHOWN WHERE ARE CIRCUITS ARE
 INDICATED AS 1-POLE BRKRS? PLEASE SEE
 SOME 2-P CIRCUITS.
  
 13)NOTE: PLEASE SEE SOME EQUIPMENT ON
 EQP SCH DOES NOT APPEAR ON PANEL
 SCHEDULES OR RISER?
 PLEASE CORRRELATE.
 215.5
  
 14)NOTE: PLEASE PROVIDE EQUIPMENT
 GROUNDING CONDUCTORS FOR ALL AFTER THE
 FIRST MEANS OF DISCONNECT.
 250.24,250.110,250.122
  
 15)NOTE: PLEASE SEE 250.66 FOR SIZING
 OF
 GROUNDING ELECTRODE CONDUCTOR. THIS IS
 TO BE BASED ON SEC'S PER NEC.
  
 16)NOTE: PLEASE VERIFY WITH FPL IF
 SEC'S
 (SERVICE ENTRANCE CONDUCTORS) WILL BE
 BROUGHT INTO 1200A MAIN "LD" BY FPL?
 PLEASE SEE RISER DIAGRAM DOES NOT
 INDICATE AN METERING DEVICE, CT , ETC.
 PLEASE SEE 2004 FPL SERVICE
 SPECIFICATIONS AND REQUIREMENTS.
  
 ************ PLEASE NOTE *************
 DUE TO ABOVE COMMENTS AND MISSING
 INFORMATION, A COMPLETE REVIEW FOR CODE
 COMPLIANCE MAY NOT BE DONE AT THIS
 TIME.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SEE MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINED ON PLANS FOR AREAS OF
 CONCERN AND NOTES.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW
 AND
 STAMPING.
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]